background image

THE FIRE PANEL ENCLOSURE

The panel is supplied with a plastic detachable lid, a plastic back box and a minimum of two separate PCBs. 

The relative location of these PCBs is indicated in figure 1 below.

The panel can be surface or semi-flush mounted. It must be installed indoors, positioned to avoid accidental 

damage, and not subject to conditions likely to affect its performance, e.g. dust, conductive or corrosive 

gases or liquids, nor subject to temperatures, input voltages and electrical loads outside the stated operating 

range. It should be sited at a height where it is easily accessible and in a prominent position within the 

building. Ideally, the indicators on the front of the enclosure should be at eye level and the ambient light 

level should allow the status of the indicators to be clearly seen.

Typical locations for the panel are in the entrance foyer/hallway of a building at ground floor level (the first 

and most obvious point of contact for emergency services) or a security office that is likely to be permanently 

manned.

Removing the lid and base PCBs

To protect the electronics from damage and to expose the base mounting holes, the panel’s lid and PCBs 

should be removed prior to first fix installation.

Anti-static handling guidelines

Please ensure that the following electro-static handling precautions are taken immediately 

prior to handling the panel’s PCBs or any other static-sensitive components:

Before handling any static-sensitive items, operators should rid themselves of any personal electro-static 

charge by momentarily touching any sound connection to safety earth, e.g. a radiator.

Always handle PCBs by their sides and avoid touching the legs of any components.

PCBs should be stored in a clean, dry place which is free from vibration, dust and excessive heat. Retaining 

the PCBs in a suitable cardboard box will also guard them against mechanical damage.

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 5 of 24

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

Figure 1 : Location of the panel’s base PCBs and removal details

1.  Take the fire alarm panel out of its box and undo the two lid screws using the Torx key provided.    

  Remove the lid to expose the Main Control PCB (the Power supply PCB is located underneath).

2.  Carefully remove the five retaining screws on the Main Control PCB and slide the PCB up and over the  

  mounting pillars, taking care not to damage any of the components.

3.  Disconnect the telecoms-style connecting cable at PL1 on the Power Supply PCB, making sure that the  

  cable remains connected to the reverse of the Main Control PCB to prevent it being misplaced. Care   

  should be taken when detaching this connector to depress the locking tab to prevent damage.

4.  Pull the Power Supply’s earth distribution strap off the spade connector at the base earth distribution post.

5.  Carefully remove the three retaining screws on the Power Supply PCB and slide the PCB up and over   

  the mounting pillars, again taking care not to damage any of the components.

MAIN CONTROL PCB

POWER SUPPLY PCB

Leave this end of the connector cable connected

to SK2 on the reverse of the Main Control PCB

push tab 

and gently

lift cable

PL1

PL1

Содержание AlarmSense CFP702-2

Страница 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Страница 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Страница 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Страница 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Страница 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Страница 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Страница 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Страница 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Страница 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Страница 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Страница 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Страница 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Страница 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Страница 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Страница 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Страница 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Страница 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Страница 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Страница 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Страница 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Страница 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Страница 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Страница 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Страница 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Отзывы: