Service level menu (for qualified heating engineers only)
7
7.5.14
Swimming pool maximum temperature
Menu: Service > Settings > Swimming pool maximum temperature
If configuration S6 is selected, the maximum temperature of the swimming pool can also be set.
When the maximum temperature is reached, the solar system pump is switched off.
7.5.15
Cylinder charge transfer cut-in temperature differential
Menu: Service > Settings > Charge transfer cut-in temperature differential
In solar systems with preheating cylinder and standby cylinder, the cylinder contents are transferred
as soon as the temperature of the standby cylinder drops below that of the preheating cylinder. The
cut-in temperature differential is definable.
7.5.16
Cylinder charge transfer cut-out temperature differential
Menu: Service > Settings > Charge transfer cut-out temperature differential
If the temperature difference falls below the set figure, cylinder charge transfer is stopped.
Setting range
Default setting
New setting
20 - 90 °C
60 °C
Tab. 27
Setting range
Default setting
New setting
7 - 20 K (°C)
10 K (°C)
Tab. 28
Setting range
Default setting
New setting
4 - 17 K (°C)
5 K (°C)
Tab. 29