Fig. 19 -- 2--Stage HP/AC Control Board
STATUS CODE 31, 32 -- PRESSURE SWITCH OR RELAY
DID NOT CLOSE OR REOPENED
Control relay may be defective. If open longer than five minutes,
inducer shuts off for 15 minutes before retry. If opens during
blower on--delay period, blower will come on for the selected
blower off--delay. Check for excessive wind, restricted vent,
defective inducer motor, defective pressure switch, lower inducer
voltage
(230VAC),
inadequate
combustion
air
supply,
disconnected or obstructed pressure tubing, or low inlet gas
pressure (if LGPS used).
STATUS CODE 33 -- LIMIT CIRCUIT FAULT
Indicates a limit or flame rollout switch is open. Blower will run
for 4 minutes or until open switch remakes, whichever is longer. If
open longer than 3 minutes, code changes to lockout 13. If open
less than 3 minutes status code 33 continues to flash until blower
shuts off. Check for loose blower wheel, restricted vent, excessive
wind, dirty filter or restricted duct system, defective switch or
connections, or inadequate combustion air supply (flame roll--out
switch open).
STATUS CODE 34 -- IGNITION PROVING FAILURE
Control will try three more times before lockout 14 occurs. If flame
signal lost during blower on--delay period, blower will come on for
the selected blower off--delay. Check for oxide buildup on flame
sensor (clean with fine steel wool), proper flame sense microamps
(.5 microamps D.C. min., 4.0--6.0 nominal), manual valve
shut--off, low inlet gas pressure, control ground continuity, gas
valve defective or turned off, flame sensor must not be grounded,
inadequate flame carryover or rough ignition, or green/yellow wire
must be connected to unit sheet metal.
STATUS CODE 41 -- BLOWER MOTOR FAULT
Indicates the blower failed to reach 250 RPM or the blower failed
to communicate within the prescribed time limits. Thirty seconds
after being turned ON or ten seconds during steady--state
operation.
STATUS CODE 42 -- INDUCER MOTOR FAULT
Indicates inducer motor hasn’t started within a prescribed time
limit. Check inducer motor and wiring.
STATUS CODE 45 -- CONTROL CIRCUITRY LOCKOUT
Auto reset after one hour lockout due to gas valve relay stuck open,
flame sense circuit failure, or software check error. Reset power to
clear lockout. Replace control if status code repeats.
E. HP/AC Control Troubleshooting
See Table 4 for HP/AC control board status codes and
troubleshooting information.
STATUS CODE 53, OUTDOOR AIR TEMPERATURE
SENSOR FAULT -- DETAILED DESCRIPTION
If an OAT sensor is found at power--up, input is constantly checked
to be within a valid temperature range. If sensor is found to be
open or shorted at any time after initial validation, Status Code 53
will be displayed at amber STATUS LED.
Check for faults in wiring connecting sensor to OAT terminals.
Using an Ohm meter, check resistance of thermistor for a short or
open condition.
If thermistor is shorted or open, replace it to return the system to
normal operation. If fault is in the wiring connections, correcting
the fault will clear the code and return the system to normal
operation.
NOTE: If fault condition is an open thermistor or a wiring problem
that appears to be an open thermistor and the power to the unit is
cycled off, the fault code will be cleared on the next power--up but
the fault will remain and system operation will not be as expected.
This is because on power--up, the unit control cannot discern
the difference between an open sensor or if a sensor is not
installed.
Sequence of Operation
The 677D----A HYBRID HEAT unit is designed for installation
with a communicating UI. This unit will not respond to commands
provided by a common thermostat except under certain emergency
situations described in Step 1—Start--Up and Troubleshooting.
The UI uses temperature, humidity and other data supplied from
indoor and outdoor system components to control heating or
cooling system for optimum comfort. The unit will be commanded
by UI to supply airflow. The unit will operate the indoor blower at
requested airflow for most modes.
677D
--
--
A
Содержание 677D--A
Страница 5: ...5 A09561 Fig 5 677D A24 30 Unit Dimensions 677D A...
Страница 6: ...6 A09562 Fig 6 677D A36 60 Unit Dimensions 677D A...
Страница 18: ...18 A10217C Fig 17 Connection Wiring Schematic 677D A Single Phase Gas Inputs 040 060 090 kBtu hr 677D A...
Страница 19: ...19 A10217L Fig 16 Cont Ladder Wiring Schematic 677D A Single Phase Gas Inputs 040 060 090 kBtu hr 677D A...
Страница 20: ...20 A10219C Fig 18 Connection Wiring Schematic 677D A Single Phase Gas Inputs 115 130 kBtu hr 677D A...
Страница 21: ...21 A10219L Fig 17 Ladder Wiring Schematic 677D A Single Phase Gas Inputs 115 130 kBtu hr 677D A...