PERFORMANCE DATA (CONT)–STANDARD ECM INDOOR MOTOR
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-
10–20
HEATING EXTENDED PERFORMANCE TABLE
30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
604B048 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
1260/0.06
1400/0.06
1600/0.08
Evaporator Air — Ewb (F)
62
63*
67
72
62
63*
67
72
62
63*
67
72
75
TC
45.0
45.8
49.6
54.7
46.7
47.3
51.2
56.3
48.1
48.7
52.5
57.8
SHC
39.3
32.0
33.4
27.2
42.6
34.3
35.8
28.9
45.8
36.8
38.4
30.6
kW
3.4
3.4
3.4
3.4
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.5
85
TC
42.8
43.6
47.2
52.1
44.3
44.9
48.6
53.5
45.6
46.1
49.9
54.8
SHC
38.2
30.9
32.3
26.2
41.3
33.2
34.7
27.7
44.3
35.5
37.3
29.4
kW
3.7
3.7
3.8
3.8
3.7
3.7
3.8
3.8
3.8
3.8
3.8
3.8
95
TC
40.6
41.3
44.7
49.4
41.8
42.4
46.0
50.7
44.2
43.7
47.0
51.8
SHC
36.9
29.8
31.2
25.2
39.9
32.0
33.6
26.7
43.0
34.6
36.1
28.3
kW
4.1
4.1
4.2
4.2
4.1
4.1
4.2
4.2
4.2
4.1
4.2
4.2
105
TC
38.2
38.9
42.1
46.4
39.6
39.8
43.1
47.6
41.5
40.8
44.0
48.5
SHC
35.7
28.7
30.1
24.0
38.3
30.7
32.3
25.5
40.0
33.2
34.8
27.0
kW
4.6
4.6
4.6
4.6
4.6
4.6
4.6
4.7
4.6
4.6
4.6
4.7
115
TC
35.7
36.3
39.3
43.3
38.2
37.1
40.1
44.2
38.7
37.9
40.8
45.0
SHC
34.4
27.5
28.9
22.9
35.7
29.5
31.0
24.3
38.2
31.8
33.5
25.8
kW
5.0
5.0
5.1
5.1
5.1
5.0
5.1
5.1
5.1
5.1
5.1
5.1
125
TC
33.4
33.4
36.2
39.4
34.6
34.1
36.9
40.5
36.1
34.8
37.5
41.2
SHC
32.1
26.2
27.6
21.5
33.8
28.2
29.7
22.9
35.6
30.2
31.9
24.4
kW
5.6
5.6
5.6
5.7
5.6
5.6
5.6
5.6
5.6
5.6
5.6
5.6
604B048
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-10
0
10
17
20
60
1400
TC
15.10
14.00
18.60
17.10
22.40
20.50
25.20
23.00
26.90
24.40
kW
2.66
2.76
2.87
2.95
3.00
1600
TC
15.40
14.30
18.90
17.40
22.70
20.90
25.60
23.30
27.30
24.80
kW
2.70
2.79
2.89
2.96
3.03
1800
TC
15.70
14.50
19.20
17.70
23.00
21.10
25.80
23.60
27.60
25.00
kW
2.67
2.79
2.88
2.94
3.01
70
1400
TC
14.40
13.30
17.90
16.50
21.80
20.00
24.60
22.50
26.40
23.90
kW
2.94
3.03
3.16
3.25
3.31
1600
TC
14.70
13.60
18.20
16.80
22.10
20.30
25.00
22.80
26.70
24.20
kW
2.97
3.05
3.17
3.26
3.31
1800
TC
15.00
13.90
18.60
17.10
22.40
20.60
25.30
23.00
27.00
24.50
kW
2.97
3.05
3.16
3.24
3.28
80
1400
TC
13.50
12.50
17.20
15.80
21.00
19.30
24.00
21.90
25.70
23.30
kW
3.23
3.34
3.47
3.58
3.66
1600
TC
13.90
12.80
17.50
16.10
21.40
19.70
24.40
22.20
26.10
23.70
kW
3.26
3.36
3.48
3.58
3.65
1800
TC
14.20
13.20
17.80
16.40
21.70
19.90
24.70
22.50
25.90
23.50
kW
3.26
3.35
3.46
3.56
3.36
604B048
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30
40
47
50
60
60
1400
TC
33.30
29.20
40.50
40.50
46.60
46.60
48.80
48.80
56.60
56.60
kW
3.15
3.32
3.48
3.54
3.78
1600
TC
33.70
29.50
41.00
41.00
47.10
47.10
49.30
49.30
57.30
57.30
kW
3.14
3.30
3.45
3.50
3.72
1800
TC
34.00
29.80
41.40
41.40
47.50
47.50
49.70
49.70
57.70
57.70
kW
3.11
3.25
3.38
3.43
3.61
70
1400
TC
32.60
28.60
39.70
39.70
45.50
45.50
47.60
47.60
55.50
55.50
kW
3.50
3.69
3.85
3.91
4.17
1600
TC
33.00
28.90
40.10
40.10
46.00
46.00
48.20
48.20
56.10
56.10
kW
3.48
3.65
3.80
3.86
4.10
1800
TC
33.30
29.20
40.50
40.60
46.50
46.50
48.80
48.80
56.60
56.60
kW
3.34
3.59
3.72
3.79
3.99
80
1400
TC
31.90
28.00
38.90
38.90
44.50
44.50
46.60
46.60
54.40
54.40
kW
3.87
4.09
4.26
4.33
4.60
1600
TC
32.30
26.30
39.30
39.30
45.10
45.10
47.10
47.10
55.00
55.00
kW
3.85
4.05
4.20
4.26
4.51
1800
TC
32.60
28.60
39.70
39.70
45.50
45.50
47.60
47.60
55.50
55.50
kW
3.80
3.98
4.12
4.17
4.40