Specification
Thermocouple
9 types
Standards:
IPTS/68/DIN 43710
CJC rejection:
20:1 (0.05°/°C) typical
External resistance:
100
Ω
maximum
Resistance thermometer
RTD-2/Pt100 2 wire
Standards:
DIN 43760
(100
Ω
0°C/138.5
Ω
100°C Pt)
Bulb current:
0.2mA maximum
Linear process inputs
mV range:
0 to 50mV
Applicable to all inputs SM = sensor maximum
Calibration accuracy:
±0.25%SM ±1°C
Sampling frequency:
input 10Hz, CJC 2 sec.
Common mode rejection: Negligible effect up to 140dB,
240V, 50-60Hz
Series mode rejection:
60dB, 50-60Hz
Temperature coefficient: 150ppm/°C SM
Reference conditions:
22°C ±2°C, rated voltage after 15
minutes settling time.
Output devices
SSd/SSd1/SSd2:
solid state relay driver: To switch a
remote SSR 5Vdc +0/-15% 15mA
non-isolated
Miniature power relay: form A/SPST contacts (AgCdO)
rLY and rLY1:
2A/250ac resistive load
rLY2:
1A/250ac resistive load
General
Displays:
Main, 4 Digits high brightness
green LED. 10mm (0.4”) high.
Digital range -199 to 9999
Hi-res mode -199.9 to 999.9
LED output indicators - flashing
SP1 square, green; SP2 round, red
Keypad:
3 elastomeric buttons
Environmental
Humidity:
Max 80%
Altitude:
up to 2000M
Installation:
Categories ll and lll
Pollution:
Degree ll
Protection:
NEMA 4X, lP66
EMC emission:
EN50081-1 FCC Rules 15 subpart J
Class A
EMC immunity:
EN50082-2
Ambient:
0-50ºC (32-130°F)
Mouldings:
flame retardant polycarbonate
Weight:
3300: 110g (3.9 oz)
9300: 120g (4.2 oz)
SPECIFICATION
32