CS3000 User’s Guide
48
Calsense
To view this real-time information:
1.
From Main Menu, navigate to
Diagnostics
and select
Live Screens
. The Live Screens menu
displays.
2.
Navigate to and select
Weather Status
. Weather Status screen displays.
Assigning Moisture Sensors to Station Groups
The Assign Moisture Sensors to Station Groups feature provides the ability to assign discovered
moisture sensors to station groups.
To edit the Soil Moisture Sensors screen (Figure 37):
1.
From Main Menu, navigate to
Setup
and select
2-Wire
. The 2-Wire dialog displays.
2.
Navigate to and select
Assign Moisture Sensors to Station Groups
. The Moisture Sensor screen
displays.
3.
Navigate to the left column and select the desired moisture sensor by serial number.
4.
Navigate to and select Sensor Name to edit the name with the pop-up keyboard. Select
OK
when done.
5.
Navigate to and select
Assign Sensor to Station Groups
. The Station Groups screen displays.
6.
Navigate to and select the desired Station Group.
7.
Navigate to the Moisture sensor field and use +/- to select a moisture sensor for the Station
Group.
8.
Press
BACK
to save changes and return to Soil Moisture Sensors screen.
9.
Navigate to the Moisture tab:
a.
Navigate to If set point is crossed and use +/- to select desired action: Do nothing or
Generate an alert.
b.
Navigate to Wet set point and use +/- to change to the desired number.
c.
Navigate to Dry set point and use +/- to change to the desired number.
10.
Navigate to the Temperature tab.
a.
Navigate to If high temp is crossed and use +/- to select desired action: Do nothing or
Generate an alert.
Figure 37: Soil Moisture Sensors Screen