LEFM 3xxCi User Manual
IB1406 Rev 12
Section 5
Page 26
August 2017
Transmitter Connections – All Models
The physical properties, acoustic properties, and calibration of the meter body are pre-programmed
into the transmitter; therefore, the meter body and transmitter are manufactured as a matched set
and must be installed as a pair. Failure to install transmitters and meter bodies as matched sets
can result in erroneous flow measurements.
Transmitter Installation Procedure
Important
All equipment should be installed by a licensed electrician in accordance with NEC/CEC or local codes.
At a minimum, install a disconnect switch in series with the transmitter power input.
Note –
•
All wiring to and from the transmitter must be routed through grounded/shielded metal conduit or
equivalent that meets site environment specifications.
•
All power connections from site shall go through a properly rated equipment switch or circuit
breaker employed as a disconnecting device (see Section 1, Table 1.2 for ratings). This switch
shall be easily accessed for and be marked as the disconnecting switch for the transmitter. This
switch shall meet the requirements of IEC 60947-1 and IEC 60947-3 and site electrical codes.
Note – Conductor insulation for external circuits must be rated for a voltage of 300V and a minimum
temperature of at least 85ºC.
Transmitter Location
To ensure that the proper supply voltage reaches the transmitter, the distance between the transmitter and
its power source must be less than that given in the below table (based on the wire gage used):
Wire Gage
Max Distance
(Meters)
Max Distance
(Feet)
12
1082.2
3550.4
14
679.7
2229.8
16
429.0
1407.3
18
269.1
882.9
20
169.1
554.6
22
106.3
348.6
24
66.9
219.6
CAUTION