Servicing
5
Installation and servicing instructions condensing gas boiler 800 - 24/29/43/60 and 800 - 24T25/29T25 H/V • edition 02/2006
37
Subject to modifications resulting from technical improvements !
Buderus • http://buderus-domestic.co.uk
5
Servicing
5.1
Operating codes
NOTE
If the code displayed on the burner-control unit
is not listed under the operating codes or fault
warnings, the burner-control unit itself is
malfunctioning.
Display
Display after
pressing the
service button
Meaning
0
800 Series is ready for operation
A
Burner interval circuit, 10 minutes from start of burner
C
Waiting for the three-way valve and/or pump to switch
H
Ready for operation
L
First safety period
P; U
Safety period
Y
Flow water temperature setting reached (switching diff2 K)
-.
800 Series runs in heating mode
A
Chimney sweep mode
H
Normal heating mode
Y
Service mode
=.
800 Series runs in hot water mode
H
Normal hot water mode
r
Reset
(after reset button has been pressed for 5 sec. UBA is reset to the switch-on
condition)