Table 4 – Heat Pump/Air Conditioner Board Status Codes

OPERATION

FAULT

AMBER

LED

FLASH

CODE

POSSIBLE CAUSE AND ACTION

Standby – no call for unit opera-

tion

None

On solid,

no flash

Normal operation.

Emergency Mode

Standard Ther-

mostat Control

Rapid, con-

tinuous

flashing

Unit being controlled by standard thermostat inputs instead of

Evolution Control. Only high stage operation is available. This

operating mode should be used in emergency situations only.

Low Stage Cool/Heat Operation

None

1, pause

Normal operation.

High Stage Cool/Heat Opera-

tion

None

2, pause

Normal operation.

System Commu-

nications Failure

16

Communication with UI lost. Check wiring to UI, indoor and outdoor

units.

Invalid Model

Plug

25

Control does not detect a model plug or detects an invalid model

plug. Unit will not operate without correct model plug.

High---Pressure

Switch Open

31

High---pressure switch trip. Check refrigerant charge, outdoor fan

operation and coils for airflow restrictions.

Low---Pressure

Switch Open

32

Low---pressure switch trip. Check refrigerant charge and indoor air

flow.

Control Fault

45

Outdoor unit control board has failed. Control board needs to be

replaced.

Brown Out

(230 v)

46

Line voltage < 187v for at least 4 seconds. Compressor and fan

operation not allowed until voltage>190v. Verify line voltage.

No 230v at Unit

47

There is no 230v at the contactor when indoor unit is powered and

cooling/heating demand exists. Verify the disconnect is closed and

230v wiring is connected to the unit.

Outdoor Air

Temp Sensor

Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor

and check wiring.

Outdoor Coil

Sensor Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check

wiring.

Thermistors Out

of Range

56

Improper relationship between coil sensor and outdoor air sensor.

Ohm out sensors and check wiring.

Low Stage Ther-

mal Cutout

71

Compressor voltage sensed, then disappears while cooling or heat-

ing demand exists. Possible causes are internal compressor over-

load trip or start relay not releasing (if installed).

High Stage Ther-

mal Cutout

72

Compressor voltage sensed, then disappears while cooling or heat-

ing demand exists. Possible causes are internal compressor over-

load trip or start relay not releasing (if installed).

Contactor

Shorted

73

Compressor voltage sensed when no demand for compressor op-

eration exists. Contactor may be stuck closed or there is a wiring

error.

No 230V at

Compressor

74

Compressor voltage not sensed when compressor should be start-

ing. Contactor may be stuck open or there is a wiring error.

Low Stage Ther-

mal Lockout

81

Thermal cutout occurs in three consecutive low/ high stage cycles.

Low stage locked out for 4 hours or until 24v power recycled.

High Stage Ther-

mal Lockout

82

Thermal cutout occurs in three consecutive high/low stage cycles.

High stage locked out for 4 hours or until 24v power recycled.

Low---Pressure

Lockout

83

Low---pressure switch trip has occurred during 3 consecutive

cycles. Unit operation locked out for 4 hours or until 24v power

recycled.

High---Pressure

Lockout

84

High---pressure switch trip has occurred during 3 consecutive

cycles. Unit operation locked out for 4 hours or until 24v power

recycled.

677D

--

--

A

Содержание 677D--A

Страница 1: ...2 Routing Power Leads Into Unit 12 Connecting Ground Lead to Ground Screw 12 Routing Control Power Wires 12 Outdoor Air Temperature Sensor OAT 12 Accessory Installation 13 Special Procedures for 208 v...

Страница 2: ...gned for outdoor installation See Fig 1 Standard units are shipped in a horizontal discharge configuration for installation on a rooftop or on a cement slab see Fig 4 for roof curb dimensions Standard...

Страница 3: ...ftop be sure the roof will support the additional weight WARNING Rigging and handling of this equipment can be hazardous for many reasons due to the installation location roofs elevated structures etc...

Страница 4: ...NOTES 1 Roof curb must be set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 gauge steel 4 Attach ductwork to curb flanges of d...

Страница 5: ...5 A09561 Fig 5 677D A24 30 Unit Dimensions 677D A...

Страница 6: ...6 A09562 Fig 6 677D A36 60 Unit Dimensions 677D A...

Страница 7: ...9 1 8 825 2800 22 559 1 8 825 2800 22 559 1 8 825 INDOOR COIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 3 17 4 7 3 17 4 7 INDOOR FAN Nominal Airflow Cfm Comfort Variabl...

Страница 8: ...ser Interface instructions for more information Efficiency 1400 1400 1400 1750 1750 1750 Max 1600 1600 1600 2000 2000 2000 Furnace gas ht airflow Low Stage 815 1215 1255 845 1215 1255 Furnace gas ht a...

Страница 9: ...ng could result in personal injury or death For vertical supply and return units tools or parts could drop into ductwork therefore install a 90 degree turn in the return ductwork between the unit and...

Страница 10: ...ast 1 in 25 mm lower than the unit drain pan condensate connection to prevent the pan from overflowing Connect a drain tube using a minimum of field supplied 3 4 in PVC or field supplied 3 4 in copper...

Страница 11: ...ompound pipe dope sparingly and only to male threads of joint when making pipe connections Use only pipe dope that is resistant to action of liquefied petroleum gases as specified by local and or nati...

Страница 12: ...anel See Fig 5 and 6 for location and size For single phase units connect leads to the black and yellow wires CONNECTING GROUND LEAD TO GROUND SCREW Connect the ground lead to the chassis using the gr...

Страница 13: ...humidifier off Wire HUM and COM terminals directly to humidifier as shown in Fig 14 B Electronic Air Cleaner Electronic Air Cleaner terminals are provided on the Evolution Control Board EAC 1 and EAC...

Страница 14: ...14 FURNACE BOARD HP AC BOARD OAT PACKAGE TWO BLACK WIRES TO CONNECT OAT SENSOR A12248 Fig 13 Control Plate A06357 Fig 14 Control Voltage Wiring Connections 677D A...

Страница 15: ...al start up 1 Remove all access panels See Fig 25 2 Read and follow instructions on all DANGER WARNING CAUTION and INFORMATION labels attached to or shipped with unit 3 Make the following inspections...

Страница 16: ...Code 16 System Communication Fault on amber STATUS LED No further troubleshooting information will be available at UI until communications are re established If either COMM LED does not light within...

Страница 17: ...fer to status code 33 STATUS CODE 14 IGNITION LOCKOUT Control will auto reset after three hours Refer to status code 34 STATUS CODE 15 BLOWER MOTOR LOCKOUT Indicates the blower failed to reach 250 RPM...

Страница 18: ...18 A10217C Fig 17 Connection Wiring Schematic 677D A Single Phase Gas Inputs 040 060 090 kBtu hr 677D A...

Страница 19: ...19 A10217L Fig 16 Cont Ladder Wiring Schematic 677D A Single Phase Gas Inputs 040 060 090 kBtu hr 677D A...

Страница 20: ...20 A10219C Fig 18 Connection Wiring Schematic 677D A Single Phase Gas Inputs 115 130 kBtu hr 677D A...

Страница 21: ...21 A10219L Fig 17 Ladder Wiring Schematic 677D A Single Phase Gas Inputs 115 130 kBtu hr 677D A...

Страница 22: ...onds during steady state operation STATUS CODE 42 INDUCER MOTOR FAULT Indicates inducer motor hasn t started within a prescribed time limit Check inducer motor and wiring STATUS CODE 45 CONTROL CIRCUI...

Страница 23: ...apsed Pressing the FAN and TEMPERATURE UP buttons simultaneously defeats cycle timers See UI installation instructions for more detail HEAT PUMP SEQUENCE OF OPERATION COOLING AND HEATING OPERATION Wit...

Страница 24: ...ir Temp Sensor Fault 53 Outdoor air sensor not reading or out of range Ohm out sensor and check wiring Outdoor Coil Sensor Fault 55 Coil sensor not reading or out of range Ohm out sensor and check wir...

Страница 25: ...n is off when outdoor coil temp is outdoor air temperature plus 1_F 6_C or outdoor fan has been ON for 30 minutes Fan is turned off to allow refrigerant system to stabilize S In high stage and low sta...

Страница 26: ...omentarily interrupting 230 VAC power or by interrupting 24 VAC power at SEC1 or SEC2 to the furnace board If flame is proved when there should be no flame present control will lock out of Gas Heating...

Страница 27: ...ontrol Valve NOTE DO NOT set low stage manifold pressure less than 1 4 IN W C or more than 2 0 IN W C for natural gas If manifold pressure is outside this range change main burner orifices f Re instal...

Страница 28: ...a 84 sec to complete one revolution b 3600 84 42 9 c 42 9 x 2 85 8 ft3 of gas flow hr d 85 8 x 1050 90 090 Btuh input In this example the nominal input rate for high stage is 90 000 Btu hr so the high...

Страница 29: ...operation COMPONENT TEST The Evolution Furnace Board features a gas component test system to help diagnose a system problem in the case of a gas component failure To initiate the component test proced...

Страница 30: ...be within the normal operating range of the unit TO USE COOLING CHARGING CHARTS Take the liquid line temperature and read the manifold pressure gauges Refer to the chart to determine what the liquid...

Страница 31: ...047 42 0 014 0 017 0 020 0 024 0 027 0 031 0 035 0 039 0 043 48 0 027 0 032 0 036 0 041 0 046 0 052 0 057 0 063 0 068 60 0 029 0 032 0 036 0 040 0 045 0 049 0 053 Table 8 Filter Pressure Drop Table IN...

Страница 32: ...as recommended in the accessory instructions Air Filter IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replace the filter with the same dimensional...

Страница 33: ...oil Straighten bent fins with a fin comb If coated with dirt or lint clean the coils with a vacuum cleaner using the soft brush attachment Be careful not to bend the fins If coated with oil or grease...

Страница 34: ...iquid line and protects against low suction pressures caused by such events as loss of charge low airflow across indoor coil dirty filters etc It opens if the system pressure drops to about 20 psig If...

Страница 35: ...cylinders contain a dip tube to allow liquid refrigerant to flow from cylinder in upright position For cylinders equipped with a dip tube charge Puron units with cylinder in upright position and a com...

Страница 36: ...en low and high stage operation so liquid pressure should not be used for troubleshooting Compressor current should increase 20 45 when switching from low to high stage The compressor solenoid when en...

Страница 37: ...ht position Cylinders manufactured March 1 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow S Recovery cylinder service pressure rating must be 400 psig...

Страница 38: ...load or increase unit size UI temperature set too low too high Reset UI setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrigerant evacuate system and re charge O...

Страница 39: ...t 2 Check gas valve Inducer pressure switch not closing 1 Check pressure switch wires connections and tubing Repair or replace if necessary Inadequate heating Dirty air filter Clean or replace filter...

Страница 40: ...UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR PRES...

Отзывы: