7
Boiler block assembly
Logano G315 – 6 720 817 939 (2017/02)
21
Fig. 31 Hooking in the burner door
7.9
Boiler outer casing
This section describes how to install thermal insulation and cladding
components.
7.9.1
Fitting the profile rails
The folded edges of the front profile rails must face forwards.
▶ An additional nut must be turned on each of the two upper tie rods on
the front of the boiler (Fig. 32, [2]).
▶ Insert the top front crosswise tie bar (Fig. 32, [1]) between the first
and second nut of the tie rods in each case and fasten to the cast lugs.
▶ Fully tighten the outside nuts.
▶ Screw the bottom front crosswise tie bar (Fig. 32, [3]) with two
machine screws to the feet of the boiler front section.
Fig. 32 Fitting the front profile rails
▶ Fasten top rear crosswise tie bar (Fig. 33, [1]) to the cast lugs then
to rear section with machine screws (M 8 x × 15). The folded edge of
the upper crosswise tier bar must point
towards the front
.
▶ Screw the bottom crosswise tie bar (Fig. 33, [2]) to the feet of the
rear section with two machine screws (M 8 x x 15). The folded edge
of the bottom crosswise tie bar must point towards the back.
Fig. 33 Fitting the back profile rails
7.9.2
Attaching the thermal insulation
▶ The thermal insulation provided corresponds to the boiler size (NOT
DEFINED). The thermal insulation must be arranged on the boiler
block as shown in Fig. 34.
▶ Push the thermal insulation under the boiler block in the lower
section of the boiler. The boiler feet are placed in the cut-outs in the
thermal insulation.
Fig. 34 Thermal insulation
H
Rear (boiler back)
V
Front (boiler front)
6 720 642 621-22.1o
6
1
2
4 3
5
6 720 642 621-26.1o
3
1
2
Boiler capacity
Boiler sections
L [inch] ([mm])
105
5
33" (840)
140
6
39-3/8" (1000)
170
7
45-11/16" (1160)
200
8
52" (1320)
230
9
58-1/4" (1480)
Table 11 Dimensions – thermal insulation
6 720 642 621-27.1o
1
2
6 720 642 621-28.1o
L
V
H
(2820 mm)
111"