background image

1.1 Zone faults

  To find out if a head out fault has occurred on a zone circuit:

1. 

Remove the panel’s lid using the Torx key provided and press the ACCESS LEVEL THREE FUNCTIONS    

 

button on the Main Control PCB to gain access to the panel’s engineer functions (see below).

2.  Continue pressing the ACCESS LEVEL THREE FUNCTIONS button until HEAD OUT light pulses.
 

Any existing Zone Fault lights are suppressed and the zone light(s) for any zone(s) with a head out fault  

 

are illuminated, e.g. if a detector head has been removed on zone 2, then Zone 2’s Fault light will be lit.

  To find out if an open circuit fault has occurred on a zone circuit:

1. 

Follow steps 1 and 2 outlined above until the OPEN CIRCUIT light pulses.

2. 

Any existing Zone Fault lights are suppressed and the zone light(s) for any zone(s) with an open circuit  

 

fault are illuminated, e.g. if the wiring on zone 6 is broken, then Zone 6’s Fault light will be lit.

  To find out if a short circuit fault has occurred on a zone circuit:

1. 

Follow steps 1 and 2 detailed above until the SHORT CIRCUIT light pulses.

2. 

Any existing Zone Fault lights are suppressed and the zone light(s) for any zone (s) that have a short circuit   

 

fault are illuminated, e.g. if the wiring on zone 4 has been shorted, then Zone 4’s Fault light will be lit.

Suggested actions:

1. 

Disconnect the faulty zone circuit completely and refit the end-of-line capacitor at the panel. If the    

 

fault condition clears this confirms there is a wiring fault.

2. 

Refit and double check the wiring and the end-of-line capacitor on the zone. Trace the fault with  

 

 

consideration for the type of fault indicated (see above).

 Note: A common head out fault is a detector head badly seated in a base which is not making a true   
 connection.

1.2 Power supply faults

A power supply fault indicates one, or more, of the following faults. Page 11 of this manual must be referenced 
when carrying out any of the suggested action procedures described below.

  The Mains supply voltage is too low or has failed completely, the Mains fuse (F1) has ruptured or the PSU has failed.

Symptoms: The panel runs on batteries, but not on Mains.

Suggested actions:

1.  Taking all due precautions, check Mains voltages are within range (see Technical Specifications, page 24)  
 

by probing Live and Neutral connections at connector block (CONN1). If not within range, repair Mains  

 supply.

2.  If within range and the red Hazardous Voltages Present light is not lit, check the Mains fuse (F1).

3.  If the fuse is intact, the red Hazardous Voltages Present light on the Power Supply PCB may, or may not,  
 

be lit. The PSU is faulty and should be replaced. Isolate the Mains supply and wait for the red Hazardous  

 

Voltages Present light to extinguish before replacing the Power Supply PCB.

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 19 of 24

DELAYS

TEST

NONLATCHING

COINCIDENCE

ACCESS

LEVEL THREE

FUNCTIONS

OPEN

CIRCUIT

SHORT

CIRCUIT

REPEATER

FAULT

SYSTEM

FAULT

SW8

CFP ALARMSENSE PANEL CONTROLS

HEAD

OUT

SOUNDER

STATUS

Содержание AlarmSense CFP702-2

Страница 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Страница 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Страница 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Страница 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Страница 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Страница 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Страница 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Страница 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Страница 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Страница 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Страница 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Страница 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Страница 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Страница 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Страница 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Страница 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Страница 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Страница 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Страница 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Страница 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Страница 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Страница 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Страница 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Страница 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Отзывы: