Set-up
SET-UP
5
This section details the four step initial configuration
that enables control with factory PID settings to start,
once the setpoint has been entered.
POWER-UP
On power-up the controller will display the self test
sequence and brief display blanking and then alternately
display
INPT
and
nonE
1
SELECT INPUT SENSOR
Press and hold
✱
and use either the
▲
or
▼
buttons to
scroll through the sensor selection (see table p.31).
When the correct sensor is displayed, release the
buttons. The controller will now alternately display
selected sensor type
INPT
and eg.
tc.S
2
TO SELECT °C/°F
Press and release the
▲
button, the controller will now
alternately display
UNIT
and
nonE
.
Press and hold the
✱
button and using the
▲
button
select
°C
,
°F
,
Bar
,
PSI
,
Ph
,
Rh
or
SEt
as required. Release
the buttons when the correct unit is displayed.
The controller will now alternately display selected range
(eg. ºC) and
unit
.
3
TO SELECT SP1 (Main setpoint output device)
Note:
Dual Relay and Dual SSd Output Options
Models 3311/9311 and 3322/9322 have their
outputs pre-configured. (see page 22)
Press and release the
▲
button, the controller will now
alternately display
SP1.D
and
nonE
.
Press and hold the
✱
button and using the
▲
button
select
SSd
or
rLY
as required. Release the buttons when the
correct device is displayed.
The controller will now alternately display
SP1.D
and
selected output device (eg.
SSd
).
4
TO ENTER INITIAL CONFIGURATION INTO
CONTROLLER MEMORY
Press and hold both
▲
and
▼
buttons for 3 seconds.
The process temperature (e.g.
23°C
) and
ParK
will be
alternately displayed as no setpoint has yet been selected.
TO SET THE MAIN SETPOINT
To display the setpoint, press and hold the
✱
button.
°C
and
0
or
°F
and
32
will be alternately displayed.
Press and hold the
✱
button. Press
▲
to increase or
▼
to decrease the setpoint.
The main setpoint LED will flash indicating that SP1 output is
ON.
The controller will now be set with the factory PID settings.