—5—

 

Factory-installed options

 

Coil options

 

 include Tin-Plated* indoor hairpins, copper/copper

and vinyl-coated construction for refrigerant coils. Units are
shipped standard with copper tube/aluminum fin construction.
See model number nomenclature for coil options.
*Tin-Plated indoor coils are built with special hairpins that are de-
signed to resist both general pitting corrosion and excessive in-
door corrosion (Formicary Corrosion).

 

Field-installed accessories

 

Economizer with solid-state controls and barometric relief
dampers 

 

includes filter racks and provide outdoor air during

cooling and reduce compressor operation.

 

Manual outside air damper

 

 includes hood and filter rack with

adjustable damper blade for up to 25% outdoor air.

 

Electric heaters 

 

provide additional heat in the unit when re-

quired. Each package has a heater module that slides into the
controls compartment. Heater sizes range from 5.0 to 20.0 kw.
The electric heater design allows the use of a single-point power
supply for the entire unit, resulting in lower installed costs.

 

Flat roof curbs

 

 in both 8 in. and 14 in. sizes are available for

roof mounted applications.

 

Square-to-round duct transition kit

 

  enables 024-048 size

units to be fitted to 14 in. round ductwork.

 

Thermostats

 

 provide control for the system heating and cooling

functions. Thermostat models are available in both programma-
ble and non-programmable versions.

 

Lifting kit 

 

includes 4 metal brackets that are used to assist in lift-

ing this product onto a roof application.

 

Crankcase heater

 

  provides anti-floodback protection for low-

load cooling applications.

 

Low-ambient kit (Motormaster II control) 

 

allows the use of

mechanical cooling down to outdoor temperatures as low as
0°F.

 

Filter rack

 

  features easy installation, serviceability, and high-

filtering performance for vertical or horizontal applications.

 

Compressor hard start kit

 

 assists compressor start-up by pro-

viding additional starting torque on single phase units and pro-
longs compressor motor life.

 

Economizer with Solid-State Controls and Barometric

Relief Dampers

Manual Air Damper (25% open)

Electric Heaters

Filter Rack

Flat Roof Curbs (8-in. and 14-in.)

Square-to-Round Duct Transition Kit

Thermostats

Crankcase Heater

Low Ambient Kit (Motormaster® II Control)

Lifting Kit

Compressor Hard Start Kit

 

ELECTRIC HEATERS

 

LEGEND

ODS — Order Distribution System
NOTE: Electric heaters are rated at 240v. Refer to Multiplication Factors table for other voltages.

 

MINIMUM AIRFLOW FOR RELIABLE ELECTRIC HEATER OPERATION

 

ODS CATALOG

ORDERING NO.

NOMINAL CAPACITY 

(kW)

USED WITH SIZES

024

030

036

042

048

060

ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)

CPHEATER052A00

 

5.0

X

X

X

X

 

CPHEATER064A00

 

5.0

X

X

 

CPHEATER070A00

 

7.5

X

X

X

X

X

X

 

CPHEATER050A00

 

10.0

X

X

X

X

X

X

 

CPHEATER066A00

 

15.0

X

X

X

X

 

CPHEATER054A00

 

20.0

X

X

X

 

ELECTRIC HEATERS (208/230 — 3 PHASE — 60 Hz)

CPHEATER055A00

 

5.0

X

X

X

X

 

CPHEATER056A00

 

10.0

X

X

X

 

CPHEATER068A00

 

10.0

X

 

CPHEATER058A00

 

15.0

X

X

X

X

 

CPHEATER067A00

 

20.0

X

X

X

 

UNIT-604B

024

030

036

042

048

060

AIRFLOW

 

750

1025

1250

1285

1710

1800

 

OPTIONS AND ACCESSORIES

Содержание 604B

Страница 1: ...contamination to help promote longer life and dependable operation Vibration isolation pro vides quiet operation Compressors have internal high pressure and overcurrent protection Convertible duct con...

Страница 2: ...from being affected by the outdoor ambient temperature and provides improved indoor air quality Conforms to American Society of Heating Refriger ation and Air Conditioning Engineers No 62P The sloped...

Страница 3: ...TY BTUH 47 F HIGH HEAT COP 47 F LOW HEAT CAPACITY BTUH 17 F LOW HEAT COP 17 F HSPF 024 24 000 3 4 14 400 2 2 7 8 030 29 000 3 4 16 000 2 2 8 0 036 36 000 3 4 19 600 2 1 8 0 042 40 500 3 4 21 600 2 2 8...

Страница 4: ...8 825 2700 22 1 8 825 2800 22 1 8 825 2800 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 INDOOR COIL Rows Fins in Face Area sq ft 3 15 3 7 3 15 3 7 4 15 3 7 3 15 4 7 4 15 4 7 4 15 5 7 STANDARD INDOOR...

Страница 5: ...ts that are used to assist in lift ing this product onto a roof application Crankcase heater provides anti floodback protection for low load cooling applications Low ambient kit Motormaster II control...

Страница 6: ...6 ECONOMIZER FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL...

Страница 7: ...HEIGHT in mm A CENTER OF GRAVITY in mm lb kg X Y Z 604B024 208 230 1 60 350 159 37 02 940 3 20 0 508 0 19 3 489 0 17 6 447 0 604B030 208 230 1 60 350 159 39 02 991 1 20 0 508 0 19 3 489 0 17 6 447 0 6...

Страница 8: ...CENTER OF GRAVITY in mm lb kg X Y Z 604B042 208 230 1 60 208 230 3 60 440 200 42 98 1091 7 21 533 4 20 5 520 7 16 6 421 6 604B048 208 230 1 60 208 230 3 60 463 210 44 98 1142 5 19 5 495 3 17 6 447 6...

Страница 9: ...ng B x C Long Support D 44 5 16 1125 5mm Return opening B X C Insulated deck pan Short Support C Typ UNIT SIZE ODS ORDER NO A in mm B in mm C in mm D in mm ROOF CURB 024 036 CPRFCURB006A00 8 203 11 27...

Страница 10: ...ric Heater table on page 5 for 208 230 v single phase unit The 5 kW heater at 240v most closely satisfies the heating required To calculate kw at 230v multiply the heater kw by multiplication factor 0...

Страница 11: ...Outdoor Coil F db at 70 rh 10 0 10 17 20 60 800 TC 7 05 6 52 9 38 8 63 11 68 10 72 27 90 25 44 14 58 13 22 kW 1 49 1 56 1 63 1 69 1 71 900 TC 7 27 6 73 9 55 8 79 11 92 10 94 13 67 12 46 14 81 13 43 kW...

Страница 12: ...3 2 3 2 3 2 604B030 Return Air F db CFM Standard Air Air Temperature Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 60 875 TC 9 4 8 7 11 9 10 9 14 4 13 2 16 3 14 9 17 2 15 6 kW 1 74 1 81 1 89 1 97...

Страница 13: ...5 604B036 Return Air F db CFM Standard Air Air Temperature Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 60 1100 TC 12 1 11 2 15 1 13 9 18 5 16 9 21 4 19 5 22 8 20 7 kW 2 25 2 34 2 43 2 49 2 51 1...

Страница 14: ...604B042 Return Air F db CFM Standard Air Air Temperature Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 60 1225 TC 13 6 12 5 16 6 15 3 19 7 18 1 22 2 20 2 23 7 21 5 kW 2 42 2 51 2 64 2 76 2 81 140...

Страница 15: ...0 60 1400 TC 15 10 14 00 18 60 17 10 22 40 20 50 25 20 23 00 26 90 24 40 kW 2 66 2 76 2 87 2 95 3 00 1600 TC 15 40 14 30 18 90 17 40 22 70 20 90 25 60 23 30 27 30 24 80 kW 2 70 2 79 2 89 2 96 3 03 180...

Страница 16: ...0 rh 10 0 10 17 20 60 1500 TC 17 89 16 55 22 37 20 58 27 39 25 14 27 90 25 44 33 30 30 20 kW 3 14 3 33 3 56 3 71 3 76 1750 TC 18 44 17 06 22 91 21 08 28 07 25 77 32 32 29 47 34 25 31 06 kW 3 23 3 39 3...

Страница 17: ...and the heat required to defrost it NOTES 1 Ratings are net they account for the effects of the evaporator fan motor power and heat 2 Direct interpolation is permissible Do not extrapolate 3 The foll...

Страница 18: ...NG 1110 1025 970 1235 1175 1115 1400 1355 1280 COOLING DEHUMIDIFY 990 960 910 990 975 940 1125 1110 1085 HEAT PUMP COMFORT 1035 975 910 1160 1080 1020 1305 1275 1220 UNIT SIZE CFM ADJUST PIN SELECT LO...

Страница 19: ...800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 024 030 20 X 20 X 1 0 05 0 07 0 08 0 10 0 12 0 13 0 14 0 15 36 20 X 24 X 1 0 09 0 10 0 11 0 13 0 14 0 15 0 16 042 048 060...

Страница 20: ...R NEC FROM POWER SOURCE RETURN AIR TOP COVER NEC NATIONAL ELECTRICAL CODE TYPICAL PIPING AND WIRING ROOF RETURN AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUC...

Страница 21: ...evaporator airflow through the units should not exceed 450 cfm ton Minimum cooling airflow The minimum airflow is 350 cfm ton for cooling mode Airflow can be lower in certain modes when humidity remov...

Страница 22: ...20 8 26 30 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 2 73 2 80 8 87 8 103 4 113 8 126 0 139 9 45 45 80 80 90 90 100 100 125 125 150 150 208 230 3 60 187 253 15 4 88 0 0 9 6 8 3 8 5 0 7 5 1...

Страница 23: ...where a phase imbalance in supply volt age is greater than 2 Use the following formula to determine the percentage of voltage imbalance Voltage imbalance max voltage deviation from average voltage 10...

Страница 24: ...24 TYPICAL WIRING SCHEMATIC 230 1 60 SHOWN...

Страница 25: ...25 TYPICAL WIRING SCHEMATIC 208 230 3 60 SHOWN 1 3 2...

Страница 26: ...c heat When thermostat is satisfied contacts open deenergizing contactor and relay motors and heaters deenergize The IFM is controlled by the Easy Select board Defrost Defrost board DB is a time and t...

Страница 27: ...ction 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor fan shall be variable speed motor and con trol as shown on equipment drawings 2 Fan wheel shall be made from steel and shal...

Страница 28: ...h can be preset to admit outdoor air for year round ventilation 5 Thermostat To provide for two stage heating and one stage cooling in addition manual or automatic changeover and indoor fan control 6...

Отзывы: