16
G. General.
1. BFIT boilers are intended for installation in an
area with a floor drain, or in a suitable drain
pan to prevent any leaks or safety relief valve
discharge resulting in property damage.
2. BFIT boilers are not intended to support
external piping and venting. All external
piping and venting must be supported
independently of the boiler.
3. BFIT boilers must be installed on a level
surface to prevent condensate from backing
up inside the boiler. Refer to Table 2 for boiler
approximate shipping weight.
4. Boiler Installation:
a. For basement installation provide a solid
level base such as concrete. Where floor is
not level water may be encountered around
boiler. Floor must be able to support weight
of boiler, water and all additional system
components.
b. Provide adequate space for condensate
piping or a condensate pump, if required.
Contaminants to Avoid
Spray cans containing chlorofluorocarbons
(CFC’s)
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes
dryers
Chlorine-type bleaches, detergents, and
cleaning solvents found in household laundry
rooms.
Adhesives used to fasten building products
and other similar products
Excessive dust and dirt
Areas likely to have contaminants:
Dry cleaning/laundry areas and establish
-
ments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Table 4: Corrosive Combustion Air
Contaminants
VI. Pre-Installation and Boiler Mounting
(continued)
Содержание BFIT 1000
Страница 9: ...9 Figure 1 BFIT MODEL 1000 2000 ...
Страница 12: ...12 IV BFIT Component Identification continued Figure 2 Component Identification ...
Страница 13: ...13 IV BFIT Component Identification continued Figure 3 Component Identification ...
Страница 52: ...52 Figure 24 Operating Instructions XII System Start up continued ...
Страница 66: ...66 APPENDIX D INLET OUTLET WATER AND FLUE OUTLET TEMPERATURE SENSOR RESISTANCE VOLTAGE CHART ...
Страница 68: ...68 ...