EXAECO
®
HIGH EFFICIENCY RECOVERY UNIT
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-002
Ind D
Maj. 02/11/2018
Créé par : JC
Validé par : AR
Page 24/49
V.1.b. Temperature menu
(8)
Temperature setpoint setting (see chapter V.4.d)
AO
(analogue outputs)
Input/Output
Running mode
AO1: Y4 S-Suppl
(0V = recycling)
(10V = Fresh air)
...
DO
(Digital output)
DO1: Reg. AN
DO2: Reg. Recy
DO3: Heat demand
DO4: Cool demand
AO1: Y1 Heating.
AO2: Y2 Exchang.
AO3: Y3 Cool
AO4: Ctrl SAF
AO5: Ctrl EAF
AO Ext1
(analogue outputs)
DO1: V.freq SAF
DO2: V freq EAF
DO3: Rot exch. activ.
DO4: Heat Pump
DO5: Cool pump.
DO6: Surventil.activ
DO7: Somme alarme
DO Ext1
(Digital output)
Temperature.
Extract Temperature
Real:
Setpoint :
21°C (8)
...
Setpoint comp ext
-20°C =
25°C (8)
-15°C =
24°C (8)
-10°C =
23°C (8)
Consigne comp ext
-5°C =
23°C (8)
0°C =
22°C (8)
5°C =
20°C (8)
Setpoint comp ext
10°C =
18°C (8)
15°C =
18°C (8)
Outdoor temp :
Supply temp
Real :
Cons
Setpoint :