47
XI. Electrical
(continued)
2. 24VAC low voltage connections are located on
the left side of PCB-02.
Three fuses and one
spare are provided.
3. 24VDC low voltage connections are located on
the right side of PCB-01 (see Figure 23). One
low voltage fuse and one spare is provided.
D.
Line voltage connections
1.
Connect 120 VAC power wiring to the line
voltage terminal strip in the control box.
2. Provide and install a fused disconnect or
service switch (12 BFIT recommended) as
requried
by the code.
2. To activate system or DWH
pump wire as
shown in Figure 23.
E.
Low voltage connections
1.
Route all low voltage wires through the
junction box's knockouts in the rear of the
boiler.
4. If outdoor temperature sensor is used, connect
sensor to PCB-04, terminals 51 and 52. The
boiler will adjust the target supply water
temperature set point downwards as the
outdoor air temperature increases.
a. The sensor should belocated on the outside
of the structure in an area where it will
sense the average air temperature around
the building. Avoid placing this sensor in
areas where it may be covered with ice or
snow. Locations where the senor will pick
up direct radiation from the sun should also
be avoided.
b. Avoid placing the senor near potential
sources of electrical noise such as
transformers, power lines, and fluorescent
lighting. Wire the sensor to the boiler using
22 gauge or larger wire. As with the sensor,
the sensor wiring should be routed away
from sources of electrical noise. Where it
is impossible to avoid such noise sources,
wire the sensor using a 2 conductor,
UL Type
CM, AWM Style 2092, 300 Volt 60 C
shielded
WARNING
Appliance must be electrically grounded as
required by National Electrical Code ANSI/
NFPA 70-latest edition.
Содержание BFIT 1000
Страница 9: ...9 Figure 1 BFIT MODEL 1000 2000 ...
Страница 12: ...12 IV BFIT Component Identification continued Figure 2 Component Identification ...
Страница 13: ...13 IV BFIT Component Identification continued Figure 3 Component Identification ...
Страница 52: ...52 Figure 24 Operating Instructions XII System Start up continued ...
Страница 66: ...66 APPENDIX D INLET OUTLET WATER AND FLUE OUTLET TEMPERATURE SENSOR RESISTANCE VOLTAGE CHART ...
Страница 68: ...68 ...