*Connect directly on controller CORRIGO
**
Connect directly on controller CORRIGO and 8A max on all DO
Designation
Terminal blocks
Wiring
MF GV
39-40
Connect to NO free voltage contact of normal Speed extended operation
MF PV
41-42
Connect to NO free voltage contact of reduced Speed extended operation
ARR Externe
43-44
Connect to NO free voltage contact of external stop
IND P
45-46
Connect to the default contact of Heating and cooling circulator. Défault =
closed contacte (free voltage contact mandatory)
MF Recycl
47-48
Connect to NO free voltage contact of Recirculation extended operation
Heating pump**
49-50
Connect to hot water circulator (Note : 24V 2AMax to relay)
DAD
57-58
59-60
57-58 Connect to the power supply of the DAD (L et N)
59-60 = Connect to the default contact of the DAD (10-11)
(shunted if not
used)
ADP (shunted if not
used)
61-62
Connect on fire emergency stop (free voltage NC contact)
Cooling pump **
63-64
Connect to cold water circulator (Note : 24V 2AMax to relay)
NC (Night cooling)
(LOBBY
®
)
65-66
24V output available if unit runs with the optional LOBBY EC for opening
dampers during
N
ight
C
ooling. (pay attention : 24V 2A Max to relay)
Heating demand
71-72
24V output available if unit is in heating demand. Could be used to manage
DX coils (pay attention : 24V 2A Max to relay)
Cooling demand
73-74
24V output available if unit is in cooling demand. Could be used to manage
DX coils (pay attention : 24V 2A Max to relay)