LEFM 3xxCi User Manual
IB1406 Rev 12
Section 2
Page 9
August 2017
Note – When attached to a junction box, the total could surpass 135 lbs (61 kg),
depending on the junction box material
Power Requirements – DC Power
Voltage Req’d 24 VDC (18 VDC to 30 VDC)
Current Draw 0.25 A at 24 VDC
Power Consumption 6 W
Power Requirements – AC Power
Voltages 120 (60 Hz) / 230 (50 Hz) VAC
Voltage Range (108 VAC to 253 VAC)
Frequency Range (47 Hz to 63 Hz)
Current Draw 0.14 A
Power Consumption 7.3 W
Pulse Outputs
Pulse/Direction Outputs (4 Total) 0-5 V or 0-12 V
Alarm Status (4 Total) 5V or 12 V = normal operation
0V = alarm condition
Communications
RS485 (up to 3 total) 2 Wire – Modbus RTU
Ethernet Copper or Fiber
HART Optional
Analog Outputs (2 total)
4-20 mA
(max load 650 Ohms)
Analog Inputs
(3 total)
4-20 mA
Meter body RTD is standard