PROPERTY TYPES & ENTRAPMENT PROTECTION
CM9-2 INSTALL ATION AND OWNER MANUAL V.3.1 | 2023.06.01
PAGE 04
Required Entrapment Protection
A
B1
B2
C
D
E
Class I - Residential
Intended for use in a home of one (1) to four (4) single family dwelings, garage or parking area associated
therewith
Swing Gate Requirements: Primary Device: A, C
Secondary Device (one required): A, B1, B2, C, D
Class II - Commercial
Intended for use in a commercial location or building such as a multi-family housing unit (five or more
single family units, hotel, garages, retail store or other building servicing the general public.
Swing Gate Requirements: Primary Device: A, C
Secondary Device (one required): A, B1, B2, C, D
Class III - Industrial
Intended for use in an industrial location or building such as a factory, loading dock area, or other locations
not intended to service the general public.
Swing Gate Requirements: Primary Device: A, B1, B2, C
Secondary Device (one required): A, B1, B2, D, E
Class IV - Restricted Access
Intended for use in a guarded industrial location or building such as a military base, hazardous chem sites,
or other restricted access locations, in which unauthorized access is prevented via supervision by staffs.
Swing Gate Requirements: Primary Device: A, B1, B2, C, D
Secondary Device (one required): A, B1, B2, C, D, E
NOTE: A minimum of 2 independent entrapment protection devices are required for each direction of travel.
The same type of device shall not be utilized for both the primary & secondary entrapment protection means
Use of a single device to cover both the opening & closing directions is in accordance with the requriement;
however, a single device is not required to cover both directions.
Inherent (built-in) Entrapment Protection System
Non-contact sensor such as a photosensor or equivalent
Contact sensor such as edge sensor or equivalent
Inherent adjustable clutch or pressure relief device
Actuation device requiring contrinuous pressure to maintain gate motion
Inherent Audio Alarm
-
-
-
-
-
-