55
XII. System Start-up
(continued)
Safety Device Test
Component
Test Method(s)
After Lockout
Annunciation
Actual Alarm
Message
High Gas
Pressure
Switch
Close factory supplied manual gas
valve outside of boiler jacket. Cycle
Boiler.
Manually reset the Concert Boiler
Control and switch. Adjust the switch
to its normal setting.
Hard Lockout.
Gas Pressure
Switch
Low Gas
Pressure
Switch
Increase the setting of the switch
until the switch trips.
Manually reset the Concert Boiler
Control and switch. Ajust the switch
to its normal setting.
Hard Lockout.
Gas Pressure
Switch
Burner Ther
-
mal Fuse
Disconnect one wire of the burner
thermal fuse. Cycle the boiler.
Re-connect wiring to the burner
thermal fuse. Reset burner thermal
fuse lockout.
Hard Lockout.
Burner Thermal
Fuse
Blocked
Condensate
Switch
Disconnect one wire of the blocked
condensate switch. Cycle the boiler.
Re-connect wire to the blocked con
-
densate switch. Reset the blocked
condenate switch lockout.
Hard Lockout.
Blocked Conden
-
sate switch
Low Water
Cutoff
While the boiler running push and
hold the LWCO test button until the
boiler control shuts down the main
burner.
Manually reset the Concert Boiler
Control and reset the LWCO
Hard Lockout.
Low Water
Level.
Water Flow
Switch
Reduce the water flow rate with a
manual shutoff valve until the boiler
shuts down.
Adjust manual valve to normal posi
-
tion.
Low Water Flow
Table 25: Safety Device Tests
Содержание BFIT 1000
Страница 9: ...9 Figure 1 BFIT MODEL 1000 2000 ...
Страница 12: ...12 IV BFIT Component Identification continued Figure 2 Component Identification ...
Страница 13: ...13 IV BFIT Component Identification continued Figure 3 Component Identification ...
Страница 52: ...52 Figure 24 Operating Instructions XII System Start up continued ...
Страница 66: ...66 APPENDIX D INLET OUTLET WATER AND FLUE OUTLET TEMPERATURE SENSOR RESISTANCE VOLTAGE CHART ...
Страница 68: ...68 ...