 INSTALLATION

MOUNTING AND WIRING

Refer  to Typical  System Wiring  Diagram  on  page  4  and 
Typical System Wiring Table on page 5

All wiring should be installed according to local and national 
electrical codes and ordinances.
The control must be secured to an area that will experience a 
minimum of vibration and remain below the maximum ambient 
temperature rating of 175

o

F.  The control is approved for minimum 

ambient temperatures of -40

o

F. 

When mounting the control, any orientation is acceptable. 
Choose a location that will not damage, obstruct or place stress 
on the control terminations, system wiring harness or system 
components.
Refer to the wiring diagram and wiring table when connecting  
the 50M58 control to other components of the system.
UL approved, 105

o

C rated 18 gauge min., stranded, 1/32" thick 

insulation wire is recommended for all low voltage safety circuit  
connections.
UL approved, 105

o

C rated 16 gauge min., stranded, 1/16" 

thick insulation wire is recommended for all line voltage 
connections.   

After installation or replacement, follow appliance manufacturer's 
recommended installation or service instructions to insure 
proper operation.
The 50M58 has only one serviceable part – an automotive type 
fuse, which protects the low voltage transformer from damage 
if its output is short-circuited. If the fuse has opened up, correct 
whatever caused the short circuit and replace the fuse with only 
a 3 amp automotive type fuse. If the fuse is not the cause of 
the control's problem, replace the entire 50M58 control. There 
are no other user serviceable parts.
Additional jumper wires are included to be used if the original 
wiring does not reach the control after mounting. Refer to the 
furnace wiring diagram for proper connection of wires.
Some applications will require connection to terminal FP2. If 
the control being replaced does not have this connections, it is 
not needed in the application and connection to terminal FP2 
is not required. 

Содержание 50M58-289

Страница 1: ...s recommended installation service instructions to ensure proper operation 50M58 289 2 Stage X 13 Style Hot Surface Ignition Control INSTALLATION INSTRUCTIONS FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND OR PROPERTY DAMAGE PRECAUTIONS CONTENTS Description 1 Precautions 1 Specifications 2 Installation 3 Mounting Wir...

Страница 2: ...period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TFI 3 Retries The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period 2 times Valve Sequence period Valve sequence period equals 5 seconds trial for ignition period x 1 initial tr...

Страница 3: ...nnections UL approved 105o C rated 16 gauge min stranded 1 16 thick insulation wire is recommended for all line voltage connections Afterinstallationorreplacement followappliancemanufacturer s recommended installation or service instructions to insure proper operation The 50M58 has only one serviceable part an automotive type fuse which protects the low voltage transformer from damage if its outpu...

Страница 4: ...D LO IND N IGN N CIRC N LINE N XFMR N HUM N EAC N R W2 W1 Y R W2 W1 Y2 CONDENSING UNITS 50M58 289 in other furnace THERMOSTAT FLAME SENSOR PROBE 2ND STAGE PRESSURE SWITCH N O HIGH LIMIT N C AUX HIGH LIMIT N C 1ST STAGE PRESSURE SWITCH N O GAS VALVE HLO HLI FP PS1 MVL MVH GND GND PS2 MV COM TR TH Low Voltage 24 VAC Line Voltage 120 VAC G G ROLLOUT SWITCH N C LEGEND N C Normally closed switch N O No...

Страница 5: ...alve FIRST STAGE W2 two stage thermostat W2 terminal or equivalent IGN 1 ignitor HOT side IGN N 5 ignitor NEUTRAL side circulator blower terminal TAP 1 L1 1 4 spade terminal input voltage 120 VAC HOT SIDE T1 XFMR 1 4 spade terminal 24 VAC transformer line voltage HOT SIDE EAC H 1 4 spade terminal air cleaner HOT side HUM 1 4 spade terminal humidifier HOT side CIRC N 1 4 spade terminal circulator b...

Страница 6: ...On 4 Off On Off On 90 sec 120 sec 150 sec 180 sec Factory default setting OPTION SWITCHES S1 1 S1 2 POSITIONS COOL CIRCULATOR SPEED 2nd Stage delay for single stage thermostats Delay Time On S1 set switch 1 2 Off Off Off 10 min On Off Auto min Off On 20 min On On Factory default setting two stage thermostat OPTION SWITCH S3 POSITION HEAT CIRCULATOR SPEED DIP Switch S3 Setting S3 1 2 1 2 1 2 1 2 Po...

Страница 7: ...emory the LED will flash two green flashes The control will flash the most re cent error first and the oldest error last last in first out There shall be 2 seconds between codes Solid LED error codes will not be displayed FAULT CODE RESET To clear the fault code memory push and hold the LAST ER ROR button for more than 5 seconds and less than 10 seconds Control will indicate this period by RAPID G...

Страница 8: ...wer failure restricted air flow through appliance or duct work Verify continuity through limit switch circuit and correct overheating cause 12 Module Ignitor contact failure Fault code indicates the module ignitor contacts are not functioning properly Replace module Solid Module internal fault condition Module contacts for gas valve not operating or processor fault Reset control if condition persi...