background image

Important note: If link PLK1 is fitted on the Main Control PCB (see right) triggering a manual call 
point on any zones programmed for coincidence will activate the alarm sounders and outputs 
immediately. Alarms from detectors will still be processed as described previously in this section.

From an installation point of view, detectors on zones assigned for coincidence should be installed in close 
proximity to each other. This ensures if the user is not around to investigate the cause of the alarm, that a detector 
in alarm on one zone is quickly confirmed by its neighbour on the corresponding zone in the event of a real fire. 
Alarms raised in zones not set up for coincidence will be processed as normal.

Non-Latching Zones (Note: This function is non-compliant with EN54-2)

Any or all of the zones on the fire alarm panel can be set up for non-latching operation.
Alarms raised from non-latching zones are indicated as normal but when the alarm stimulus that triggered the zone 
is cleared, the alarm condition at the panel automatically clears too (i.e. a manual panel reset is not required).
Note: Alarms raised on non-latching zones will not trigger the panel’s auxiliary fire and remote outputs.
Non-latching zones may be used to interconnect fire panels to prevent a ‘deadly embrace’ situation. This is a permanent 
unresettable alarm condition arising from multiple fire panels simultaneously flagging latching alarm conditions.

Delays

A delay of 1 to 10 minutes can be set between the fire alarm panel being triggered to its alarm sounders and 
outputs being activated. This is a particularly useful feature in public places where the nuisance and panic caused 
by a false alarm must be avoided

The delay period is set by adjusting the VR1 control on the Main Control 
PCB (see right) using a terminal screwdriver. Note: The same delay 
period will apply to all pre-programmed delayed zones and outputs.

When an alarm occurs on a delayed zone, it is processed as normal. 
However, the activation of any pre-programmed sounders and outputs is postponed until 
the delay period has expired, thus allowing the cause of the alarm to be investigated by a responsible person.
During the delay period, the Output Delays light on the panel front pulses to indicate the delay is operative. 
Pressing the SILENCE/RESOUND SOUNDERS button will override the delay at any time and result in any delayed 
sounders and outputs being activated. Alternatively, in the event of a false alarm, pressing the CONTROL PANEL 
RESET button (at access level 2) during the delay period will return the system to normal.
Important note: If link PLK1 is fitted on the Main Control PCB (see right), triggering a manual call 
point during the delay period will activate any delayed alarm sounders and outputs immediately. 
If link PLK1 is not fitted, triggering a manual call point will have no effect on the delayed alarm 
sounders and outputs.

Test

To aid commissioning and routine maintenance checks, a non-latching ‘one man walk test’ facility is available.
When a detector or manual call point is triggered on any zone(s) in test, the alarm sounders operate for 
approximately one second on and eight seconds off. This cycle continues until the cause of the alarm is removed 
(either by the test smoke clearing from the detector or the manual call point being reset), at which point the zone 
circuit also automatically resets. As the engineer walks around the site, additional devices on the zone(s) in test can 
be checked with the momentary activation of the alarm sounders confirming correct operation.
Zones programmed for test, will be indicated at the panel by their Fault lights pulsing quickly in synchronisation 
with the General Test light. Should an alarm occur on a zone that is not programmed for test, the alarm will be 
processed in the normal way. All zones that are in test will have their tests temporarily suspended until the alarm(s) 
from the other zones are reset. At this point zone testing may resume. In other words, the alarm will operate 
correctly despite being in test mode.

Program sounders to resound or not resound

Once the sounders (AlarmSense™ and conventional) have been activated after an alarm and then silenced, it is 
possible to set up the panel so that a new alarm raised from another zone resounds, or does NOT resound, the 
sounders in accordance with EN54-2 {Clause 7.8d}.
Program sounders on zone circuits to be fitted or not fitted

By default, zone circuits have AlarmSense™ sounders fitted. However, it is possible to programme a zone circuit 
to have sounders not fitted.

Fault diagnosis
A wide range of fault diagnosis features are available at access level 3. These are described in detail on pages 18 
to 22 of this manual.

LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 15 of 24

DELAY MINUTES

0

1

2

3

4 5 6

7

8

9

10

VR1

Use a small terminal 
screwdriver to adjust the 
delay time period.
For information on how to 
assign individual zones so 
the delay period applies to 
them, see pages 16 and 17.

PLK1

FUNCTION

MCP/SOUNDER

PLK1

FUNCTION

MCP/SOUNDER

Содержание AlarmSense CFP702-2

Страница 1: ...LPCB APPROVED CFP 2 4 8 ZONE FIRE ALARM CONTROL PANEL CFP702 2 2 Zone CFP702 2 2 Zone CFP704 2 4 Zone CFP708 2 8 Zone installation maintenance manual Approved Document No DFU7002020 Rev 4...

Страница 2: ...non latching zones delays test sounder status 16 17 Fault Diagnosis 18 Fault indications 18 Zone faults 19 Power supply faults 19 System faults 21 Repeater faults 22 Conventional sounder faults 22 Re...

Страница 3: ...lause 7 11 A delay facility selectable on a zone by zone basis is provided to delay the alarm sounders remote fire and or auxiliary outputs Test condition Clause 10 0 A zone test facility is provided...

Страница 4: ...this document A basic understanding of fire alarm system components and their use is assumed We strongly recommend that a suitably qualified and competent person is consulted in connection with the d...

Страница 5: ...of any personal electro static charge by momentarily touching any sound connection to safety earth e g a radiator Always handle PCBs by their sides and avoid touching the legs of any components PCBs s...

Страница 6: ...switched fused spur at 3 A or a 6 A Type B circuit breaker to IEC EN 60898 1 The Mains supply MUST be exclusive to the panel and be reliably earthed at the indicated earthing post Hint As an alternat...

Страница 7: ...e programmed into the panel using the Sounder Status function see Page 17 for details Also there are limitations on the number of sounders which can be used please refer to page 8 for important advice...

Страница 8: ...d supplying the panel s battery charging circuit and any output relays which may be fitted As a safe margin and to allow for these other loads the total sounder loading for the panel should not exceed...

Страница 9: ...limiting fuse which trips if one or more of the loads are shorted This affects all loads and results in appropriate faults being reported at the panel The current consumed by this output must be consi...

Страница 10: ...connected directly to this connector block and NOT to the base earth distribution post which is provided for making off zone circuit and conventional sounder circuit screens The Power Supply PCB s ea...

Страница 11: ...HR R V V 0V 1A 250 R 1A R Incoming Mains Cable This cable MUST be segregated from other cables Good quality cable glands MUST always be fitted Battery Connector CONN2 Leads supplied in the panel s acc...

Страница 12: ...lihood of incorrect connection Figure 10 Main Control PCB layout INSTALLATION MAINTENANCE MANUAL Approved Document No DFU7002020 Rev 4 Page 12 of 24 LPCB APPROVED CFP ALARMSENSE 2 4 8 ZONE FIRE ALARM...

Страница 13: ...All screens should be adequately insulated and connected between the nut and washers on the base earth distribution post see right using suitable eyed crimp connectors Do not disturb the lower nut th...

Страница 14: ...el only The programming of coincidence double knock Note This function is non compliant with EN54 2 The setting up zones for non latching operation Note This function is non compliant with EN54 2 The...

Страница 15: ...alse alarm pressing the CONTROL PANEL RESET button at access level 2 during the delay period will return the system to normal Important note If link PLK1 is fitted on the Main Control PCB see right tr...

Страница 16: ...non compliant with EN54 2 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the COINCIDENCE light flashes any pairs of zones that are already programmed for coincidence will have their Zone Fault...

Страница 17: ...LEVEL THREE FUNCTIONS button To program zones into test 1 Press the ACCESS LEVEL THREE FUNCTIONS button until the TEST light flashes any zones that are already programmed for test will have their Zon...

Страница 18: ...correct this fault see page 19 section 1 1 Supply Present This light should be lit green at all times If off see power supply faults page 19 section 1 2 Power Supply Fault This light flashes yellow w...

Страница 19: ...rs this confirms there is a wiring fault 2 Refit and double check the wiring and the end of line capacitor on the zone Trace the fault with consideration for the type of fault indicated see above Note...

Страница 20: ...power supply fault will automatically be cleared Depending on battery size and the depth of discharge this may take several hours If the batteries are in poor condition they must be replaced If the b...

Страница 21: ...d System Fault lights will be cycle continuously plus the panel s internal sounder will activate Suggested action Press the panel s RESET button and if still in access level 3 the ESCAPE ACCESS button...

Страница 22: ...ulty and must be replaced 3 If a sounder circuit fault is detected correct the fault and reconnect the sounder circuit The sounder fault will automatically clear within 60 seconds Note If the sounder...

Страница 23: ...pecification on page 24 for quiescent consumption of AlarmSense devices A The total alarm current of the sounders plus any other devices connected to other alarm outputs See Zone Circuit specification...

Страница 24: ...ored for open and short circuit YES Reverse voltage DC monitoring Indicated by common fault Alarm voltage 27VDC maximum 20VDC minimum final battery voltage Sounder circuit fuses Each circuit protected...

Отзывы: