47
Sequence of Operation / Settings
•
Master / Slave switch:
Master
•
Pump Exercise:
OFF
•
Priority:
OFF
•
AUX During Priority Demand:
OFF
•
Sec Pump Status During Zone 1 Demand
Jumper:
OFF
•
System Pump Status During Zone 1 Demand
Jumper:
ON
•
A demand occurs from a thermostat on zones
2-6 closing R to W. The “T-STAT CALL” LED
illuminates for the corresponding zone.
•
ZVR control sends 24 VAC to the corresponding
zone MOTOR terminals to open the zone
valve.
•
When the zone valve end switch closes,
the “VALVE OPEN” LED illuminates for the
corresponding zone. ZVR control sends
120 VAC to SYSTEM PUMP and SEC PUMP
outputs. The control will close the XX contacts
to signal the boiler of a demand.
•
If a demand occurs from the thermostat on
zone 1 closing R to W. The “T-STAT CALL” LED
and the “VALVE OPEN” LED will illuminate.
(When using a pump for zone 1 instead of a
zone valve a jumper must be installed on the
ZONE 1 END SWITCH terminals.) ZVR control
sends 120 VAC to the ZONE #1 PUMP.
•
When the thermostat demands from zones 2-6
are satisfied R to W will open and the “T-STAT
CALL” and “VALVE OPEN” LEDs will turn off.
24 VAC is dropped to the corresponding zone
MOTOR terminals.
Description of terminals
= Ground
N
= Neutral (Common leg of 120 VAC)
L
= Line (Hot leg of 120 VAC)
Thermostat terminals
R = 24 VAC
W = Heat call
C = Common of 24 VAC
Boiler terminals
XX
= Dry contact rated up to 120 VAC, 2 Amps,
which is typically connected to TT on boiler control,
closes when any zone calls including priority.
ZONE 1 E/S
= Dry contact rated up to 120 VAC,
2 Amps, will close with any call to ZONE 1. Zone
1 can be enabled as a priority zone, typically used
for heating domestic hot water. The ZONE 1 E/S
can be used to close a DHW contact on boiler
controls equipped with these features.
AUX
= Dry contact, rated up to 120 VAC, 2 Amps,
close when any zone calls and can be used
as
signal to a variable speed self regulated pump or
other controls.
Pump terminals
SYSTEM PUMP
= Runs when any zone calls for
heat.
SEC PUMP
= Runs when any zone calls for heat.
ZONE 1 PUMP
= Runs when zone 1 thermostat
calls for heat and zone 1 end switch has closed.
A jumper is required between the ZONE 1 END
SWITCH terminals when using a pump for ZONE
1 instead of a zone valve.
STATUS DURING ZONE 1 DEMAND ON / OFF:
When status jumper is placed on ON pins, the
secondary and / or system pump will continue to
operate during Zone 1 demand. When jumper is
placed on OFF pins, the corresponding pump will
be OFF during Zone 1 demand.
Valve terminals
Motor = 24 VAC to power the zone valve motor
End Switch = Connects to end switch on zone
valve. Must be jumped if using a 2–wire zone valve.
WARNING:
NEVER CONNECT R & C DIRECTLY,
this will be a direct short on the 24 VAC supply
•
If zone 1 thermostat is still calling for heat
the XX contacts will remain closed and the
SYSTEM PUMP and the ZONE #1 PUMP will
remain powered. 120 VAC will be dropped
to the SEC PUMP. (This is due to the jumper
position of the SEC PUMP for STATUS
DURING ZONE #1 DEMAND.)
•
When all the thermostat demands are satisfied
R to W will open and the “T-STAT CALL” and
“VALVE OPEN” LEDs will turn off. The X X
contacts will open terminating the demand for
heat to the boiler. The 120 VAC is dropped to
all of the PUMP outputs (SYSTEM PUMP, SEC
PUMP and ZONE #1 PUMP).
Содержание Z-one ZSR103
Страница 9: ...1 1...