—12—
PERFORMANCE DATA (CONT)–STANDARD ECM INDOOR MOTOR
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-
10–20
HEATING EXTENDED PERFORMANCE TABLE
30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
604B030 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
875/0.06
1000/0.07
1125/0.08
Evaporator Air — Ewb (F)
62
63*
67
72
62
63*
67
72
62
63*
67
72
75
TC
27.9
28.6
30.7
33.6
28.8
29.4
31.6
34.5
29.3
30.0
32.2
35.2
SHC
24.1
20.0
20.6
16.8
26.0
21.2
22.1
17.8
27.0
22.6
23.5
18.7
kW
2.1
2.1
2.1
2.1
2.1
2.1
2.1
2.2
2.1
2.1
2.1
2.2
85
TC
26.9
27.5
29.5
32.3
27.6
28.1
30.2
33.1
28.3
28.7
30.8
33.7
SHC
23.8
19.5
20.3
16.4
25.6
20.8
21.7
17.4
26.5
22.1
23.1
18.3
kW
2.3
2.3
2.4
2.4
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
95
TC
25.6
26.2
28.2
30.8
26.3
26.8
28.8
31.5
27.0
27.3
29.3
32.0
SHC
23.1
19.1
19.9
16.0
24.7
20.5
21.3
16.9
26.2
21.7
22.6
17.8
kW
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
105
TC
24.3
24.7
26.6
29.2
25.1
25.3
27.2
29.7
25.9
25.7
27.5
30.1
SHC
22.4
18.6
19.3
15.4
23.8
19.9
20.8
16.3
24.4
21.1
22.1
17.2
kW
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
2.9
115
TC
22.8
23.2
24.9
27.3
23.8
23.6
25.3
27.7
24.5
24.0
25.7
28.1
SHC
21.7
18.0
18.8
14.8
22.3
19.3
20.2
15.7
23.7
20.5
21.5
16.6
kW
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
125
TC
21.4
21.4
24.9
27.3
23.8
23.6
25.3
27.7
24.5
24.0
25.7
28.1
SHC
20.7
17.3
18.8
14.8
22.3
19.3
20.2
15.7
23.7
20.5
21.5
16.6
kW
3.5
3.5
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
3.2
604B030
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-10
0
10
17
20
60
875
TC
9.4
8.7
11.9
10.9
14.4
13.2
16.3
14.9
17.2
15.6
kW
1.74
1.81
1.89
1.97
2.00
1000
TC
9.6
8.9
11.8
10.8
14.5
13.3
16.3
14.9
17.3
15.7
kW
1.72
1.84
1.86
1.92
1.96
1125
TC
9.6
8.9
12.0
11.1
14.5
13.3
16.4
15.0
17.5
15.9
kW
1.70
1.76
1.82
1.91
1.94
70
875
TC
8.9
8.2
11.4
10.5
14.0
12.8
15.9
14.5
16.5
15.0
kW
1.92
2.01
2.10
2.17
2.20
1000
TC
9.0
8.3
11.5
10.5
14.1
12.9
16.0
14.6
16.8
15.2
kW
1.91
1.98
2.06
2.13
2.16
1125
TC
9.0
8.4
11.5
10.6
14.9
13.7
16.4
15.0
17.5
15.9
kW
1.89
1.96
2.03
2.09
2.12
80
875
TC
8.2
7.6
10.8
9.9
13.5
12.4
15.3
13.9
15.7
14.3
kW
2.11
2.21
2.32
2.39
2.41
1000
TC
8.3
7.7
10.9
10.0
13.5
12.4
15.4
14.1
15.9
14.4
kW
2.09
2.19
2.28
2.35
2.37
1125
TC
8.2
7.6
10.9
10.0
13.6
12.5
15.6
14.2
16.2
14.7
kW
2.07
2.16
2.25
2.31
2.34
604B030
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30
40
47
50
60
60
875
TC
20.3
17.8
26.0
26.0
29.4
29.4
30.6
30.6
34.7
34.7
kW
2.13
2.27
2.35
2.38
2.51
1000
TC
20.6
18.1
26.1
26.1
29.4
29.4
30.7
30.7
34.8
34.8
kW
2.08
2.19
2.26
2.29
2.40
1125
TC
21.3
18.7
26.2
26.2
29.4
29.4
30.7
30.7
34.8
34.8
kW
2.05
2.13
2.20
2.23
2.31
70
875
TC
18.6
16.3
24.4
24.4
28.9
28.9
30.1
30.1
34.1
34.1
kW
2.29
2.49
2.59
2.62
2.76
1000
TC
19.4
17.0
25.5
25.5
29.0
29.0
30.2
30.2
34.2
34.2
kW
2.27
2.43
2.50
2.53
2.65
1125
TC
21.5
18.8
26.2
26.2
30.2
30.2
34.2
34.2
34.2
34.2
kW
2.22
2.36
2.43
2.46
2.56
80
875
TC
17.3
15.2
22.9
22.9
28.3
28.3
29.5
29.5
33.6
33.6
kW
2.50
2.71
2.86
2.88
3.04
1000
TC
17.6
15.4
23.6
23.6
28.5
28.5
29.7
29.7
33.7
33.7
kW
2.45
2.65
2.76
2.78
2.92
1125
TC
18.2
16.0
24.3
24.3
28.6
28.6
29.8
29.8
33.6
33.6
kW
2.43