To program non-latching zones (

Note: This function is non-compliant with EN54-2)

1.  Press the ACCESS LEVEL THREE FUNCTIONS button until the NONLATCHING light flashes (any zones that are already  

 

 

programmed for non-latching operation will have their Zone Fault lights lit steady).

2.  To change the non-latching configuration press the NEXT OPTION button (Zone 1’s Fault light will flash slower than the  
 

NONLATCHING light if NOT programmed, or at the same rate if it is).

3.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4.  To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5.  Repeat steps 3 and 4 until the process is complete.
6.  To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the    
 

ACCESS LEVEL THREE FUNCTIONS button.

To program delays

1.  Press the ACCESS LEVEL THREE FUNCTIONS button until the DELAYS light flashes (any zones that are already programmed  
 

for delays will have their Zone Fault lights lit steady, and similarly, if the Remote Output or Auxiliary Output are delayed,  

 

then their relevant status lights will be lit steady. Note: Any existing fault indications will be temporarily suppressed during  

 

this programming function. On exiting the function, the previous indications will be restored).

2.  To change the delays configuration press the NEXT OPTION button (Zone 1’s Fault light will flash slower than the DELAYS  
 

light if NOT programmed, or at the same rate if it is).

3.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4.  To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5.  Repeat steps 3 and 4 until the zone selection process is complete.
6.  Pressing the NEXT OPTION button when on the last zone will select the Remote Output for editing. The output’s current  
 

status will be shown by the Remote Output Status light, in the same way as for the zones.

7.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
8.  Pressing the NEXT OPTION button will select the Auxiliary Output for editing. The output’s current status will be shown by  
 

the Auxiliary Output Status light, in the same way as for the zones.

9.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
10.  Pressing the NEXT OPTION button will return the selection to zone 1.
11.  Set the delay period which will apply to all delayed zones or outputs by adjusting the VR1 control on the Main Control PCB  
 

with a terminal screwdriver (this can be anything from 1 to 10 minutes), then press the ESCAPE ACCESS button or move   

 

onto the next programming function by pressing the ACCESS LEVEL THREE FUNCTIONS button.

To program zones into test

1.  Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes (any zones that are already programmed for  
 

test will have their Zone Fault lights lit steady).

2.  To change the test configuration press the NEXT OPTION button (Zone 1’s Fault light will flash slower than the TEST light if  
 

NOT programmed, or at the same rate if it is).

3.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4.  To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5.  Repeat steps 3 and 4 until the process is complete.
 

Important: Before testing any of the zones you have programmed for test, you must first press the ESCAPE ACCESS button.  

 

Any zone(s) in test will be flashing and the General Test light will also be flashing. Testing can now commence. Remember  

 

to take the relevant zones out of test when testing is complete.

To program the sounder status (new zone in alarm resounds, or does not resound, the sounders)

1.  Press the ACCESS LEVEL THREE FUNCTIONS button until the SOUNDER STATUS light flashes.
 

If the SOUNDER STATUS light flashes three times quickly with a longer off period, then an alarm in a new zone will  

 

 

resound the sounders. If the SOUNDER STATUS light flashes with equal on-off periods, then an alarm in a new zone will   

 

NOT resound the sounders.

2.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
3.  To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the    
 

ACCESS LEVEL THREE FUNCTIONS button.

To program the sounder status (sounders fitted or not fitted)

1.  Press the ACCESS LEVEL THREE FUNCTIONS button until the SOUNDER STATUS light flashes. Then press the ACCESS LEVEL  
 

THREE FUNCTIONS button a second time.

 

Any zone circuits that are programmed (by default) to have sounders fitted will have their Zone Fault lights lit steady.

2.  To change the configuration press the NEXT OPTION button (Zone 1’s Fault light will flash at the same rate as the  

 

 

SOUNDER STATUS light if sounders are programmed as fitted, or flash slower if programmed as NOT fitted).

3.  If required, toggle between the two states by pressing the ENABLE/DISABLE button.
4.  To confirm your choice, press the NEXT OPTION button. This will move you to the next zone (if available).
5.  Repeat steps 3 and 4 until the process is complete.
6.  To finish the function, press the ESCAPE ACCESS button, or move onto the next programming function by pressing the    
 

ACCESS LEVEL THREE FUNCTIONS button.

The relevant part of the System Set-Up Data chart in the User Manual / Log Book must be updated if you 
implement or make any changes to the coincidence, non-latching zones, delays, or sounder status functions.

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 17 of 24

Содержание AlarmSense CFP702-2

Страница 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Страница 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Страница 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Страница 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Страница 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Страница 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Страница 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Страница 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Страница 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Страница 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Страница 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Страница 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Страница 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Страница 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Страница 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Страница 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Страница 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Страница 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Страница 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Страница 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Страница 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Страница 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Страница 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Страница 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Отзывы: