8
Connecting the boiler on the flue gas side
Logano G315 – 6 720 817 939 (2017/02)
24
▶ Attach the front panel (Fig. 43, [3]) at the bottom in the center to the
▶ Attach the front panel at the top to the folded edge of the front cover
Fig. 43 Fitting the front panel
▶ Hook burner door panel into the cut-outs in the front cover (Fig. 44,
[3]).
Fig. 44 Attaching the burner door panel
8
Connecting the boiler on the flue gas side
This chapter explains how to connect the boiler on the flue gas side.
8.1
Installing a vent pipe sealing collar (accessory)
▶ Push the vent pipe as far as possible onto the draft diverter outlet.
▶ Place the vent pipe sealing collar around the vent pipe and draft
diverter outlet so that it overlaps at the top.
▶ Place hose clamps (Fig. 45, [4]) over the vent pipe sealing collar.
One of the hose clamps must press onto the draft diverter outlet and
and one onto the vent pipe.
▶ Tighten hose clamps.
The vent pipe sealing collar must fit smoothly and firmly in place after
tightening the hose clamps.
Fig. 45 Installing the vent pipe
[1]
Vent pipe sealing collar
[2]
Flue gas temperature sensor
[3]
Sleeve
[4]
Vent pipe
[5]
hose clamps
[6]
Exhaust Manifold
[A]
2 × Vent pipe diameter, at least 28 22/64 inches (720 mm)
8.1.1
Installing a flue gas temperature sensor (accessory)
▶ Weld a sleeve (Fig. 45, [3]) at a distance of two (2) × vent pipe
diameters (A) – min. 720 mm – from the draft diverter in the vent
pipe.
▶ Fit the flue gas temperature sensor (Fig. 45, [2]) as described in the
separate installation manual.
3
2
1
6 720 817 939-05.1T
1
6 720 817 939-06.1T
We recommend you use a vent pipe sealing collar
(
Retighten the hose clamps if required.
)
6 720 642 623-57.1o
6
4
1
3
2
5