PACKAGED HEAT PUMP UNITS 
CONSTANT VOLUME APPLICATION

HVAC GUIDE SPECIFICATIONS

SIZE RANGE: 

2 TO 5 TONS, NOMINAL COOLING

BRYANT MODEL NUMBER:

 604B

PART 1—GENERAL

SYSTEM DESCRIPTION

Outdoor rooftop or ground mounted, heat pump unit uti-
lizing a hermetic compressor for heating and cooling
duty and optional electric heating. Unit shall discharge
supply air vertically or horizontally as shown on contract
drawings. Outdoor fan/coil section shall have a draw-
thru design with vertical discharge for minimum sound
levels.

QUALITY ASSURANCE

A. Unit shall be rated in accordance with ARI Standards 210/

240-94 and 270-95.

B. Unit shall be designed in accordance with UL Standard

1995.

C. Unit shall be manufactured in a facility registered to ISO

9001 manufacturing quality standard.

D. Unit shall be UL listed and c-UL certified as a total package

for safety requirements.

E. Roof curb shall be designed to conform to NRCA Stan-

dards.

F. Insulation and adhesives shall meet NFPA 90A require-

ments for flame spread and smoke generation.

G. Cabinet insulation shall meet ASHRAE Standard 62P.

DELIVERY, STORAGE AND HANDLING

Unit shall be stored and handled per manufacturer’s

recommendations.

PART 2 — PRODUCTS

EQUIPMENT

A. General:

Factory-assembled, single-piece, heat pump unit. Con-
tained within the enclosure shall be all factory wiring, pip-
ing, controls, refrigerant charge (R-410A), and special
features required prior to field start-up.

B. Unit Cabinet:

1. Unit cabinet shall be constructed of phosphated, zinc-

coated, pre-painted steel capable of withstanding 500
hrs of salt spray.

2. Normal service shall be through a single removable

cabinet panel.

3. The unit shall be constructed on a rust proof unit base

that has an externally trapped, integrated sloped drain
pan.

4. Indoor fan compartment top surface shall be insulated

with a minimum 1/2-in. thick, flexible fiberglass insula-
tion, coated on the air side and retained by adhesive
and mechanical means. The indoor wall sections will
be insulated with a minimum semi-rigid foil-faced board
capable of being wiped clean. Aluminum foil-faced fi-
berglass insulation shall be used in the entire indoor air
cavity section.

5. Unit shall have a field-supplied condensate trap.

C. Fans:

1. The indoor fan shall be variable speed motor and con-

trol, as shown on equipment drawings.

2. Fan wheel shall be made from steel, and shall be dou-

ble-inlet type with forward curved blades with corrosion
resistant finish. Fan wheel shall be dynamically bal-
anced.

3. Outdoor fan shall be direct drive propeller type with alu-

minum blades riveted to corrosion resistant steel spi-
ders, be dynamically balanced, and discharge air
vertically.

D. Compressor:

1. Fully hermetic compressors with factory-installed vibra-

tion isolation.

2. Scroll compressors shall be standard on all units.
3. Compressor Protection:

Defrost control shall protect compressor by preventing
“short cycling.”

E. Coils:

Indoor and outdoor coils shall have aluminum plate fins
mechanically bonded to seamless copper tubes with all
joints brazed. (Copper/copper and vinyl-coated construc-
tion available as option.) Tube sheet openings shall be
belled to prevent tube wear.

F. Refrigerant Metering Device:

Refrigerant metering device shall be of the single body
fixed orifice feed type (outdoor) and TXV (indoor).

G. Filters:

Filter section shall consist of field-installed, throwaway, 1-
in. thick fiberglass filters of commercially available sizes.

H. Controls and Safeties:

1. Unit controls shall be complete with a self-contained

low voltage control circuit.

2. Units shall incorporate an internal compressor protec-

tor that provides reset capability.

3. Unit shall provide High and Low/Loss-of-Charge Pres-

sure Safety Protection.

I.

Operating Characteristics:
1. Unit shall be capable of starting and running at 125°F

ambient outdoor temperature, exceeding maximum
load criteria of ARI Standard 240-94.

2. Compressor with standard controls shall be capable of

operation down to 55° F ambient outdoor temperature in
cooling and -10°F in heating.

3. Fan on/off delay profile is selected (for compressor

modes) on the Easy Select™ board.

J. Electrical Requirements:

All unit power wiring shall enter the unit cabinet at a single

location.

K. Motors:

1. Compressor motors shall be of the refrigerant-cooled

type with line-break thermal and current overload pro-
tection.

2. All fan motors shall have permanently lubricated bear-

ings, and inherent, automatic reset, thermal overload
protection.

3. Outdoor fan motor shall be totally enclosed.

GUIDE SPECIFICATIONS

Содержание 604B

Страница 1: ...contamination to help promote longer life and dependable operation Vibration isolation pro vides quiet operation Compressors have internal high pressure and overcurrent protection Convertible duct con...

Страница 2: ...from being affected by the outdoor ambient temperature and provides improved indoor air quality Conforms to American Society of Heating Refriger ation and Air Conditioning Engineers No 62P The sloped...

Страница 3: ...TY BTUH 47 F HIGH HEAT COP 47 F LOW HEAT CAPACITY BTUH 17 F LOW HEAT COP 17 F HSPF 024 24 000 3 4 14 400 2 2 7 8 030 29 000 3 4 16 000 2 2 8 0 036 36 000 3 4 19 600 2 1 8 0 042 40 500 3 4 21 600 2 2 8...

Страница 4: ...8 825 2700 22 1 8 825 2800 22 1 8 825 2800 22 1 8 825 3300 22 1 4 1100 3300 22 1 4 1100 INDOOR COIL Rows Fins in Face Area sq ft 3 15 3 7 3 15 3 7 4 15 3 7 3 15 4 7 4 15 4 7 4 15 5 7 STANDARD INDOOR...

Страница 5: ...ts that are used to assist in lift ing this product onto a roof application Crankcase heater provides anti floodback protection for low load cooling applications Low ambient kit Motormaster II control...

Страница 6: ...6 ECONOMIZER FILTER RACK MANUAL OUTSIDE AIR DAMPER DAMPER BLADE MANUAL OUTSIDE AIR HOOD REPLACEMENT PANEL...

Страница 7: ...HEIGHT in mm A CENTER OF GRAVITY in mm lb kg X Y Z 604B024 208 230 1 60 350 159 37 02 940 3 20 0 508 0 19 3 489 0 17 6 447 0 604B030 208 230 1 60 350 159 39 02 991 1 20 0 508 0 19 3 489 0 17 6 447 0 6...

Страница 8: ...CENTER OF GRAVITY in mm lb kg X Y Z 604B042 208 230 1 60 208 230 3 60 440 200 42 98 1091 7 21 533 4 20 5 520 7 16 6 421 6 604B048 208 230 1 60 208 230 3 60 463 210 44 98 1142 5 19 5 495 3 17 6 447 6...

Страница 9: ...ng B x C Long Support D 44 5 16 1125 5mm Return opening B X C Insulated deck pan Short Support C Typ UNIT SIZE ODS ORDER NO A in mm B in mm C in mm D in mm ROOF CURB 024 036 CPRFCURB006A00 8 203 11 27...

Страница 10: ...ric Heater table on page 5 for 208 230 v single phase unit The 5 kW heater at 240v most closely satisfies the heating required To calculate kw at 230v multiply the heater kw by multiplication factor 0...

Страница 11: ...Outdoor Coil F db at 70 rh 10 0 10 17 20 60 800 TC 7 05 6 52 9 38 8 63 11 68 10 72 27 90 25 44 14 58 13 22 kW 1 49 1 56 1 63 1 69 1 71 900 TC 7 27 6 73 9 55 8 79 11 92 10 94 13 67 12 46 14 81 13 43 kW...

Страница 12: ...3 2 3 2 3 2 604B030 Return Air F db CFM Standard Air Air Temperature Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 60 875 TC 9 4 8 7 11 9 10 9 14 4 13 2 16 3 14 9 17 2 15 6 kW 1 74 1 81 1 89 1 97...

Страница 13: ...5 604B036 Return Air F db CFM Standard Air Air Temperature Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 60 1100 TC 12 1 11 2 15 1 13 9 18 5 16 9 21 4 19 5 22 8 20 7 kW 2 25 2 34 2 43 2 49 2 51 1...

Страница 14: ...604B042 Return Air F db CFM Standard Air Air Temperature Entering Outdoor Coil F db at 70 rh 10 0 10 17 20 60 1225 TC 13 6 12 5 16 6 15 3 19 7 18 1 22 2 20 2 23 7 21 5 kW 2 42 2 51 2 64 2 76 2 81 140...

Страница 15: ...0 60 1400 TC 15 10 14 00 18 60 17 10 22 40 20 50 25 20 23 00 26 90 24 40 kW 2 66 2 76 2 87 2 95 3 00 1600 TC 15 40 14 30 18 90 17 40 22 70 20 90 25 60 23 30 27 30 24 80 kW 2 70 2 79 2 89 2 96 3 03 180...

Страница 16: ...0 rh 10 0 10 17 20 60 1500 TC 17 89 16 55 22 37 20 58 27 39 25 14 27 90 25 44 33 30 30 20 kW 3 14 3 33 3 56 3 71 3 76 1750 TC 18 44 17 06 22 91 21 08 28 07 25 77 32 32 29 47 34 25 31 06 kW 3 23 3 39 3...

Страница 17: ...and the heat required to defrost it NOTES 1 Ratings are net they account for the effects of the evaporator fan motor power and heat 2 Direct interpolation is permissible Do not extrapolate 3 The foll...

Страница 18: ...NG 1110 1025 970 1235 1175 1115 1400 1355 1280 COOLING DEHUMIDIFY 990 960 910 990 975 940 1125 1110 1085 HEAT PUMP COMFORT 1035 975 910 1160 1080 1020 1305 1275 1220 UNIT SIZE CFM ADJUST PIN SELECT LO...

Страница 19: ...800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 024 030 20 X 20 X 1 0 05 0 07 0 08 0 10 0 12 0 13 0 14 0 15 36 20 X 24 X 1 0 09 0 10 0 11 0 13 0 14 0 15 0 16 042 048 060...

Страница 20: ...R NEC FROM POWER SOURCE RETURN AIR TOP COVER NEC NATIONAL ELECTRICAL CODE TYPICAL PIPING AND WIRING ROOF RETURN AIR FLEXIBLE DUCT CEILING CONCENTRIC DIFFUSER BOX FIELD SUPPLIED SUPPLY AIR FLEXIBLE DUC...

Страница 21: ...evaporator airflow through the units should not exceed 450 cfm ton Minimum cooling airflow The minimum airflow is 350 cfm ton for cooling mode Airflow can be lower in certain modes when humidity remov...

Страница 22: ...20 8 26 30 36 1 41 7 54 2 62 5 72 2 83 3 35 7 35 7 58 3 61 7 68 2 73 2 80 8 87 8 103 4 113 8 126 0 139 9 45 45 80 80 90 90 100 100 125 125 150 150 208 230 3 60 187 253 15 4 88 0 0 9 6 8 3 8 5 0 7 5 1...

Страница 23: ...where a phase imbalance in supply volt age is greater than 2 Use the following formula to determine the percentage of voltage imbalance Voltage imbalance max voltage deviation from average voltage 10...

Страница 24: ...24 TYPICAL WIRING SCHEMATIC 230 1 60 SHOWN...

Страница 25: ...25 TYPICAL WIRING SCHEMATIC 208 230 3 60 SHOWN 1 3 2...

Страница 26: ...c heat When thermostat is satisfied contacts open deenergizing contactor and relay motors and heaters deenergize The IFM is controlled by the Easy Select board Defrost Defrost board DB is a time and t...

Страница 27: ...ction 5 Unit shall have a field supplied condensate trap C Fans 1 The indoor fan shall be variable speed motor and con trol as shown on equipment drawings 2 Fan wheel shall be made from steel and shal...

Страница 28: ...h can be preset to admit outdoor air for year round ventilation 5 Thermostat To provide for two stage heating and one stage cooling in addition manual or automatic changeover and indoor fan control 6...

Отзывы: