2
Product description
Logano GB125 BE US/CA - Subject to technical modifications.
8
2.8
Dimensions and specifications
Fig. 3
Connections and dimensions (measurements in inches)
VK
= Boiler supply
RK
= Boiler return
EL
= Boiler drain (connection for drain valve)
Dimensions and connections:
6 720 649 309-01.1ITL
Boiler type
Unit
GB125/22 BE
GB125/30 BE
GB125/35 BE
Boiler sections
3
4
4
Rated heat output (gross output)
131/86 °F
MBtu/hr
76
102
124
Rated heat output (net IBR rating)
131/86 °F
MBtu/hr
67
90
109
Rated heat output/heating capacity
(gross output)176/140 °F
MBtu/hr
75
100
121
Rated heat output
(net IBR rating)176/140 °F
MBtu/hr
65
87
105
Rated thermal input/burner input
MBtu/hr
81
108
131
AFUE
%
91.2
91.1
91.0
Flue gas temperature 176/140 °F
°F (°C)
176 (80)
176 (80)
192 (89)
Boiler water content
gal (l)
8.7 (35.6)
11.8 (44.9)
11.8 (44.9)
Gas volume of combustion chamber and heat
exchanger
cu. ft.
(l)
1.5 (42.9)
2.0 (57.9)
2.0 (57.9)
Oil consumption/oil firing rate
gph (l/h)
0.60 (2.3)
0.75 (2.9)
0.95 (3.6)
Flue gas resistance
in. W.C.
(Pa)
0.08" - 0.14" W.C. (20 - 35)
Heat exchanger water pressure drop
(DeltaT = 18 °F)
ft. of
head
(mbar)
1.8' (54)
2.0' (60)
2.7' (81)
Maximum supply temperature
1)
1) Safety limit (manual reset high limit, STB)
Maximum permitted supply temperature = manual reset high limit (STB) – 32 °F
Example: manual reset high limit (STB) = 212 °F, maximum possible supply temperature = 212 - 32 = 180 °F
The safety limit must comply with the requirements applicable in your country.
°F (°C)
212 (100)
Maximum operating pressure
psi
(bar)
44 (3)
Maximum time constant of thermostat and
manual reset high limit (STB)
s
40
Tab. 2
Technical specifications