EXAECO
®
HIGH EFFICIENCY RECOVERY UNIT
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-002
Ind D
Maj. 02/11/2018
Créé par : JC
Validé par : AR
Page 30/49
V.5. Administrator settings
Activation of the
communication
,
dehumidification
and
fire function
requires an access to Configuration menu in system
level. You have to get the access rights to « Admin » level. Follow the instructions below:
Enter
1111
with directionnal arrows and validate with OK button. Press left arrow twice to reach the menu. In case of mistake
press C button twice and start again
V.5.a. Configuration menu with admin level access
Access rights
Enter
Quitter
Enter password
1111
Of the required autoris.
Current level :
ADMIN
Configuration
Communication
Système
Port 1
Esclave
1 et 2 Activation MODBUS RS485 and settings (see chapter V.6)
3 et 4 Activation BACNET MSTP and settings (see chapter V.6)
5 et 6 Settings TCP/IP(see chapter V.6)
7 et 8 Activation du BACNET IP and settings (see chapter V.6)
9 Adressage Repetiteur (voir chapitre V.6)
Communication
Modbus esclave
Port 1
Active (1)
Device name :
-
(4)
Mac :
0 (4)
Id appareil Bas :
2640
(4)
Id appareil Haut :
0 (4)
(x10000)
Vitesse :
9600
Bps
(4)
Ad. maître max :
127
(4)
Adresse Modbus :
1
(2)
Vitesse :
9600
Bps
(2)
2 bits d’arrêt :
Oui
(2)
Parité Non
(2)
Adresses
PLA :
254 (9)
ELA :
254 (9)
Communication
Bacnet
MSTP
Port 1
Active (3)
TCP/IP
IP :
- (6)
Subnet Mask
- (6)
Subnet Mask
- (6)
Gateway
- (6)
DHCP :
OUI (5)
Ip actuel
:
Communication
Bacnet IP
Active (7)
Device name :
-
(8)
Adresse BBMD :
0 (8)
Id appareil Bas :
2640
(8)
Id appareil Haut :
0 (8)
(x10000)
N° port UDP bas
7808(8)
N° port UDP haut
4(8)
(x10000)