50M58-289

TERMINAL

50M58-289 TYPICAL WIRING TABLE

TERMINAL

TYPE

SYSTEM COMPONENT

CONNECTION

W1

two-stage thermostat W1 terminal (or equivalent)

G

two-stage thermostat G terminal (or equivalent)

R

two-stage thermostat R terminal (or equivalent)

Y

two-stage thermostat Y terminal (or equivalent)

YLO

two-stage thermostat YLO terminal

TWIN

one wire twinning terminal*

C

7 -screw

terminal

block

two-stage thermostat C terminal (or equivalent)

MV COM (8)

gas valve COMMON

MVH (1)

gas valve SECOND STAGE

**  Maximum recommended flame probe wire length is 36 inches.

*  For TWINNING applications, use only 50M51-843 Controls

24 VAC transformer (low voltage COMMON SIDE)

TR (9)

24 VAC transformer (low voltage HIGH SIDE)

TH (5)

flame sensor probe**

FP (3)

1st stage pressure switch INPUT

PS1 (12)

2nd stage pressure switch INPUT

PS2 (2)

high limit INPUT

HLI (6)

high limit OUTPUT

HLO (11)

MUST BE RELIABLY GROUNDED TO CHASSIS

GND (4)

MUST BE RELIABLY GROUNDED TO CHASSIS

GND (10)

MVL (7)

gas valve FIRST STAGE

W2

two-stage thermostat W2 terminal (or equivalent)

IGN (1)

ignitor HOT side

IGN N (5)

ignitor NEUTRAL side

circulator blower terminal (TAP 1)

L1

1

/

4

" spade terminal

input voltage (120 VAC) HOT SIDE

T1

XFMR

1

/

4

" spade terminal

24 VAC transformer line voltage HOT SIDE

EAC-H 

1

/

4

" spade terminal

air cleaner HOT side

HUM 

1

/

4

" spade terminal

humidifier HOT side

CIRC N

1

/

4

" spade terminal

circulator blower NEUTRAL terminal

LINE N

1

/

4

" spade terminal

input voltage (120 VAC) NEUTRAL SIDE

XFMR N

1

/

4

" spade terminal

24 VAC transformer line voltage NEUTRAL SIDE

HUM N 

1

/

4

" spade terminal

humidifier NEUTRAL side

EAC N 

1

/

4

" spade terminal

air cleaner NEUTRAL side

T2

circulator blower terminal (TAP 2)

T3

circulator blower terminal (TAP 3)
circulator blower terminal (TAP 4)

inducer HIGH SPEED HOT side

IND HI (2)
IND LO (3)

inducer LOW SPEED HOT side

IND N (4)

inducer NEUTRAL side

T4

1

/

4

" spade terminal

circulator blower HOT SIDE

CIRC-H

1

/

4

" spade terminal

1

/

4

" spade terminal

1

/

4

" spade terminal

1

/

4

" spade terminal

X-13 motor low voltage return 

COM

1

/

4

" female spade terminal

IGN

IND

IND

N

LO

IND

HI

IGN

N

MVH

PS2

GND

TH

MVL

TR

HLO

GND

PS1

FP

HLI

MV

COM

 

 WIRING

Содержание 50M58-289

Страница 1: ...s recommended installation service instructions to ensure proper operation 50M58 289 2 Stage X 13 Style Hot Surface Ignition Control INSTALLATION INSTRUCTIONS FAILURETO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE PERSONAL INJURY AND OR PROPERTY DAMAGE PRECAUTIONS CONTENTS Description 1 Precautions 1 Specifications 2 Installation 3 Mounting Wir...

Страница 2: ...period of time between energizing the main gas valve and deactivation of the ignition means prior to the end of TFI 3 Retries The additional attempts within the same thermostat cycle for ignition when the supervised main burner flame is not proven within the first trial for ignition period 2 times Valve Sequence period Valve sequence period equals 5 seconds trial for ignition period x 1 initial tr...

Страница 3: ...nnections UL approved 105o C rated 16 gauge min stranded 1 16 thick insulation wire is recommended for all line voltage connections Afterinstallationorreplacement followappliancemanufacturer s recommended installation or service instructions to insure proper operation The 50M58 has only one serviceable part an automotive type fuse which protects the low voltage transformer from damage if its outpu...

Страница 4: ...D LO IND N IGN N CIRC N LINE N XFMR N HUM N EAC N R W2 W1 Y R W2 W1 Y2 CONDENSING UNITS 50M58 289 in other furnace THERMOSTAT FLAME SENSOR PROBE 2ND STAGE PRESSURE SWITCH N O HIGH LIMIT N C AUX HIGH LIMIT N C 1ST STAGE PRESSURE SWITCH N O GAS VALVE HLO HLI FP PS1 MVL MVH GND GND PS2 MV COM TR TH Low Voltage 24 VAC Line Voltage 120 VAC G G ROLLOUT SWITCH N C LEGEND N C Normally closed switch N O No...

Страница 5: ...alve FIRST STAGE W2 two stage thermostat W2 terminal or equivalent IGN 1 ignitor HOT side IGN N 5 ignitor NEUTRAL side circulator blower terminal TAP 1 L1 1 4 spade terminal input voltage 120 VAC HOT SIDE T1 XFMR 1 4 spade terminal 24 VAC transformer line voltage HOT SIDE EAC H 1 4 spade terminal air cleaner HOT side HUM 1 4 spade terminal humidifier HOT side CIRC N 1 4 spade terminal circulator b...

Страница 6: ...On 4 Off On Off On 90 sec 120 sec 150 sec 180 sec Factory default setting OPTION SWITCHES S1 1 S1 2 POSITIONS COOL CIRCULATOR SPEED 2nd Stage delay for single stage thermostats Delay Time On S1 set switch 1 2 Off Off Off 10 min On Off Auto min Off On 20 min On On Factory default setting two stage thermostat OPTION SWITCH S3 POSITION HEAT CIRCULATOR SPEED DIP Switch S3 Setting S3 1 2 1 2 1 2 1 2 Po...

Страница 7: ...emory the LED will flash two green flashes The control will flash the most re cent error first and the oldest error last last in first out There shall be 2 seconds between codes Solid LED error codes will not be displayed FAULT CODE RESET To clear the fault code memory push and hold the LAST ER ROR button for more than 5 seconds and less than 10 seconds Control will indicate this period by RAPID G...

Страница 8: ...wer failure restricted air flow through appliance or duct work Verify continuity through limit switch circuit and correct overheating cause 12 Module Ignitor contact failure Fault code indicates the module ignitor contacts are not functioning properly Replace module Solid Module internal fault condition Module contacts for gas valve not operating or processor fault Reset control if condition persi...

Отзывы: