INSTALLATION

ALS

600T-AD

2019.12.5 Rev 2

Dimming Protocol & Wiring Diagrams (0-10V)

0-10V DIMMER RATINGS

The stated VA (volt-ampere) rating is the rated capacity of the dimmer which includes the 
electronic transformer heat losses and the lamp load. A transformer dissipates less than 20% 
of the connected load as heat. The lamp load plus the transformer loss determine the dimmer 
capacity required. See the example below.

LED Lighting

TRAXXX-E

20% of Lamp Load lost as heat

(19.2W = 20% of 72W)

480W Lamp Load

(4W x 18’ = 72W)

Lamp Load + Heat Loss

(72W + 19.2W = 91.2W)

Dimmer must be rated to at least 91.2W

DIMMING PROTOCOL 

(0-10V: 1% Dimming)

ALS600T is available in 120 or 277 volts with a dimmable integral or remote driver. The driver 
is available with 0-10V dimming capabilities. Consult factory for other dimming protocols 
available. The following applies to 0-10V dimming interfaces. A 0-10v fluorescent dimmer will 
not dim the LEDs.

Technical Requirements For Control Equipment

• The light output of the LEDs operated by the controllable LED driver is controlled by DC voltage
   applied to the control input leads (grey and violet). The actual response curve of LED driver
   current versus control voltage.
• The control device must be capable of accepting, or sinking, the DC current flow from the
   driver. The DC current from the driver that must be sinked by the control circuit is
   150uA (+/50% for isolated dim interfaces, up to 1.5mA for non-isolated dim interfaces).
• If the control bus is opened, or if the control device internally opens the control bus under
   some conditions, the voltage on the control bus will then be a function of the drivers, which is
   10-15V. Maximum light output will be delivered under this condition.
• If the control bus is shorted either by a mechanical switch in the control or by the circuitry of
   the control device, or inadvertently in the wiring, the current on the control bus will be less
   than 1.5mA.
• As can be determined from the two items, simple two-level operation of the drivers can be
   achieved by proper usage and application of a simple open/closed switch on the control bus
   with maximum light being achieved when the switch is open and minimum light with the
   switch is closed.
• The driver is intended to be used with control voltages between 0-10VDC volts peak maximum
   on the driver control leads.
• Control equipment intended to control more than one driver must be capable of sinking the
   current supplied to the control bus by the maximum number of drivers specified for the control
   device. At any given level setting it must maintain control bus voltage constant within a range
   of ±5% as the number of drivers connected to the control bus varies from a minimum of one
   driver up to the maximum number specified for the control device. 
• Driver of various ratings may be mixed on the same control system. 

DIMMING PROTOCOL 

(0-10V: 0% Dimming)

Technical Requirements For Control Equipment 

• The light output of the LEDs operated by the controllable LED driver is controlled by DC voltage
   applied to the control input leads (grey and violet). The actual response curve of LED driver
   current versus control voltage.
• The control device must be capable of accepting or sinking the DC current flow from the
   driver. The DC current from the driver that must be sinked by the control circuit is
   150uA (+/50% for isolated dim interfaces, up to 1.5mA for non-isolated dim interfaces).
• If the control bus is shorted either by a mechanical switch in the control or by the circuitry of
   the control device, or inadvertently in the wiring, the current on the control bus will be less
   than 1.5mA.
• As can be determined from the two items, simple two-level operation of the drivers can be
   achieved by proper usage and application of a simple open/closed switch on the control bus
   with maximum light being achieved when the switch is open and minimum light with the
  switch is closed.
• The driver is intended to be used with control voltages between 0-10VDC volts peak maximum
   on the driver control leads.

DIM- (Wire 4)

Neutral (Wire 2)

Hot (Wire 1)

Ground (Green)

DIM+ (Wire 3)

Primary Voltage
120-277V AC

0-10V Dimmer
(By others)

0-10V WIRING DIAGRAM (Dry or Wet Location)

Содержание alumLEDs ALS600T-AD-AA-SM Series

Страница 1: ...f LED colors and whites Available in 3 Watts up to 24 Watts Per Foot product is shipped in 1 2 3 and 4 luminaires Available for outdoor rated installations INSTALLATION RECOMMENDATIONS AlumLEDs can be...

Страница 2: ...nsult factory for any malfunctions Do not attempt to repair Only use alumLEDs with specified rated voltages Do not exceed the specified voltage for any alumLEDs luminaire Do not use alumLEDs extrusion...

Страница 3: ...e or inadvertently in the wiring the current on the control bus will be less than 1 5mA As can be determined from the two items simple two level operation of the drivers can be achieved by proper usag...

Страница 4: ...ew size Recommendation 8 32 x 1 screw Note Allow 0 25 clearance for lateral expansion of assembled mounting clips Only install mounting clips on flat even surfaces 2 Mark location where mounting clips...

Страница 5: ...imum of two mounting arms per fixture Mount arms 6 from center of mounting plate to end of fixture Refer to spacing diagrams for details 3 Mark location where mounting arms will be installed Screw arm...

Страница 6: ...ing is accurate according to the spacing diagram Set Screw 5 Loosen set screw until the mounting bracket can move freely Turn the mounting bracket until desired angle is achieved then mate the locking...

Страница 7: ...make changes or withdraw specifications without prior notice Page 7 of 11 INSTALLATION ALS600T AD 2019 12 5 Rev 2 Accessories ALS600T AD LVR 1 Place louvers onto top of extrusion ensuring internal opt...

Страница 8: ...n 1 Slightly unscrew Pivot Lock Knobs on both ends of fixture until Pivot Lock Bar and Upper Extrusion move freely Do not remove Pivot Lock Knob 2 Adjust as needed Use Angle Finder Markings on end cap...

Страница 9: ...en snap fixture into mounting clips Install set screws if necessary Set screws required for downward and outward facing applications Set Screw 4 If applicable connect disconnects between fixtures Push...

Страница 10: ...obe to a wire and the black probe to each other wire Repeat for each wire If a conductive path is formed between any of the wires the multimeter will beep flash or read 0 ohms Troubleshoot to identify...

Страница 11: ...carbonate 6 18AWG stranded 105 C stripped 3 8 tinned 60Hz PRODUCT FEATURES The Surge Series are 3 leaded devices that protect Line Ground Line Neutral and Neutral Ground in accordance with IEEE ANSI C...