Fixing the base onto a wall

Using the five mounting holes provided (see figure 3 below), fix the base securely onto a vertical wall, 

2

 

mounting height. The mounting holes are suitable for use with No.8-10, or 4-5mm countersunk screws.

Assess the condition and construction of the wall and use suitable screw fixings for the in-service weight of 
the product. Any dust or swarf created during the fixing process must be kept out of the fire alarm panel 
and care must be taken not to damage any wiring or components.

Figure 3 : Internal view of the back box with PCBs removed / side view for flush mounting

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 7 of 24

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

AlarmSense

 zone circuit wiring

Depending on the model purchased, two, four or eight AlarmSense™ zone circuit connections are available 
on the fire alarm panel. A recommended maximum of 25 devices can be fitted on each circuit which may 
include AlarmSense™ detectors, AlarmSense™ manual call points or AlarmSense™ sounders. These can be 
mixed in any order. Only AlarmSense™ devices can be used on the zone circuits.
Note: Any AlarmSense™ sounders fitted must be locked to their base or non-removable. If AlarmSense™ 
sounders are not fitted on a populated zone circuit then this must be programmed into the panel using the 
Sounder Status function (see Page 17 for details).
Also, there are limitations on the number of sounders which can be used (please refer to page 8 for 
important advice on sounder loading and distribution).

Figure 4 : Typical zone circuit wiring

Connect an end-of-line (EOL) capacitor (provided in the panel ’s accessory pack) across the terminals of the 
last device on each circuit to allow the wiring to be monitored. Unused zone circuits must also have an EOL 
capacitor fitted at the panel terminals.

Note that an open circuit fault on zone circuit wiring will stop some or all of the detectors, manual call 
points and sounders operating, and a short circuit will stop all devices operating.

For more specific device wiring information, refer to the instructions provided with the AlarmSense™ 
devices used.

The wiring for each zone circuit should be connected to the relevant 5mm connector block on the Main 
Control PCB and their screens terminated at the panel’s base earth distribution post (see page 13 for 
detailed second fix connection details).

ALARMSENSE™

MANUAL CALL

POINT

+

PANEL ZONE

CIRCUIT

TERMINALS

+

+

ALARMSENSE™

OPTICAL/HEAT

DETECTOR

ALARMSENSE™

SOUNDER, OR

SOUNDER BASE

ALARMSENSE™

MANUAL CALL

POINT

ALARMSENSE™

SOUNDER

BEACON BASE

ALARMSENSE™

OPTICAL/HEAT

DETECTOR

END OF LINE

CAPACITOR

DO NOT SPUR

(wiring not

monitored)

75mm

WALL

339mm

170mm

Ensure no

fixing devices

are located

underneath the

Power Supply

PCB to avoid

compromising

electrical

safety

Fixing centres

Fixing centres

Содержание AlarmSense CFP702-2

Страница 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Страница 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Страница 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Страница 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Страница 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Страница 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Страница 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Страница 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Страница 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Страница 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Страница 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Страница 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Страница 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Страница 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Страница 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Страница 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Страница 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Страница 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Страница 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Страница 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Страница 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Страница 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Страница 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Страница 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Отзывы: