—14—
PERFORMANCE DATA (CONT)–STANDARD ECM INDOOR MOTOR
COOLING EXTENDED PERFORMANCE TABLE
HEATING EXTENDED PERFORMANCE TABLE
-
10–20
HEATING EXTENDED PERFORMANCE TABLE
30–60
*At 75°F entering dry bulb—Tennessee Valley Authority [TVA] rating conditions; all others at 80°F entering dry bulb.
See Legend and Notes on page 17.
604B042 COOLING PERFORMANCE TABLE
Temp (F)
Outdoor Air
Entering
Condenser
Evaporator Air—CFM/BF
1100/0.06
1225/0.07
1400/0.08
Evaporator Air — Ewb (F)
62
63*
67
72
62
63*
67
72
62
63*
67
72
75
TC
39.6
40.4
43.4
47.6
40.5
41.2
44.2
48.4
41.5
42.1
45.1
49.4
SHC
33.5
27.6
28.6
23.4
35.4
29.0
30.0
24.3
37.9
30.8
31.9
25.6
kW
3.0
3.0
3.0
3.1
3.0
3.0
3.0
3.1
3.0
3.0
3.0
3.1
85
TC
37.9
38.7
41.5
45.5
38.7
39.4
42.3
46.3
39.7
40.2
43.2
47.2
SHC
32.8
26.9
27.8
22.7
34.6
28.2
29.2
23.6
37.0
30.0
31.1
24.8
kW
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
3.3
3.3
3.4
3.4
95
TC
36.2
36.8
39.6
43.4
36.9
37.5
40.3
44.1
37.8
38.2
41.0
44.9
SHC
32.0
26.1
27.0
21.9
33.8
27.4
28.4
22.8
35.9
29.1
30.3
24.0
kW
3.7
3.7
3.7
3.8
3.7
3.7
3.7
3.8
3.7
3.7
3.7
3.8
105
TC
34.2
34.8
37.4
41.0
34.9
35.4
38.0
41.6
36.0
36.0
38.7
42.3
SHC
31.0
25.2
26.2
21.1
32.7
26.5
27.6
22.0
34.3
28.3
29.4
23.2
kW
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
4.1
115
TC
32.1
32.6
35.0
38.4
32.8
33.1
35.5
38.9
34.0
33.7
36.1
39.5
SHC
30.0
24.3
25.2
20.2
31.4
25.6
26.6
21.0
32.8
27.3
28.5
22.2
kW
4.5
4.5
4.5
4.5
4.5
4.5
4.5
4.6
4.5
4.5
4.5
4.6
125
TC
29.8
30.1
32.3
35.3
30.6
30.5
32.7
35.7
31.7
31.0
33.2
36.2
SHC
28.6
23.2
24.2
19.1
29.6
24.5
25.5
20.0
30.6
26.1
27.3
21.1
kW
4.9
4.9
4.9
5.0
4.9
4.9
4.9
5.0
4.9
4.9
4.9
5.0
604B042
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
-10
0
10
17
20
60
1225
TC
13.6
12.5
16.6
15.3
19.7
18.1
22.2
20.2
23.7
21.5
kW
2.42
2.51
2.64
2.76
2.81
1400
TC
13.6
12.6
16.7
15.3
19.8
18.2
22.3
20.3
23.7
21.5
kW
2.39
2.48
2.60
2.70
2.75
1575
TC
13.7
12.7
16.8
15.5
19.8
18.2
22.3
20.4
23.8
21.6
kW
2.36
2.24
2.54
2.63
2.68
70
1225
TC
13.0
12.1
16.1
14.9
19.4
17.8
21.8
19.9
23.3
21.1
kW
2.70
2.80
2.93
3.05
3.11
1400
TC
13.2
12.2
16.2
14.9
19.4
17.8
21.9
20.0
23.4
21.2
kW
2.67
2.76
2.88
2.99
3.05
1575
TC
13.2
12.2
16.3
15.0
19.5
17.9
22.0
20.1
23.5
21.3
kW
2.64
2.72
2.82
2.93
2.98
80
1225
TC
12.8
11.9
16.0
14.7
19.0
17.4
21.4
19.6
22.9
20.8
kW
3.02
3.13
3.25
3.37
3.43
1400
TC
12.9
11.9
15.9
14.6
19.0
17.4
21.5
19.6
23.0
20.9
kW
2.99
2.97
2.83
3.31
3.37
1575
TC
13.0
12.0
15.8
14.6
19.1
17.6
21.6
19.7
23.1
21.0
kW
2.96
3.04
3.14
3.24
3.30
604B042
Return
Air (F db)
CFM (Standard Air)
Air Temperature Entering Outdoor Coil (F db at 70% rh)
30
40
47
50
60
60
1225
TC
29.2
25.6
35.6
35.6
40.8
40.8
42.0
42.0
49.8
49.8
kW
2.99
3.20
3.35
3.40
3.70
1400
TC
29.3
25.7
35.8
35.8
41.0
41.0
43.0
43.0
50.2
50.2
kW
2.91
3.09
3.24
3.31
3.55
1575
TC
29.4
25.8
36.0
36.0
41.3
41.3
43.2
43.2
50.6
50.6
kW
2.82
2.99
3.13
3.18
3.41
70
1225
TC
28.8
25.2
35.1
35.1
40.1
40.1
41.9
41.9
48.8
48.8
kW
3.32
3.57
3.74
3.81
4.11
1400
TC
28.9
25.3
35.3
35.3
40.3
40.3
42.1
42.1
49.1
49.1
kW
3.24
3.46
3.62
3.68
3.95
1575
TC
29.0
25.4
35.4
35.4
40.5
40.5
42.4
42.4
49.5
49.5
kW
3.16
3.35
3.49
3.56
3.79
80
1225
TC
28.4
24.9
34.6
34.6
39.5
39.5
41.3
41.3
47.9
47.9
kW
3.68
3.97
4.14
4.22
4.55
1400
TC
28.5
25.0
34.7
34.7
39.7
39.7
41.5
41.5
48.2
48.2
kW
3.59
3.85
4.01
4.08
4.38
1575
TC
28.6
25.1
34.9
34.9
39.9
39.9
41.7
41.7
48.6
48.6
kW
3.51
3.73
3.88
3.94
4.21