Specification
4
Logano GE515 - We reserve the right to make any changes due to technical modifications.
11
Logano GE515
Boiler size
240
295
350
400
455
510
Flue gas temperature
2
,
part load (60 %)
°C
138
138
140
129
130
140
Flue gas temperature
2
,
full load
°C
164–183
161–183
161–177
157–171
159–172
164–174
Flue gas volume flow,
oil, part load (60 %)
kg/s
0.0647
0.080
0.094
0.108
0.123
0.137
Flue gas volume flow,
oil, full load
3
kg/s
0.092–0.110
0.109–0.135
0,134–0,160
0.159–0.182
0.182–0.208
0.207–0.233
Flue gas volume flow,
gas, part load (60 %)
kg/s
0.065
0.080
0.095
0.108
0.123
0.138
Flue gas volume flow,
gas, full load
3
kg/s
0.092–0.111
0.110–0.136
0.135–0.161
0.160–0.183
0.183–0.208
0.208–0.233
CO
2
content, oil
%
13
CO
2
content, gas
%
10
Required pressure
(draught)
Pa
0
Flue gas resistance
mbar
0.5–0.6
1.0–1.4
1.1–1.6
2.1–2.9
2.5–3.3
2.4–3.1
Maximum permissible
flow temperature
4
°C
100–120
5
Maximum permissible
operating pressure
bar
6
Type approval number, boiler
06-226-640
CE designation, boiler
CE - 0461 AR 6154
2
Acc. to DIN 303. The minimum flue gas temperature for the chimney calculation is approx. 12 K lower.
3
Full load details relate to the upper and lower rated output range.
4 High limit safety cut-out (safety limit thermostat). Max. possible flow temperature = safety limit (STB) –18 K. Example: Safety limit (STB)= 100 C;
max. possible flow temperature = 100 – 18 = 82 °C.
5
In accordance with national standards and guidelines.