Function List
LEVEL 2
MANUAL CONTROL MODES
SP1.P
0 to 100 % ‘read only’
Read SP1 output percentage power
HAND
[oFF] 1 to 100 % (not in ON/OFF)
SP1 manual percentage power control
For manual control should a sensor fail.
Record typical
SP1.P
values beforehand.
PL.1
100 to 0 % duty cycle
[100]
Set SP1 power limit percentage
Limits maximum SP1 heating power during warm-up
and in proportional band.
PL.2
100 to 0 % duty cycle
[100]
Set SP2 percentage power limit (cooling)
SP2 OPERATING MODES
(see page 12/13)
SP2.A
[nonE] dV.hi dV.Lo bAnd
FS.hi FS.Lo Cool
Main SP2 operating mode
SP2.B
[nonE] LtCh hoLd nLin
Subsidiary SP2 mode: latch/sequence
Non-linear cool proportional band
INPUT SELECTION AND RANGING
DISP
[1] 0.1
Select display resolution: for display of process
temperature, setpoint,
OFSt, Set.2, hi.SC, LoSC
.
HISC
sensor minimum [sensor maximum]
°C/°F
Set full scale
LO.SC
[sensor minimum] sensor maximum
°C/ºF
Set scale minimum
(default 0°C or 32°F)
INPT
Select input sensor
[nonE]
(See
SENSOR SELECTION
table, page 31)
UNIT
nonE °C °F bAr Psi Ph rh SEt
Select °C/°F or process units
18