5
1
2
3
L
POWER I N
N
POWER
T-SAT
CALL
ZONE 6
L
ZONE #1
PUMP
N
L
SEC
PUMP
N
STATUS DURING
ZONE #1 DEMAND
ZONE 1
END
SWITCH
MOTOR
ZONE 2
END
SWITCH
MOTOR
ZONE 3
END
SWITCH
MOTOR
ZONE 4
END
SWITCH
MOTOR
ZONE 5
END
SWITCH
MOTOR
ZONE 6
END
SWITCH
MOTOR
L
SYSTEM
PUMP
N
T-STAT 2
C
R
W
T
T COM
COMMS
D
P
ZONE 1
E / S
X X
T-STAT 3
C
R
W
T
T COM
T-STAT 1
C
R
W
T
T COM
T-STAT 4
C
R
W
T
T COM
T-STAT 5
C
R
W
T
T COM
T-STAT 6
C
R
W
T
T COM
AUX
O
N
O
F
F
O
N
O
F
F
VALVE
OPEN
1
2
3
4
5
2
2 1 3
4 1 3
White Rogers
1361
Zone Valve
4 wire
Zone Valve
2 wire
Taco
570
2
Wiring a standard zone valve to Caleffi Z-one Relay
Since a two wire actuator does not have an end switch for feedback
to the ZVR control, the end switch terminals must have a jumper to
simulate the end switch. If the end switch jumper is not installed, no
demand will be sent to the boiler and the pumps will not turn on
.
Wiring a Taco 570 valve to Caleffi Z-one Relay
When connecting the Taco 570 zone valve to the Caleffi Z-one Relay,
the wiring of this valve can only be done in one way. The left motor
terminal on the ZVR series control must be connected to terminal 2
on the zone valve. The right motor terminal must be connected to
terminal 1 on the zone valve. Lastly, the left end switch terminal
must be connected to terminal 3 on the zone valve. Failure to follow
schematic will lead to damage of product.
Wiring a White Rogers 1361 valve to Caleffi Z-one Relay
The White Rogers 1361 zone valve requires 24 VAC to terminal 2
at all times, therefor connect to the R terminal of the associated
T-STAT on the ZVR control. The left motor terminal on the ZVR
series control must be connected to terminal 4 on the zone valve.
The right motor terminal must be connected to terminal 1 on the
zone valve. Lastly, the left end switch terminal must be connected
to terminal 3 on the zone valve. The 1361 can not be used on any
zone when the ZVR control is set for priority.
Wiring zone valve to Caleffi ZVR control