C-TEC AlarmSense CFP702-2 Скачать руководство пользователя страница 18

FAULT DIAGNOSIS

Fault indications

When a fault occurs on a critical part of the fire alarm system, the panel responds by activating its internal sounder 
and illuminating the General Fault light and any other Fault light(s) relating to the fault. The panel’s fault output 
will also activate (provided it has not been disabled).

The type of faults typically indicated at the fire alarm panel are highlighted below. A more precise diagnosis of 
fault conditions is available at access level 3 (the summaries below refer to the sections you should read later 
in this manual for further information). Unless otherwise stated, repairing any particular fault condition will 
automatically clear the fault from the panel. If the panel is reset whilst faults still exist, the faults will reappear 
after a short period of time.

Note: It is possible to mute the panel’s internal sounder at any time by momentarily pressing the SILENCE INTERNAL 
SOUNDER button.

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 18 of 24

General Fault

This light flashes yellow when there is a 
fault on any part of the fire alarm system. 
It is always lit in tandem with at least one 
other Fault light which displays precise 
information on the type of fault detected.

Zone Faults

All of the panel’s zone circuits (up to eight) are monitored for open 
and short circuit faults and detector head removal (unless there is 
an alarm condition or the zone is in test or disabled). All faults are 
indicated by the relevant Zone Fault light(s) pulsing yellow. The 
Sounder Status light will also pulse yellow if sounders are fitted.
For advice on how to correct this fault see page 19, section 1.1.

Supply 

Present

This light 
should be lit 
green at all 
times. If off, see 
power supply 
faults, page 19, 
section 1.2.

Power Supply Fault

This light flashes yellow when 
one or more of the following 
has occurred:

1) The Mains supply is too low or 
has failed completely.
2) Mains fuse (F1) has ruptured.
3) Battery fuse (F2) has ruptured.
4) The battery supply voltage is 
too low. 
5) The panel’s power supply unit 
is faulty.

For advice on how to correct this 
fault see page 19, section 1.2.

Remote Output Status

This light flashes yellow 
when there is a fault on 
the output’s aux. 24V 
supply.

For advice on how to deal 
with this type of fault see 
page 22, section 1.6.

System Fault

This light flashes yellow 
when one or more of the 
following has occurred:

1) There is a microprocessor 
“watchdog” fault.
2) The microprocessor’s 
site memory has been 
corrupted.
3) The microprocessor’s 
program menu has been 
corrupted.
4) The Main Control PCB is 
faulty.

For advice on how to 
correct this fault see page 
21, section 1.3.

Repeater Fault

This light flashes 
yellow when the 
master panel cannot 
communicate with 
one or more repeater 
panels (if fitted).

For advice on how to 
correct this fault see 
page 22, section 1.4.

Sounder Status

This light pulses yellow 
when one or more 
of the following has 
occurred:

1) A conventional 
sounder circuit has a 
fault.
2) A sounder on a zone 
circuit has a fault. The 
relevant Zone Fault 
light(s) will also pulse 
yellow.

All sounder circuits are 
monitored for open 
and short circuit faults 
(unless disabled or in 
an alarm condition).

For advice on how to 
correct this fault see 
page 22, section 1.5.

1

2

3

7

5

4

6

8

supply 

present

remote 

output

general 

fault

power 
supply 

fault

system 

fault

repeater 

fault

sounder 

status

auxiliary 

output 

status

output 

delays

test

remote 

output 

status 

fault 

output 

status

general 

disablement

accessed

Zone fault/disabled/test

Содержание AlarmSense CFP702-2

Страница 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Страница 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Страница 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Страница 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Страница 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Страница 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Страница 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Страница 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Страница 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Страница 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Страница 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Страница 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Страница 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Страница 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Страница 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Страница 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Страница 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Страница 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Страница 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Страница 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Страница 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Страница 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Страница 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Страница 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Отзывы: