Failure to comply with the following warnings could 
result in personal injury or property damage.

FIRE HAZARD

•  Do not exceed the specified voltage.
•  Protect the control from direct contact with water 

(dripping, spraying, rain, etc.)

•  If the control has been in direct contact with water, 

replace the control.

•  Label all wired before disconnection when servicing 

controls. Wiring error can cause improper and 
dangerous operation.

•  Route and secure wiring away from flame.

SHOCK HAZARD

•  Disconnect electric power before servicing.
•  Ensure proper earth grounding of appliance.
•  Ensure proper connection of line neutral and line 

hot wires.

EXPLOSION HAZARD

•  Shut off main gas to appliance until installation is 

complete.

Installation should be done by a qualified heating and air 
conditioning contractor or licensed electrician.
Do not exceed the specification ratings.
All wiring must conform to local and national electrical codes 
and ordinances.
This control is a precision instrument, and should be handled 
carefully. Rough handling or distorting components could cause 
the control to malfunction.
Following installation or replacement, follow manufacturer's 
recommended installation/service instructions to ensure proper 
operation.

50M58-289

2-Stage, X-13 Style Hot Surface Ignition Control

INSTALLATION INSTRUCTIONS

FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE 
INSTALLING  OR  OPERATING THIS  CONTROL  COULD  CAUSE  PERSONAL 
INJURY AND/OR PROPERTY DAMAGE.

 

 PRECAUTIONS

CONTENTS

Description ............................................................. 1

Precautions ............................................................ 1

Specifications ......................................................... 2

Installation .............................................................. 3

 

Mounting & Wiring

Operation ................................................................ 6

System Lockout and Diagnostic Features .............. 7

Troubleshooting ...................................................... 8

 

 DESCRIPTION

Do  not  short  out  terminals  on  gas  valve  or  primary 

control. Short or incorrect wiring may damage the 
thermostat.

CAUTION

!

WARNING

!

The 50M58-289 is a replacement control for two-stage automatic 
gas ignition controls employing a microprocessor to continually 
monitor, analyze, and control the proper operation of the gas 
burner and inducer. The 50M58-289 controls a multiple tapped 
induction circulation blower.
Signals interpreted during continual surveillance of the two-
stage thermostat and flame sensing element initiate automatic 

ignition of the burner, sensing of the flame, and system shutoff 
during normal operation.
The control incorporates system fault analysis for quick gas 
flow shutoff, coupled with automatic ignition retry upon sensing 
a fault correction.

www.white-rodgers.com

www.emersonclimate.com

PART NO. 37-7547B

Replaces 37-7547A

1445

Содержание 50M58-289

Страница 1: ...s recommended installation service instructions to ensure proper operation 50M58 289 2 Stage X 13 Style Hot Surface Ignition Control INSTALLATION INSTRUCTIONS FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND OR PROPERTY DAMAGE PRECAUTIONS CONTENTS Description 1 Precautions 1 Specifications 2 Installation 3 Mounting Wir...

Страница 2: ...period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TFI 3 Retries The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period 2 times Valve Sequence period Valve sequence period equals 5 seconds trial for ignition period x 1 initial tr...

Страница 3: ...nnections UL approved 105o C rated 16 gauge min stranded 1 16 thick insulation wire is recommended for all line voltage connections Afterinstallationorreplacement followappliancemanufacturer s recommended installation or service instructions to insure proper operation The 50M58 has only one serviceable part an automotive type fuse which protects the low voltage transformer from damage if its outpu...

Страница 4: ...D LO IND N IGN N CIRC N LINE N XFMR N HUM N EAC N R W2 W1 Y R W2 W1 Y2 CONDENSING UNITS 50M58 289 in other furnace THERMOSTAT FLAME SENSOR PROBE 2ND STAGE PRESSURE SWITCH N O HIGH LIMIT N C AUX HIGH LIMIT N C 1ST STAGE PRESSURE SWITCH N O GAS VALVE HLO HLI FP PS1 MVL MVH GND GND PS2 MV COM TR TH Low Voltage 24 VAC Line Voltage 120 VAC G G ROLLOUT SWITCH N C LEGEND N C Normally closed switch N O No...

Страница 5: ...alve FIRST STAGE W2 two stage thermostat W2 terminal or equivalent IGN 1 ignitor HOT side IGN N 5 ignitor NEUTRAL side circulator blower terminal TAP 1 L1 1 4 spade terminal input voltage 120 VAC HOT SIDE T1 XFMR 1 4 spade terminal 24 VAC transformer line voltage HOT SIDE EAC H 1 4 spade terminal air cleaner HOT side HUM 1 4 spade terminal humidifier HOT side CIRC N 1 4 spade terminal circulator b...

Страница 6: ...On 4 Off On Off On 90 sec 120 sec 150 sec 180 sec Factory default setting OPTION SWITCHES S1 1 S1 2 POSITIONS COOL CIRCULATOR SPEED 2nd Stage delay for single stage thermostats Delay Time On S1 set switch 1 2 Off Off Off 10 min On Off Auto min Off On 20 min On On Factory default setting two stage thermostat OPTION SWITCH S3 POSITION HEAT CIRCULATOR SPEED DIP Switch S3 Setting S3 1 2 1 2 1 2 1 2 Po...

Страница 7: ...emory the LED will flash two green flashes The control will flash the most re cent error first and the oldest error last last in first out There shall be 2 seconds between codes Solid LED error codes will not be displayed FAULT CODE RESET To clear the fault code memory push and hold the LAST ER ROR button for more than 5 seconds and less than 10 seconds Control will indicate this period by RAPID G...

Страница 8: ...wer failure restricted air flow through appliance or duct work Verify continuity through limit switch circuit and correct overheating cause 12 Module Ignitor contact failure Fault code indicates the module ignitor contacts are not functioning properly Replace module Solid Module internal fault condition Module contacts for gas valve not operating or processor fault Reset control if condition persi...