background image

800SA/801SA: Installation, Start–Up, Operating and Service and Maintenance Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

22

Inspections before the sale and at the time of installation will determine

the acceptability of the chimney or the need for repair and/or (re)lining.

Refer to the 

Fig. 30

 to perform a chimney inspection. If the inspection of

a previously used tile-lined chimney:

a. Shows signs of vent gas condensation, the chimney should be 

relined in accordance with local codes and the authority having 

jurisdiction. The chimney should be relined with a listed metal 

liner, Type-B vent, or a listed chimney adapter kit shall be used to 

reduce condensation. If a condensate drain is required by local 

code, refer to the current edition of NFGC NFPA54/ANSI 

Z223.1, Section 12.10 for additional information on condensate 

drains.

b. Indicates the chimney exceeds the maximum permissible size in 

the tables, the chimney should be rebuilt or relined to conform to 

the requirements of the equipment being installed and the 

authority having jurisdiction. 

A  chimney  without  a  clay  tile  liner,  which  is  otherwise  in  good

condition, shall be rebuilt to conform to current edition of ANSI/NFPA

211 or be lined with a UL listed metal liner or UL listed Type-B vent.

Relining with a listed metal liner or Type-B vent is considered to be a

vent-in-a-chase. 
If  a  metal  liner  or  Type-B  vent  is  used  to  line  a  chimney,  no  other

appliance shall be vented into the annular space between the chimney

and the metal liner.

EXTERIOR MASONRY CHIMNEY FAN + NAT

INSTALLATIONS WITH TYPE-B DOUBLE-WALL
VENT CONNECTORS 

©

NFPA & AGA

APPLIANCE APPLICATION REQUIREMENTS 

Appliance operation has a significant impact on the performance of the

venting  system.  If  the  appliances  are  sized,  installed,  adjusted,  and

operated properly, the venting system and/or the appliances should not

suffer  from  condensation  and  corrosion.  The  venting  system  and  all

appliances  shall  be  installed  in  accordance  with  applicable  listings,

standards, and codes. 
The furnace should be sized to provide 100 percent of the design heating

load requirement plus any margin that occurs because of furnace model

size  capacity  increments.  Heating  load  estimates  can  be  made  using

approved  methods  available  from  Air  Conditioning  Contractors  of

America (Manual J); American Society  of Heating,  Refrigerating, and

Air-Conditioning  Engineers;  or  other  approved  engineering  methods.

Excessive oversizing of the furnace could cause the furnace and/or vent

to fail prematurely. When a metal vent or metal liner is used, the vent

must be in good condition and be installed in accordance with the vent

manufacturer’s instructions.
To prevent condensation in the furnace and vent system, the following

precautions must be observed: 

1. The return-air temperature must be at least 60°F (16°C)db except

for brief periods of time during warm-up from setback at no lower

than  55°F  (13°C)  db  or  during  initial  start-up  from  a  standby

condition.

2. Adjust the gas input rate per the installation instructions. Low gas

input rate causes low vent gas temperatures, causing condensation

and  corrosion  in  the  furnace  and/or  venting  system.  Derating  is

permitted only for altitudes above 2000 ft. (610 M).

3. Adjust the air temperature rise to the midpoint of the rise range or

slightly  above.  Low  air  temperature  rise  can  cause  low  vent  gas

temperature and potential for condensation problems.

4. Set  the  thermostat  heat  anticipator  or  cycle  rate  to  reduce  short

cycling. 

Air  for combustion  must not  be  contaminated  by  halogen  compounds

which  include  chlorides,  fluorides,  bromides,  and  iodides.  These

compounds  are  found  in  many  common  home  products  such  as

detergent, paint, glue, aerosol spray, bleach, cleaning solvent, salt, and

air freshener, and can cause corrosion of furnaces and vents. Avoid using

such  products  in  the  combustion-air  supply.  Furnace  use  during

construction  of  the  building could cause  the furnace  to  be exposed  to

halogen compounds, causing premature failure of the furnace or venting

system due to corrosion. 
Vent dampers on any appliance connected to the common vent can cause

condensation  and  corrosion  in  the  venting  system.  Do  not  use  vent

dampers on appliances common vented with this furnace. 

ADDITIONAL VENTING REQUIREMENTS

A 4” (101 mm) round vent elbow is supplied with the furnace. A 5-inch

(127 mm) or 6- inch (152 mm) vent connector may be required for some

model  furnaces. A  field-supplied  4-inch-to-5-inch  (101  -  127  mm)  or

4-inch-to-6-inch (101 - 152 mm) sheet metal increaser fitting is required

when 5-inch (127 mm) or 6-inch (152 mm) vent connector is used. See

Fig. 31

 

Fig. 43

 Venting Orientation for approved vent configurations. 

NOTE: 

Vent connector length for connector sizing starts at furnace vent

elbow. The 4-inch vent elbow is shipped for upflow configuration and

may be rotated for other positions. Remove the 3 screws that secure vent

elbow to furnace, rotate furnace vent elbow to position desired, reinstall

screws. The factory-supplied vent elbow does NOT count as part of the

number of vent connector elbows. 

The vent connector can exit the furnace through one of 5 locations on the

casing. 

1. Attach the single wall vent connector to the furnace vent elbow, and

fasten  the  vent  connector  to  the  vent  elbow  with  at  least  two

field-supplied, corrosion-resistant, sheet metal screws located 180°

apart.

NOTE: 

An  accessory  flue  extension  is  available  to  extend  from  the

furnace elbow to outside the furnace casing. See Product Data Sheet for

accessory listing. If flue extension is used, fasten the flue extension to

the vent elbow with at least two field-supplied, corrosion-resistant, sheet

metal screws located 180° apart. Fasten the vent connector to the flue

extension with at least two field-supplied, corrosion resistant sheet metal

screws located 180° apart. 

2. Vent  the  furnace  with  the  appropriate  connector  (see

 

Fig. 31

 

-

Fig. 43

).

3. Determine the correct location of the knockout to be removed.
4. Use a hammer and screwdriver to strike a sharp blow between the

tie points and work  the  slug  back  and forth until the slug breaks

free.

CAUTION

!

BURN HAZARD

Failure to follow this caution may cause personal injury.

Hot  vent  pipe  is  within  reach  of  small  children  when  installed  in

downflow position. See the following instruction.

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs.  Use care and wear

appropriate  protective  clothing,  safety  glasses  and  gloves  when

handling parts and servicing furnaces.

Содержание 800SA

Страница 1: ...r Hour 21 EXTERIOR MASONRY CHIMNEY FAN NAT INSTALLATIONS WITH TYPE B DOUBLE WALL VENT CONNECTORS NFPA AGA 22 VENTING NOTES FOR Fig 31 Fig 43 25 START UP ADJUSTMENT AND SAFETY CHECK 25 GENERAL 25 Table...

Страница 2: ...residential garage must be installed as specified in the warning box in the Location section 9 The furnace may be used for construction heat provided that the furnace installation and operation compli...

Страница 3: ...tion in a Garage CODES AND STANDARDS Follow all national and local codes and standards in addition to these instructions The installation must comply with regulations of the serving gas supplier local...

Страница 4: ...tic discharge can affect electronic components Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control...

Страница 5: ...a volume of at least 50 cubic feet per 1 000 Btuh input rating for all gas appliances installed in the space Spaces having less than 50 cubic feet per 1 000 Btuh require the OUTDOOR COMBUSTION AIR MET...

Страница 6: ...ns from the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 1 For other than fan assisted appliances such as a draft hood equipped water heater A04002 1 SQ IN PER 4000 BTUH DUCTS TO OUTD...

Страница 7: ...and dilution of flue gases However in buildings with unusually tight construction additional air MUST be provided using the methods described in the Outdoor Combustion Air Method section 4 Unusually...

Страница 8: ...Table 3 and Fig 9 3 Construct plenum to dimensions specified see Table 3 and Fig 9 4 If downflow subbase KGASB is used install as shown see Table 10 If Coil Assembly Part No CNPV CNRV CAP and CNR or...

Страница 9: ...red 11 13 16 284 19 483 13 7 16 341 20 5 8 600 Downflow Applications on Combustible Flooring with Cased Coil subbase not required 12 5 16 319 19 483 13 5 16 338 20 508 17 1 2 445 Upflow Applications o...

Страница 10: ...revent screws from pulling out use 2 8 x 3 4 in 19 mm screws into the side and 2 8 x 3 4 in 19 mm screws in the bottom of the furnace casing for each strap see Fig 14 and Fig 15 If the screws are atta...

Страница 11: ...0 ft 3 M of main duct to the first branch take off may require internal acoustical lining As an alternative fibrous ductwork may be used if constructed and installed in accordance with the latest edit...

Страница 12: ...915 915 825 785 740 700 48070E21 Gray Cooling Do not use for heating 1735 1685 1640 1595 1545 1495 1450 1405 1360 1310 Yellow Alt Cooling or alt Heating 1480 1435 1395 1340 1290 1240 1190 1135 1085 10...

Страница 13: ...side inlets a combination of 1 side and the bottom or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM Fig 17 Dimensional Drawing 60110E24 Gray Cooling...

Страница 14: ...of Massachusetts 1 Gas supply connections MUST be performed by a licensed plumber or gas fitter 2 When flexible connectors are used the maximum length shall not exceed 36 inches 915 mm 3 When lever h...

Страница 15: ...NPT plugged tapping accessible for test gauge connection MUST be installed immediately upstream of gas supply connection to furnace and downstream of manual equipment shutoff valve WARNING FIRE OR EXP...

Страница 16: ...electrical circuit with a properly sized fuse or circuit breaker for this furnace See Table 7 for wire size and fuse specifications A readily accessible means of electrical disconnect must be located...

Страница 17: ...WITCH WHT BLK WHT BLK NOTES Connect Y terminal in furnace as shown for proper blower operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be...

Страница 18: ...es into electrical box 9 Remove cover from furnace J Box 10 Route field ground wire through holes in electrical box and casing and into furnace J Box 11 Reattach furnace J Box to furnace casing with s...

Страница 19: ...board thermostat strip The HUM terminal is energized when the pressure switch closes during a call for heat see Fig 28 NOTE DO NOT connect furnace control HUM terminal to HUM humidifier terminal on Th...

Страница 20: ...or condensation in the venting system These furnaces are approved for common venting and multistory venting with other fan assisted or draft hood equipped appliances in accordance with the NFGC the lo...

Страница 21: ...appliances connected to the venting system are not in operation 1 Seal any unused openings in venting system 2 Inspect the venting system for proper size and horizontal pitch as required in the curre...

Страница 22: ...on in the furnace and or venting system Derating is permitted only for altitudes above 2000 ft 610 M 3 Adjust the air temperature rise to the midpoint of the rise range or slightly above Low air tempe...

Страница 23: ...the furnace being vented Follow all manufacturer s installation requirements for venting and termination included with the listed mechanical venter Caution For the following applications use the mini...

Страница 24: ...lication Vent Elbow Left A03208 Fig 36 Upflow Application Vent Elbow Up A03212 Fig 37 Downflow Application Vent Elbow Up then Right A03218 Fig 38 Horizontal Right Application Vent Elbow Right SEE NOTE...

Страница 25: ...Data Sheet for accessory listing 6 Factory authorized accessory Downflow Vent Guard Kit required in downflow installations with lower vent configuration See Product Data Sheet for accessory listing 7...

Страница 26: ...ure will not operate if any thermostat signal is present at the control 4 Component test sequence is as follows see service label attached to furnace or Fig 44 a LED will display previous status code...

Страница 27: ...fices See EXAMPLE 1 3 Adjust manifold pressure to obtain correct input rate a Turn gas valve ON OFF switch to OFF b Remove manifold pressure tap plug from gas valve see Fig 21 c Connect a water column...

Страница 28: ...When thermometer readings stabilize subtract return air temperature from supply air temperature to determine air temperature rise NOTE If the temperature rise is outside this range first check 1 Gas i...

Страница 29: ...Ammeter WARNING FURNACE OVERHEATING HAZARD Failure to follow this caution may result in reduced furnace life Recheck temperature rise It must be within limits specified on the rating plate Recommende...

Страница 30: ...urn thermostat below room temperature or from HEAT to OFF and turn 115v power OFF then back ON 3 Check Pressure Switch This control proves operation of the draft inducer blower a Turn off 115 v power...

Страница 31: ...S switch until LED goes out then reconnect it NOTE If wire to LS or DSS is disconnected longer than 4 sec main blower starts and status code is overwritten with a limit circuit 33 code 2 When above it...

Страница 32: ...wheel as follows 1 Turn off electrical supply to furnace 2 Remove outer door 3 For downflow or horizontal furnaces having vent pipes within the furnace that pass in front of the blower access door a...

Страница 33: ...eavy build up of soot and carbon indicates that a problem exists which needs to be corrected such as improper adjustment of manifold pressure insufficient or poor quality combustion air incorrect size...

Страница 34: ...TV sealant G E 162 P771 9003 is available through RCD in 3 oz tubes 12 Apply new sealant to flange of collector box and attach to cell panel using existing screws making sure all screws are secure 13...

Страница 35: ...zing the humidifier terminal HUM The inducer motor IDM will remain energized for a 5 second post purge period The blower motor BLWM and air cleaner terminal EAC 1 will remain energized for 90 120 150...

Страница 36: ...tart Up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 36 WIRING DIAGRAM A19...

Страница 37: ...f s u o i v e r p o n s a w r a t s l l i w r e c u d n i e h T e c n e u q e s t s e t t n e n o p m o c f e i r b a h g u o r h t o g l l i w n u r d n a t w o l b I S H e h T t s e t t n e n o p m...

Страница 38: ...estricted duct system Loose blower wheel Defective switch or connections Defective blower motor or capacitor Inadequate combustion air supply flame rollout switch open Restricted vent Proper vent sizi...

Страница 39: ...ealer listing by brand name or contact BRYANT HEATING COOLING SYSTEMS Consumer Relations Department P O Box 4952 Syracuse New York 13221 4952 1 800 428 4326 Have available the model number series numb...

Страница 40: ...46231 Edition Date 03 20 Catalog No II800SA 04 Replaces II800SA 03 800SA 801SA Installation Start Up Operating and Service and Maintenance Instructions Manufacturer reserves the right to change at any...

Отзывы: