OPERATING AND COMMISSIONING INSTRUCTIONS

 

 

MS-CDF-002 

Ind  D 

Maj. 02/11/2018 

Créé par : JC 

Validé par : AR 

Page 18/49 

 

IV.12.

 

Hot water coil intergrated (H) / Changeover water coil (CO) et cold coil C

 

For units equipped with a cold battery or changeover, the additional module is equipped with a removable stainless 
steel condensate tray with integrated siphon. Connection of the PVC pipe diameter 32 to predict. 

Connection between the additional module and the B1 junction box to be made. 

Pay attention to let the doors free of access (ducts, cables) 

In the ELITE and EDEN version, the battery is already installed in the central unit, the Antifreeze Thermostat is connected. 
However, you must wire the 3-way valve. If you are using a hot coil battery, also connect the THA (Thermostat Antifreeze) 
and remove the supply temperature sensor after the battery 

 

 

 

 

THE VALVE MUST BE CONNECTED OFF 

 

Connect the actuator of the 3-way valve as follows: 

Hot Battery  

Terminal 

77

 of the connector B1 (additional module)

 

on +24V (G) of the actuator  

Terminal 

78

 of the connector B1 (additional module)

 

on 0V (G0) of the actuator 

Terminal 

79

 of the connector B1 (additional module)

 

on 10V (Y) of the actuator 

Connect the NC contact (C et 2) of 

THA

 (

TH

ermostat 

A

ntigel) on terminal 

75

 and 

76 

of the connector B1 (additional module)

  

Possibility to connect the hot water circulator to the control unit on the terminals

 49

 and 

50. 

(Note: 24V output to relay) 

Possibility to connect a free voltage contact NO pump fault on the terminals

 

45

 et 

46 

  
Cold battery 

Terminal 

80

 of the connector B1 (additional module)

 

on +24V (G) of the actuator  

Terminal 

81

 of the connector B1 (additional module)

 

on 0V (G0) of the actuator 

Terminal 

82

 of the connector B1 (additional module)

 

on 10V (Y) of the actuator 

Connect the NC contact (C et 2) of 

THA

 (

TH

ermostat 

A

ntigel) on terminal 

75

 and 

76 

of the connector B1 (additional module)

 

Possibility to connect the cold water circulator to the control unit on the terminals

 63

 and 

64. 

(Note: 24V output to relay) 

Possibility to connect a free voltage contact NO pump fault on the terminals

 

45

 et 

46 

 

 

Changeover battery 

Red wire of changeover thermostat (CO) on 10V (Y) of the actuator  
Terminal 

77

 of the connector B1 (additional module)

 

on +24V (G) of the actuator  

Terminal 

78

 of the connector B1 (additional module)

 

on 0V (G0) of the actuator 

Terminal 

79

 of the connector B1 (additional module)

 

on brown wire of changeover thermostat (CO) 

Terminal 

82

 of the connector B1 (additional module)

 

on black wire of changeover thermostat (CO) 

Connect the NC contact (C et 2) of 

THA

 (

TH

ermostat 

A

ntigel) on terminal 

75

 and 

76 

of the connector B1 (additional module) 

  

Possibility to connect the hot water circulator to the control unit on the terminals

 49

 and 

50. 

(Note: 24V output to relay) 

Possibility to connect the cold water circulator to the control unit on the terminals

 63

 and 

64. 

(Note: 24V output to relay) 

Possibility to connect a free voltage contact NO pump fault on the terminals

 

45

 et 

46 

  
 
 
 

Содержание EXAECO 10

Страница 1: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 1 49...

Страница 2: ...ELECTRICAL WIRING 12 IV 1 POWER SUPPLY 12 IV 2 TEMPERATURE SENSOR WIRING 12 IV 3 TERMINAL BLOCKS 12 IV 4 Wiring and operation of rotative exchanger 14 IV 5 Wiring and operation of 3 ways mixed damper...

Страница 3: ...ers 2 chapter V 3 a 29 V 4 c CO2 setpoint for DIVA QUATTRO option 3 Chapter V 3 a 29 V 4 d Minimum opening percentage of the 3 ways mixing damper FEE 4 chapitre V 3 a 29 V 5 Administrator settings 30...

Страница 4: ...the product Contacts for pick up requests E mail operations pro ecologic france com Phone 01 30 57 79 14 Internet www e dechet com SAFETY INSTRUCTIONS In compliance with the current norms the machine...

Страница 5: ...their installation position If the device is handled using a fork lift truck ensure this supports the load bearing structure If the device is moved using a crane use four cables of identical lengths T...

Страница 6: ...nected in accordance with Best Practices in order that the condensates are removed as efficiently as possible The height H must be at least equal to the maximum internal negative pressure of the unit...

Страница 7: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 7 49 II 2 a 2 Principal module EXAECO 17 22...

Страница 8: ...ct air fan starts and the extract air register opens o Temperature regulation starts defined in the regulation mode set Electric heater if set starts with airflow controller Pumps start o After a defi...

Страница 9: ...LOBBY Constant pressure ventilation Pa CONSTANT PA MODE Constant pressure adjustement Pa Fitted with a factory turned clocked set in LS 1 2 from 00h00 to 24h00 Possibility of adding a remote forced st...

Страница 10: ...nd 22 CO2 CO2 sensor REGULATION Control cabinet SRG Extract temperature sensor C1 Connector to connect module module ELITE THA External frost guard thermostat version ELITE H THS Overheat security swi...

Страница 11: ...n Standard and DIVA or TRPS Extract pressure transmitter for LOBBY MAC2 et QUATTRO 7 Terminal blocks 27 to 74 8 DEP FR filter pressure switch 9 Terminal blocks main supply 10 Control breaker 11 Proxim...

Страница 12: ...CORRIGO Connect directly on controller CORRIGO and 8A max on all DO Designation Terminal blocks Wiring DEP FS DEP FR 1 2 3 4 Connect to terminal of exhaust filter switch Connect to terminal 1 and 3 of...

Страница 13: ...50 Connect to hot water circulator Note 24V 2AMax to relay DAD 57 58 59 60 57 58 Connect to the power supply of the DAD L et N 59 60 Connect to the default contact of the DAD 10 11 shunted if not use...

Страница 14: ...ith 3 ways mixed dampers If it is not enough to reach the temperature setpoint hot battery starts running En t COLD RECOVERY if outside temperature is higher than inside temperature and cold is needed...

Страница 15: ...n TEMPERATURE FUNCTION OF MODULE FEE In winter When you are in hot demand the 3 way module closes appropriately until the maximum recycling minimum fresh air flow rate can be adjusted see chapter V 6...

Страница 16: ...lid par AR Page 16 49 IV 6 Filter pressure switch wiring The supply air filter pressure switch is factory connected IV 7 Fan pressure switch The fans pressure switchs are factory connected IV 8 Pressu...

Страница 17: ...r runs only with fresh air At the end of Night Cooling period heating is blocked to 0V during 60 minutes Start conditions customizable in chapter V 5 b 2 o Outside temperatures are higher to 22 C duri...

Страница 18: ...nit on the terminals 49 and 50 Note 24V output to relay Possibility to connect a free voltage contact NO pump fault on the terminals 45 et 46 Cold battery Terminal 80 of the connector B1 additional mo...

Страница 19: ...4V digital output To be connected to terminals 71 and 72 and to give the run command to drive a DX module Attention 24V 2A Max to relay 0 10V analogue output To be connected to terminals 8 and 9 8 0V...

Страница 20: ...on all the other alarms 3 Normal work keeps the unit running with parameters activated on site Stop LS HS 4 Supply fan only start or keeps in HS the supply fan extract stopped 5 Extract fan only star...

Страница 21: ...uttons help to navigate inside the parameter o OK button help to enter the value and to confirm a choice C button helps to cancel it o Alarm button red allows the access of the defaults list o Left ar...

Страница 22: ...ATTENTION Do not modify parameters which are not in bold characters in this case no after sales will be admitted Regulation mode Year month day Hour System state of unit SP Setpoint T C Act T C actuel...

Страница 23: ...pport alarme Running mode Auto 7 Running time Vent SAF 00 0 H Viewing the history alarms use the down arrow to scroll through the history Alarm report Input Output AI Ext1 Analogue Input AI1 T AS suup...

Страница 24: ...Reg AN DO2 Reg Recy DO3 Heat demand DO4 Cool demand AO1 Y1 Heating AO2 Y2 Exchang AO3 Y3 Cool AO4 Ctrl SAF AO5 Ctrl EAF AO Ext1 analogue outputs DO1 V freq SAF DO2 V freq EAF DO3 Rot exch activ DO4 He...

Страница 25: ...AC2 QUATTRO Real 1503m3 h example Setpoint 1500m3 h 5 Frequency control SAF Sp 1 1 70 5 Sp 1 2 50 5 CO2 except DIVA OU QUATTRO R al 654ppm exemple Setpoint 1000ppm 6 Pressure Control SAF Sp 1 1 non ut...

Страница 26: ...esday 2 Per 1 07 00 22 00 Per 2 00 00 00 00 Etc until sunday holidays Timer Hour Date Hour 15 54 1 Date 2011 01 25 1 Day Tuesday 1 Timer reduced speed Slow speed Monday 3 Per 1 00 00 05 00 Per 2 22 00...

Страница 27: ...ays periods 4 chapter V 3 d Access Time settings Holidays The system is set without vacation period In case you wish to reduce the operating time during holiday periods set the holiday operating hours...

Страница 28: ...stop unit with CORRIGO controller or do a forced start LS 7 manual speed 1 2 or HS 7 manual speed 1 1 In standard unit works automatically with clocks 7 Auto If unit do not work in automatic mode an a...

Страница 29: ...O2 setpoint for DIVA QUATTRO option 3 Chapter V 3 a Access Configuration Ctrl CO2 COV CO2 setpoint is set in standard LS 800ppm HS 1000ppm Unit will increase its speed proportionally to reach its maxi...

Страница 30: ...ent level ADMIN Configuration Communication Syst me Port 1 Esclave 1 et 2 Activation MODBUS RS485 and settings see chapter V 6 3 et 4 Activation BACNET MSTP and settings see chapter V 6 5 et 6 Setting...

Страница 31: ...r Modus fonction 1 5 et 15 2 Input status register Modus fonction 2 3 Holding register Modus fonction 3 6 et 16 4 Input resister Modus fonction 4 Supported Modbus functions Read Coils 1 Read discrete...

Страница 32: ...address should be entered in the format xxx xxx xxx xxx follwed by the port number default settings 47808 MAC The MAC address of the device This need to be unique only to the subnet Device ID The ID...

Страница 33: ...Remote control do not run or gives wrong values Remote control further than 100m Repetitor is not connected correctly VI 2 List of alarms n Affichage Description Type Tempo Cause 1 Malfunction supply...

Страница 34: ...wrongly connected see chapter IV 3 29 Rotation sentinel exchanger Control the value DI6 C 300s The belt of the exchanger is brocken 31 Supply air fan control error Difference higher than 50Pa between...

Страница 35: ...ee chapter VI 3 87 in manual mode Functions are modified in manual mode C 5s In Manuel Auto menu everything must be in Auto VI 3 Acknowledge the default timer service These settings require an access...

Страница 36: ...U7 F7 NO Periodicity of the cleaning Componants 1 MONTH 3 MONTHS 6 MONTHS 12 MONTHS Filtration Blowing for the G4filters Cleaning for the G4filters Washing for the G4filters Replacement Of the filters...

Страница 37: ...Maj 02 11 2018 Cr par JC Valid par AR Page 37 49 Location of the battery Saisir la pile et tirer doucement vers le haut jusqu ce que la pile quitte son logement Appuyer fermement sur la pile neuve po...

Страница 38: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 38 49 VIII ANNEXES VIII 1 Power diagram EXAECO 10...

Страница 39: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 39 49 VIII 2 Power diagram EXAECO 13 22...

Страница 40: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 40 49 VIII 3 Control diagram...

Страница 41: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 41 49...

Страница 42: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 42 49 VIII 4 Motors wiring...

Страница 43: ...ECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 43 49 VIII 5 Aeraulics diagram VIII 5 a EXAECO 10 VIII 5 b EXAECO...

Страница 44: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 44 49 VIII 5 c EXAECO 17 VIII 5 d EXAECO 22...

Страница 45: ...e of the FEE module ouvert ferm In Standard the minimum opening of the RMR and RMS registers is 30 or about 15 fresh air flow 100 opening of RMS fresh air and return air registers RMR output AO1 0V al...

Страница 46: ...al speed 6 In operation 9 CO2 functionning 10 Night cooling 12 stopped X 30003 Outdoor Temperature R 30001 Operating time of the supply fan R 30004 Operating time of the extract fan R 30005 Supply air...

Страница 47: ...ly comp ext for T C out de 10 C R 40016 18 Supply setpoint Set in constant supply comp ext for T C out de 15 C R 40017 18 Return setpoint Set in return control R 40018 21 speed supply HS setpoint In f...

Страница 48: ...e Alarm synthesis If 1 ALARM L 10163 SAF default If 1 ALARM L 10033 EAF default If 1 ALARM L 10034 Filter default If 1 ALARM L 10038 Antifreeze default If 1 ALARM L 10040 Fire default If 1 ALARM L 100...

Страница 49: ...EXAECO HIGH EFFICIENCY RECOVERY UNIT OPERATING AND COMMISSIONING INSTRUCTIONS MS CDF 002 Ind D Maj 02 11 2018 Cr par JC Valid par AR Page 49 49 IX NOTES...