background image

26

the UI. When activated, the following sequence of operation will
occur. Reversing valve will energize and compressor will turn off

for 30 seconds, then turn back on to complete defrost. At the end
of the defrost cycle, the reversing valve de--energizes, compressor

will turn off for another 30 seconds, and the fan will turn off for 40

seconds, before starting in the heating mode.
DEHUMIDIFICATION MODE
This Evolution system can be used to dehumidify the living space.
See User Interface Installation Instructions for more details.
SEQUENCE OF OPERATION--GAS HEAT

NOTE

: Evolution control must be grounded for proper operation

or control will lock out.

NOTE

: If a power interruption occurs during a call for heat, the

control will start a 90--second blower--only ON period two seconds
after power is restored, if the UI is still calling for gas heating. The
amber LED light will flash code 12 during the 90--second period,
after which the LED will be ON continuously, as long as no faults
are detected. After the 90--second period, the unit will respond to
the UI normally.
GAS HEAT MODE AND ADJUSTMENTS
When the UI calls for gas heat, the Evolution furnace board

performs a self--check, verifies the pressure switch is open, and
starts the inducer on high speed.

1. Inducer Pre--purge Period: When the inducer motor comes

up on high speed, the pressure switch closes, and the

Evolution ignition control on the furnace board begins a 15
second pre--purge period. If the pressure switch fails to

remain closed, the inducer will remain running. After the
pressure switch re--closes, the Evolution ignition control
will begin a 15 second pre--purge period.

2. Trial--For--Ignition Sequence: The spark igniter will spark

for 3 seconds. The main gas valve relay contact closes to

energize the gas valve on low stage. After 5 seconds, the
igniter is de--energized and a 2--second flame--proving

period begins. NOTE: The unit always lights on high
speed inducer and low stage gas valve operation.

3. Flame--Proving: When the burner flame is proved at the

flame--proving sensor, the furnace control determines what
heating stage to run based on feedback from the UI. If the

UI is asking for low stage gas heat, the ignition control will
change the inducer speed to low speed and keep the gas
valve energized on low stage. If the UI is asking for high

stage gas heat, the ignition control will maintain running the
inducer on high speed and energize the gas valve’s high

stage relay to increase gas flow.

If the burner flame is not proved within 2 seconds, the control will

close the gas valve and repeat the ignition sequence up to 3 more
Trials--For--Ignition before going to Ignition--Lockout. Lockout

will reset automatically after 3 hours, by momentarily interrupting
230 VAC power, or by interrupting 24 VAC power at SEC1 or

SEC2 to the furnace board.
If flame is proved when there should be no flame present, control
will lock out of Gas--Heating mode and operate the inducer motor

until flame is no longer proved.

4. Blower--On Delay:

If the burner flame is proven,

approximately 37 seconds after the gas valve is opened the
Indoor Blower is turned on to the appropriate speed for the

gas heating stage.

Simultaneously, the humidifier terminal HUM and electronic air

cleaner terminal EAC--1 are energized throughout the heating
cycle.

NOTE

:

EAC--2 terminal is common with L2 and will have

115VAC--to--ground when unit is powered.

5. Blower--Off Delay: When the call for gas heat is satisfied,

the gas valve is de--energized, stopping the flow of gas to
the burners, and de--energizing the HUM terminal. The

inducer motor will remain on for a 4--second post--purge
period. The indoor blower and air cleaner terminal EAC--1

will remain energized for 90, 120, 150, or 180 seconds
(depending on selection of blower--off delay selected in the
UI). The factory--set default is 120--second blower--OFF

delay.

CHECK GAS INPUT (NATURAL GAS)

UNIT DAMAGE HAZARD

Failure to follow this caution may result in component

damage.

Do not

redrill an orifice. Improper drilling (burrs,

out--of--round holes, etc.) can cause excessive burner noise

and misdirection of burner flame. If orifice hole appears
damaged or it is suspected to have been redrilled, check

orifice hole with a numbered drill bit of correct size.

!

CAUTION

FIRE HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
DO NOT bottom out gas valve regulator adjusting screws.

This can result in unregulated manifold pressure and result

in excess overfire and heat exchanger failures.

!

WARNING

CARBON MONOXIDE POISONING HAZARD

Failure to follow this warning could result in personal

injury, death and/or property damage.
If the manifold pressure and/or gas rate is not properly

adjusted on HI and LO stages, excess carbon monoxide can

be produced.

!

WARNING

FIRE AND UNIT DAMAGE HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage.
Unsafe operation of the unit may result if manifold pressure

is outside of the ranges listed in Table 6.

!

WARNING

Gas input rates on rating plate are for installations at altitudes up to
2000 ft (610 m). Input rate must be within

±

2% of rating plate

input.

1. Determine the correct gas input rate.

a. The rated gas inputs shown in Table 3 are for altitudes

from sea level to 2000 ft (610 m) above sea level.

These inputs are based on natural gas with a heating
value of 1025 Btu/ft3 at .60 specific gravity.

IN THE U.S.A.:
The input rating for altitudes above 2,000 ft (610 m) must be

reduced by 4 percent for each 1,000 ft (305 m) above sea level.
For installations below 2,000 ft (610 m), refer to the unit rating

plate.

677D

--

--

A

Содержание 677D--A

Страница 1: ...2 Routing Power Leads Into Unit 12 Connecting Ground Lead to Ground Screw 12 Routing Control Power Wires 12 Outdoor Air Temperature Sensor OAT 12 Accessory Installation 13 Special Procedures for 208 v...

Страница 2: ...gned for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or on a cement slab see Fig 4 for roof curb dimensions Standard...

Страница 3: ...ftop be sure the roof will support the additional weight WARNING Rigging and handling of this equipment can be hazardous for many reasons due to the installation location roofs elevated structures etc...

Страница 4: ...NOTES 1 Roof curb must be set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 gauge steel 4 Attach ductwork to curb flanges of d...

Страница 5: ...5 A09561 Fig 5 677D A24 30 Unit Dimensions 677D A...

Страница 6: ...6 A09562 Fig 6 677D A36 60 Unit Dimensions 677D A...

Страница 7: ...9 1 8 825 2800 22 559 1 8 825 2800 22 559 1 8 825 INDOOR COIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variabl...

Страница 8: ...ser Interface instructions for more information Efficiency 1400 1400 1400 1750 1750 1750 Max 1600 1600 1600 2000 2000 2000 Furnace gas ht airflow Low Stage 815 1215 1255 845 1215 1255 Furnace gas ht a...

Страница 9: ...ng could result in personal injury or death For vertical supply and return units tools or parts could drop into ductwork therefore install a 90 degree turn in the return ductwork between the unit and...

Страница 10: ...ast 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tube using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper...

Страница 11: ...ompound pipe dope sparingly and only to male threads of joint when making pipe connections Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and or nati...

Страница 12: ...anel See Fig 5 and 6 for location and size For single phase units connect leads to the black and yellow wires CONNECTING GROUND LEAD TO GROUND SCREW Connect the ground lead to the chassis using the gr...

Страница 13: ...humidifier off Wire HUM and COM terminals directly to humidifier as shown in Fig 14 B Electronic Air Cleaner Electronic Air Cleaner terminals are provided on the Evolution Control Board EAC 1 and EAC...

Страница 14: ...14 FURNACE BOARD HP AC BOARD OAT PACKAGE TWO BLACK WIRES TO CONNECT OAT SENSOR A12248 Fig 13 Control Plate A06357 Fig 14 Control Voltage Wiring Connections 677D A...

Страница 15: ...al start up 1 Remove all access panels See Fig 25 2 Read and follow instructions on all DANGER WARNING CAUTION and INFORMATION labels attached to or shipped with unit 3 Make the following inspections...

Страница 16: ...Code 16 System Communication Fault on amber STATUS LED No further troubleshooting information will be available at UI until communications are re established If either COMM LED does not light within...

Страница 17: ...fer to status code 33 STATUS CODE 14 IGNITION LOCKOUT Control will auto reset after three hours Refer to status code 34 STATUS CODE 15 BLOWER MOTOR LOCKOUT Indicates the blower failed to reach 250 RPM...

Страница 18: ...18 A10217C Fig 17 Connection Wiring Schematic 677D A Single Phase Gas Inputs 040 060 090 kBtu hr 677D A...

Страница 19: ...19 A10217L Fig 16 Cont Ladder Wiring Schematic 677D A Single Phase Gas Inputs 040 060 090 kBtu hr 677D A...

Страница 20: ...20 A10219C Fig 18 Connection Wiring Schematic 677D A Single Phase Gas Inputs 115 130 kBtu hr 677D A...

Страница 21: ...21 A10219L Fig 17 Ladder Wiring Schematic 677D A Single Phase Gas Inputs 115 130 kBtu hr 677D A...

Страница 22: ...onds during steady state operation STATUS CODE 42 INDUCER MOTOR FAULT Indicates inducer motor hasn t started within a prescribed time limit Check inducer motor and wiring STATUS CODE 45 CONTROL CIRCUI...

Страница 23: ...apsed Pressing the FAN and TEMPERATURE UP buttons simultaneously defeats cycle timers See UI installation instructions for more detail HEAT PUMP SEQUENCE OF OPERATION COOLING AND HEATING OPERATION Wit...

Страница 24: ...ir Temp Sensor Fault 53 Outdoor air sensor not reading or out of range Ohm out sensor and check wiring Outdoor Coil Sensor Fault 55 Coil sensor not reading or out of range Ohm out sensor and check wir...

Страница 25: ...n is off when outdoor coil temp is outdoor air temperature plus 1_F 6_C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In high stage and low sta...

Страница 26: ...omentarily interrupting 230 VAC power or by interrupting 24 VAC power at SEC1 or SEC2 to the furnace board If flame is proved when there should be no flame present control will lock out of Gas Heating...

Страница 27: ...ontrol Valve NOTE DO NOT set low stage manifold pressure less than 1 4 IN W C or more than 2 0 IN W C for natural gas If manifold pressure is outside this range change main burner orifices f Re instal...

Страница 28: ...a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90 090 Btuh input In this example the nominal input rate for high stage is 90 000 Btu hr so the high...

Страница 29: ...operation COMPONENT TEST The Evolution Furnace Board features a gas component test system to help diagnose a system problem in the case of a gas component failure To initiate the component test proced...

Страница 30: ...be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to determine what the liquid...

Страница 31: ...047 42 0 014 0 017 0 020 0 024 0 027 0 031 0 035 0 039 0 043 48 0 027 0 032 0 036 0 041 0 046 0 052 0 057 0 063 0 068 60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 Table 8 Filter Pressure Drop Table IN...

Страница 32: ...as recommended in the accessory instructions Air Filter IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replace the filter with the same dimensional...

Страница 33: ...oil Straighten bent fins with a fin comb If coated with dirt or lint clean the coils with a vacuum cleaner using the soft brush attachment Be careful not to bend the fins If coated with oil or grease...

Страница 34: ...iquid line and protects against low suction pressures caused by such events as loss of charge low airflow across indoor coil dirty filters etc It opens if the system pressure drops to about 20 psig If...

Страница 35: ...cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position For cylinders equipped with a dip tube charge Puron units with cylinder in upright position and a com...

Страница 36: ...en low and high stage operation so liquid pressure should not be used for troubleshooting Compressor current should increase 20 45 when switching from low to high stage The compressor solenoid when en...

Страница 37: ...ht position Cylinders manufactured March 1 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow S Recovery cylinder service pressure rating must be 400 psig...

Страница 38: ...load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrigerant evacuate system and re charge O...

Страница 39: ...t 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace filter...

Страница 40: ...UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR PRES...

Отзывы: