VIII.5.e.
Opening percentage curve of the FEE module
ouvert
fermé
In Standard the minimum% opening of the RMR and RMS registers is 30% or about
15% fresh air flow
100% opening of RMS fresh air and return air registers RMR =
output AO1 = 0V = all fresh air
0% opening of RMS fresh air and return air registers RMR =
output AO1 = 10V = all recycling
30% opening of RMS fresh air and return air registers RMR =
output AO1 = 7V = mixture