Burn  hazard.  Due  to  high  temperature  of  the

fluid,  the  pump  casing  and  the  motor  may

reach temperatures higher than 50°C.
DO  NOT  TOUCH  these  parts  unless  with

suitable  protective  devices  or  wait  and  make

sure they have completely cooled.

To start the pump.  If the shaft turns in the wrong direc-

tion, a red warning light will begin to flash. 

7.3 Perfomance settings of the pump

ATTENTION:  Turn  off  the  power  supply  before

performing the change of the speed.

To modify pump performance (head) according to need it

is necessary to remove the upper cover (Fig.2 – POS.2).

To  change  the  speed  move  the  speed  selector  (Fig.4

page 44 ) to the desired speed.

7.4 Switch off of the pump

The appliance must be switch off every time there

are faults. (see troubleshooting).

The product is designed for a continuous duty,  the swit-

ch off is performed by disconnecting the power supply by

means  the  expected  disconnecting  devices.  (see  para-

graph "6.5 Electrical connection").

8 MAINTENANCE

Before  any  operations  it's  necessary  to  disconnect  the

power supply. 

If  required  ask  to  an  electrician  or  to  an  expert  techni-

cian.

Every  maintenance  operations,  cleaning  or

reparation  executed  with  the  electrical  system

under  voltage,  it  could  cause  serious  injuries  to

people.

In  case  of  extraordinary  maintenance,  or  maintenance

operations that require part-removing, the operator must

be  a  qualified  technician  able  to  read  schemes  and

drawings.
It is suggest to  register all maintenance operation execu-

ted. 

During  maintenance  keep  particular  attention  in

order  to  avoid  the  introduction  of  small  external

parts, that could compromise the device safety.
It is forbidden to execute any operations with the

direct use of hands. Use water-resistant, anti-cut

gloves  to  disassemble  and  clean  the  filter  or  in

other particular cases.

During 

maintenance 

operations 

external

personnel is not allowed.

Maintenance  operations  that  are  not  described  in  this

manual must be made only by special personnel authori-

zed by Calpeda S.p.A.
For further technical information regarding the use or the

maintenance of the device, contact Calpeda S.p.A.

8.1 Routine maintenance

Before every maintenance operations disconnect the

power supply and make sure that the device could

not accidentally operate.

The pumps are made to function for many years in nor-

mal conditions with no need for maintenance. 
If unused for long periods of time, the pump may seize up.

The  following  procedure  must  be  used  to  unblock  the

pump.
- close the delivery sluice gate;
- unscrew  the  vent  cap  and  turn  the  pump  shaft  with  a

screwdriver (fig. 2 – POS. 5) until the pump is unblocked;

- close the vent cap and open the delivery sluice gate.
The  red  flashing  light  communicates  the  number  of  the

defect.

9. DISPOSAL

The final disposal of the device must be done by speciali-
zed company.
Make sure the specialized company follows the classifica-
tion of the material parts for the separation. 
Observe  the  local  regulations  and  dispose  the  device
accordingly  with  the  international  rules  for  environment
protection.

10 SPARE PARTS
10.1 Spare-parts request

When  ordering  spare  parts,  please  quote  the  data  stam-
ped on the name-plate (type, date and serial number).

The spare parts request shall be sent to CALPEDA S.p.A.
by phone, fax, e-mail.

11. Troubleshooting

WARNING:

Turn  off  the  power  supply  before  performing

any operations.

Do not allow the pump or motor to run  when dry even for

a short period

Strictly follow the user instructions and if necessary con-

tact an authorised service centre.

The  flashing  red  light  communicates  the  number  of  the
defect.    Each  series  of  flashes  is  separated  by  a  longer
interval, the number of flashes between intervals indicates
the defect code. 

Changes reserved.

OFF

OFF

i

OFF

i

ON

GB

NC, NCD Rev. 2 - Operating Instructions

Page 9 / 48

Error

cod

2

3

4

5

Description of the error

Voltage too low or phase missing. 

Check

the power supply.

Overheated  pump  motor.

If  the  error

occures 3x, turn the power off and then on. 
If  the  error  occures  in  spite  of  moderate
temperature of the media, service is needed.

Internal  connection  error  is  identified.

Turn  the  power  off  and  then  on.  In  case  it
does not help, service is needed.

Wrong  direction  of  rotation. 

Interchange

two voltage phases.

Red light

IST ND_NCD 02_2016_MXS 11_03con gall  29/03/16  09:49  Pagina 9

Содержание NC Series

Страница 1: ...3 hastighets Circulatiepompen met 3 snelheden NC NCD ISTRUZIONI ORIGINALI PER L USO Pagina 2 Italiano OPERATING INSTRUCTIONS Page 6 English BETRIEBSANLEITUNG Seite 10 Deutsch INSTRUCTIONS POUR L UTILI...

Страница 2: ...zione Indica l obbligo di uso di dispositivi di protezione individuale protezione delle mani Interventi che devono essere svolti con l apparecchio spento e scollegato dalle fonti di energia Interventi...

Страница 3: ...deve essere messo in funzione in caso di difetti o parti danneggiate Le operazioni di manutenzione ordinaria e straor dinaria che prevedono uno smontaggio anche parziale dell apparecchio devono essere...

Страница 4: ...e l isolamento del solo corpo pompa figura 2 3 POS 15 6 5 Collegamento elettrico Il collegamento elettrico deve essere eseguito da un elettricista qualificato nel rispetto delle prescrizioni locali Se...

Страница 5: ...contattare CALPEDA S p A 8 1 Manutenzione ordinaria Prima di ogni intervento di manutenzione togliere l alimentazione elettrica e assicurarsi che la pompa non rischi di essere messa sotto tensione per...

Страница 6: ...ions related to the maintenance of the device Indicates that it is mandatory to use individual protection devices Operations that must be done with the device switched off and disconnected from the po...

Страница 7: ...device must be done only after disconnection from the supply 4 2 Safety devices The device has an external case that prevents any con tact with internal parts 4 3 Residual risks The appliance designed...

Страница 8: ...ody of the pump must be insulated figures 2 3 POS 15 6 5 Electrical connection Electrical connection must be carried out only by a qualified electrician in accordance with local regulations Follow all...

Страница 9: ...or the maintenance of the device contact Calpeda S p A 8 1 Routine maintenance Before every maintenance operations disconnect the power supply and make sure that the device could not accidentally ope...

Страница 10: ...tem Techniker vorzunehmen sind welcher das Ger t unter normalen Umst nden korrekt betreiben kann und dazu berechtigt ist s mtliche Wartungs Einstellungs und Reparaturma nahmen an mechanischen Teilen v...

Страница 11: ...angebracht werden Das Ger t darf nicht betrieben werden falls M ngel oder Besch digungen festzulegen sind Alle Wartungs und Instandhaltungsarbeiten bei denen das Ger t v llig oder teilweise abzumonti...

Страница 12: ...systemen frei bleiben wenn ausschlie lich nur die Isolierung des blo en Pumpengeh uses durchgef hrt wird Abb 2 3 POS 15 6 5 Elektrischer Anschlu Der elektrische Anschlu ist von Fach personal unter Bea...

Страница 13: ...es 8 1 Ordentliche Wartung Vor jeglicher Wartungsarbeit ist das Ger t vom Stromnetz zu trennen und sicherzustellen dass die Pumpe nicht unerw nscht wieder unter Spannung gesetzt werden darf Die Pumpen...

Страница 14: ...Obligation du port des dispositifs de protection individuelle protection des mains Interventions r alisables seulement avec l appareil teint et d branch des sources d nergie Interventions r alisables...

Страница 15: ...is en marche en cas de d fauts ou de parties endommag es Les op rations de maintenance ordinaire et extraordinaire qui pr voient le d montage m me partiel de l appareil doivent tre effectu es uniqueme...

Страница 16: ...ge lorsque uniquement l isolation du seul corps pompe est effectu e figure 2 3 POS 15 6 5 Connexion lectrique La connexion lectrique doit tre ex cut e par un sp cialiste suivant les prescriptions loca...

Страница 17: ...Avant toute intervention de maintenance couper l alimentation lectrique et s assurer que la pompe ne risque pas d tre mise sous tension par inadvertance Les pompes ont t con ues pour fonctionner plusi...

Страница 18: ...parato Indica la obligaci n de utilizar los dispositivos de protecc n individual protecci n de las manos Intervenciones que deben ser realizadas con el dispositivo apagado y desconectado de las fuente...

Страница 19: ...el fabricante en el dispositivo El dispositivo no debe ser puesto en funciona miento en presencia de defectos o piezas da a das Las operaciones de mantenimiento ordinario y extraordinario que implica...

Страница 20: ...POS 15 6 5 Conexionado el ctrico El conexionado el ctrico tiene que ser realizado por un electricista cualificado y cumpliendo las prescripciones locales Seguir las normas de seguridad Realizar una to...

Страница 21: ...ngase en contacto con CALPEDA S p A 8 1 Mantenimiento ordinario Antes de cualquier operaci n de mantenimiento desconecte la fuente de alimentaci n y aseg rese de que la bomba no pueda recibir tensi n...

Страница 22: ...riska och mekaniska tg rder i samband med s rskilt underh ll av apparaten Indikerar skyldigheten att anv nda personlig skyddsutrustning skyddshandskar Ingrepp som m ste utf ras n r apparaten r avst ng...

Страница 23: ...r ndra m rkskyltar som anbringats p apparaten av tillverkaren Apparaten f r inte s ttas ig ng om det finns fel eller skadade delar L pande och s rskilt underh llsarbete som f rut ser en nedmontering v...

Страница 24: ...nder i v rmesystemen n r endast isoleringen av hela pumpenheten utf rs figur 2 3 POS 15 6 5 Elanslutning Elinstallationen m ste utf ras av en beh rig elektriker och i enlighet med lokala best mmelser...

Страница 25: ...on om anv ndning eller underh ll av apparaten var god kontakta CALPEDA S p A 8 1 L pande underh ll Fr nkoppla elf rs rjningen och s kerst ll att pumpen inte riskerar att oavsiktligen sp nningsf ras in...

Страница 26: ...te gebruiken en bevoegd is om alle ingrepen van mechanische aard voor het onderhoud de afstelling of ter reparatie uit te voeren Geeft de verplichting aan om persoonlijke bescher mingsmiddelen te gebr...

Страница 27: ...et ingeschakeld worden in het geval van defecten of beschadigde onderdelen De handelingen voor het gewone en buitengewo ne onderhoud waarvoor een deel van het appa raat gedemonteerd moet worden mogen...

Страница 28: ...rmingssystemen wanneer alleen de isolatie van uitsluitend het pomplichaam wordt uitgevoerd figuur 2 3 POS 15 6 5 Elektrische aansluiting De elektrische aansluiting moet uitgevoerd worden door een gekw...

Страница 29: ...derhoud van de machine kunt u contact opnemen met de firma Calpeda S p A 8 1 Gewoon onderhoud Alvorens enige onderhoudswerkzaamheid uit te voeren moet de elektrische stroom worden uitgeschakeld en gec...

Страница 30: ...33 11 33 12 42 12 1 42 47 1 Calpeda SpA 2 3 1 1 E E 1 2 Calpeda S p A Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 1 4 1 5 1 5 Calpeda S p A 1 2 2 NC NCD 2 1 50 1...

Страница 31: ...250 DN mm dm mm 3 3 1 12 1 1450 2900 rpm IP 44 230 V 1 50 Hz 400 V 3 50 Hz 200 70 dB A 1 MPa 10 bar 3 2 40 C 4 4 1 CALPEDA S p A 4 2 4 3 4 4 4 5 5 12 1 5 1 25 kg 12 1 6 6 1 12 1 6 2 3 2 6 3 i i i IST...

Страница 32: ...32 48 NC NCD Rev 2 GR 6 4 1 2 1 6 4 1 2 3 15 6 5 L 2 2 3 mm 7 7 1 7 2 1 5 50 C OFF OFF 2 2 3 2 4 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 32...

Страница 33: ...8 NC NCD Rev 2 GR 7 3 c 2 POS 2 4 44 c 8 7 4 OFF 6 5 8 CALPEDA SpA CALPEDA SpA 8 1 2 5 9 10 10 1 CALPEDA S p A 11 OFF OFF i OFF ON i 2 3 4 5 3 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagin...

Страница 34: ...0 37 11 37 12 42 12 1 42 47 1 Calpeda S p A 2 3 CE 1 1 1 2 Calpeda S p A Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 1 4 1 5 1 5 Calpeda S p A 1 2 2 NC NCD 2 1 50...

Страница 35: ...2 3 NC D G 40 F 120 250 DN 3 3 1 12 1 1450 2900 IP 44 230 V 1 50 400 V 3 50 200 70 dB A 1 10 3 2 40 4 4 1 Calpeda S p A 4 2 4 3 4 4 4 5 5 12 1 5 1 25 12 1 6 6 1 12 1 6 2 3 2 i IST ND_NCD 02_2016_MXS...

Страница 36: ...C 36 48 NC NCD Rev 2 RU 6 3 6 4 1 fig 2 POS 1 6 4 1 2 3 15 6 5 2 2 3 7 7 1 7 2 1 5 50 C OFF OFF i 2 2 3 2 4 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 36...

Страница 37: ...C 37 48 NC NCD Rev 2 RU 7 3 2 2 4 44 7 4 6 5 8 Calpeda S p A Calpeda S p A 8 1 2 5 9 10 10 1 Calpeda S p A 11 OFF OFF OFF ON i i 2 3 4 5 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 37...

Страница 38: ...11 41 12 42 12 1 42 47 1 CALPEDA S P A 2 3 CE 1 1 1 2 CALPEDA S P A Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia www calpeda it 1 3 1 4 1 5 Calpeda S p A 1 2 2 NC NCD 2 1 50 10 C to...

Страница 39: ...F 120 250 mm dm mm 3 3 1 12 1 1450 2900rpm IP44 230 V 1 50 Hz 400 V 3 50 Hz 200 70 dB A 1Mpa 10bar 3 2 40 4 4 1 CALPEDA S P A 4 2 4 3 4 4 4 5 5 12 1 5 1 25 12 1 6 6 1 12 1 6 2 3 2 6 3 i i IST ND_NCD 0...

Страница 40: ...40 48 NC NCD Rev 2 6 4 1 2 POS 1 6 4 1 2 3 15 6 5 3mm 7 7 1 7 2 50 C OFF OFF 2 3 2 3 2 4 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 40...

Страница 41: ...41 48 NC NCD Rev 2 7 3 2 POS 2 4 44 7 4 6 5 8 CALPEDA CALPEDA S P A 8 1 2 5 9 10 10 1 CALPEDA S P A 11 OFF OFF ON i i OFF 2 3 4 5 3 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 41...

Страница 42: ...60 250 A NC 40 120 250 A NC4 50 40 280 A NC4 50 60 280 A NC 50 120 280 A NC4 65 30 340 A NC4 65 60 340 A NC 65 120 340 A NC4 80 60 360 A NC 80 120 360 A 17 4 17 7 17 9 24 24 3 24 6 28 6 28 6 30 8 32...

Страница 43: ...55 8 56 2 57 9 59 5 NCM 40 60 250 A NCM 40 120 250 A NCM4 50 60 280 A NCM 50 120 280 A 40 PN a 6 10 65 6 10 80 10 6 10 280 340 360 250 h1 mm mm 70 80 100 65 h2 250 252 257 198 AD 130 130 130 125 l1 11...

Страница 44: ...Velocit 2 Speed 2 Velocit 3 Speed 3 Impostazione delle prestazioni della pompa Perfomance settings of the pump Einstellung der Leistungen der Pumpe Param trer les prestations de la pompe Ajuste del r...

Страница 45: ...45 48 NC NCD Rev 2 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 45...

Страница 46: ...46 48 NC NCD Rev 2 IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pagina 46...

Страница 47: ...med bestemmelserne i Direktiv 2004 108 EC 2006 42 EC 2006 95 EC og er i overensstemmelse med de heri indeholdte standarder Kommissionens forordning nr 640 2009 D F E DK CALPEDA S p A intygar att pumpa...

Страница 48: ...s p a Via Roggia di Mezzo 39 36050 Montorso Vicentino Vicenza Italia Tel 39 0444 476476 Fax 39 0444 476477 E mail info calpeda it www calpeda com IST ND_NCD 02_2016_MXS 11_03con gall 29 03 16 09 49 Pa...

Отзывы: