EXAECO
®
HIGH EFFICIENCY RECOVERY UNIT
OPERATING AND COMMISSIONING INSTRUCTIONS
MS-CDF-002
Ind D
Maj. 02/11/2018
Créé par : JC
Validé par : AR
Page 18/49
IV.12.
Hot water coil intergrated (H) / Changeover water coil (CO) et cold coil C
For units equipped with a cold battery or changeover, the additional module is equipped with a removable stainless
steel condensate tray with integrated siphon. Connection of the PVC pipe diameter 32 to predict.
Connection between the additional module and the B1 junction box to be made.
Pay attention to let the doors free of access (ducts, cables)
In the ELITE and EDEN version, the battery is already installed in the central unit, the Antifreeze Thermostat is connected.
However, you must wire the 3-way valve. If you are using a hot coil battery, also connect the THA (Thermostat Antifreeze)
and remove the supply temperature sensor after the battery
THE VALVE MUST BE CONNECTED OFF
Connect the actuator of the 3-way valve as follows:
Hot Battery
:
Terminal
77
of the connector B1 (additional module)
on +24V (G) of the actuator
Terminal
78
of the connector B1 (additional module)
on 0V (G0) of the actuator
Terminal
79
of the connector B1 (additional module)
on 10V (Y) of the actuator
Connect the NC contact (C et 2) of
THA
(
TH
ermostat
A
ntigel) on terminal
75
and
76
of the connector B1 (additional module)
Possibility to connect the hot water circulator to the control unit on the terminals
49
and
50.
(Note: 24V output to relay)
Possibility to connect a free voltage contact NO pump fault on the terminals
45
et
46
Cold battery
:
Terminal
80
of the connector B1 (additional module)
on +24V (G) of the actuator
Terminal
81
of the connector B1 (additional module)
on 0V (G0) of the actuator
Terminal
82
of the connector B1 (additional module)
on 10V (Y) of the actuator
Connect the NC contact (C et 2) of
THA
(
TH
ermostat
A
ntigel) on terminal
75
and
76
of the connector B1 (additional module)
Possibility to connect the cold water circulator to the control unit on the terminals
63
and
64.
(Note: 24V output to relay)
Possibility to connect a free voltage contact NO pump fault on the terminals
45
et
46
Changeover battery
:
Red wire of changeover thermostat (CO) on 10V (Y) of the actuator
Terminal
77
of the connector B1 (additional module)
on +24V (G) of the actuator
Terminal
78
of the connector B1 (additional module)
on 0V (G0) of the actuator
Terminal
79
of the connector B1 (additional module)
on brown wire of changeover thermostat (CO)
Terminal
82
of the connector B1 (additional module)
on black wire of changeover thermostat (CO)
Connect the NC contact (C et 2) of
THA
(
TH
ermostat
A
ntigel) on terminal
75
and
76
of the connector B1 (additional module)
Possibility to connect the hot water circulator to the control unit on the terminals
49
and
50.
(Note: 24V output to relay)
Possibility to connect the cold water circulator to the control unit on the terminals
63
and
64.
(Note: 24V output to relay)
Possibility to connect a free voltage contact NO pump fault on the terminals
45
et
46