13
System inspection and maintenance
Logano G315 – 6 720 817 939 (2017/02)
34
▶ Take the flue gas baffle plates forwards out of the flue gas passages
(Fig. 61, [1 – 4]).
Fig. 61 Flue gas baffles, removing
The various brush types available from
Buderus
(optional extras) are
Fig. 62 Cleaning brushes
▶ Clean the flue gas passages (Fig. 63, [1]) starting at the front and
working towards the back with cleaning brushes 1 and 2 (Fig. 62).
▶ Clean the rear wall of the combustion chamber with cleaning brush 3.
▶ Clean the rest of the combustion chamber (Fig. 63, [2]) with
cleaning brush 2.
▶ Clean the bottom flue gas passages from the front with cleaning
Fig. 63 Heat exchanger heater flue, cleaning
▶ Undo the four self-tapping screws on the rear boiler panel at the
bottom.
▶ Remove bottom rear boiler panel.
▶ Loosen spring hooks below the flue outlet (
▶ Fold both ends of the thermal insulation up (Fig. 64, [1]) and fasten
in this position with the spring hooks.
▶ Remove the cleanout covers from the rear section (Fig. 64, [2]) and
on the draft diverter (Fig. 64, [3]).
▶ Remove all loose combustion residues from the combustion
chamber, the flue gas passages and the draft diverter.
▶ Check sealant ropes on the openings of the cleanout covers and
burner door. Replace damaged or hardened sealant ropes.
Fig. 64 Removing the cleanout cover
▶ Clean flue gas baffle plates with the cleaning brushes.
6 720 642 621-44.1o
2
3
1
4
6 720 642 623-69.1o
3
2
1
You can obtain sealant ropes from your nearest branch
office.
6 720 642 621-46.1o
2
3
1
6 720 642 621-45.1o
1
2
3
Содержание Logano G315
Страница 55: ...Appendix Logano G315 6 720 817 939 2017 02 55 ...
Страница 56: ......