243
PERFORMANCE DATA (cont)
COOLING CAPACITIES — STANDARD UNITS (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
Where: hewb = Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4. Use chart below for bypass factor.
581A300 (25 Tons)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
7,500/0.05
8,250/0.06
9,500/0.07
Evap Air — Ewb (F)
54
58
62
67
72
76
80
54
58
62
67
72
76
80
54
58
62
67
72
76
80
60
TC
287
296
304
331
359
385
408
297
304
310
336
367
390
414
311
315
319
345
375
398
421
SHC
287
274
261
220
178
145
110
297
285
273
229
185
148
110
311
303
294
246
194
152
111
kW
15.5
15.7
15.9
16.5
17.3
17.9
18.6
15.7
15.9
16
16.7
17.4
18.1
18.7
16
16.1
16.2
16.9
17.6
18.3
19
70
TC
279
286
293
318
345
367
392
288
293
298
323
350
372
397
301
303
306
329
357
381
403
SHC
279
267
255
214
173
139
105
288
278
268
224
178
142
105
301
294
287
239
188
147
105
kW
17
17.2
17.3
18
18.7
19.3
20
17.2
17.3
17.5
18.1
18.8
19.4
20.1
17.5
17.6
17.7
18.3
19
19.7
20.3
75
TC
275
281
287
311
338
360
383
283
288
293
316
343
365
388
296
298
300
323
349
372
394
SHC
275
264
252
212
170
136
102
283
274
265
221
176
139
103
296
290
284
237
185
144
103
kW
17.9
18.1
18.2
18.8
19.5
20.1
20.8
18.1
18.2
18.4
18.9
19.7
20.3
20.9
18.4
18.5
18.5
19.1
19.8
20.5
21.1
85
TC
267
272
277
299
324
345
366
274
278
282
304
329
350
370
286
287
289
311
334
355
375
SHC
267
257
247
207
165
131
97.3
274
267
259
216
171
134
97.3
286
282
278
232
180
139
97.3
kW
19.8
19.9
20
20.6
21.2
21.8
22.4
20
20.1
20.1
20.7
21.4
22
22.6
20.2
20.3
20.3
20.9
21.5
22.1
22.7
95
TC
259
263
267
288
311
331
350
267
270
273
293
315
335
354
278
279
281
299
322
340
358
SHC
259
251
242
202
160
126
92.5
267
261
255
212
166
129
92.5
278
276
273
227
175
134
92.4
kW
22.1
22.2
22.3
22.8
23.4
23.9
24.5
22.3
22.4
22.5
22.9
23.5
24
24.6
22.6
22.6
22.6
23.1
23.6
24.2
24.7
105
TC
253
256
260
279
301
318
335
260
262
264
282
304
322
338
269
270
270
287
308
326
342
SHC
253
246
239
198
156
122
87.9
260
255
250
207
162
125
87.8
269
268
267
222
171
129
87.7
kW
24.9
25
25.1
25.4
25.9
26.4
26.9
25.1
25.1
25.1
25.5
26
26.5
26.9
25.2
25.2
25.2
25.6
26.1
26.6
27.1
115
TC
246
249
252
270
291
305
320
253
255
256
274
294
309
323
262
262
262
277
298
312
328
SHC
246
240
235
195
152
118
83.5
253
250
246
204
158
121
83.4
262
261
261
218
167
125
83.9
kW
28.1
28.2
28.3
28.6
29
29.3
29.6
28.3
28.3
28.3
28.6
29
29.4
29.7
28.4
28.4
28.4
28.7
29.1
29.4
29.9
125
TC
238
240
242
259
279
293
305
245
246
246
262
281
295
310
253
253
253
266
284
298
313
SHC
238
234
230
190
148
114
79.2
245
243
240
199
153
116
79.7
253
253
253
214
162
120
79.9
kW
31.6
31.7
31.7
32
32.4
32.6
32.9
31.8
31.8
31.8
32.1
32.4
32.7
33
31.9
31.9
31.9
32.1
32.5
32.7
33.1
581A300 (25 Tons) (cont)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
10,750/0.08
12,000/0.09
Evap Air — Ewb (F)
54
58
62
67
72
76
80
54
58
62
67
72
76
80
60
TC
322
324
327
351
380
404
429
332
333
334
357
386
410
432
SHC
322
317
313
260
203
157
111
332
330
329
276
212
162
111
kW
16.3
16.4
16.4
17
17.8
18.5
19.2
16.6
16.6
16.6
17.2
18
18.6
19.2
70
TC
311
312
314
336
364
386
408
320
320
321
341
368
392
414
SHC
311
308
305
255
198
151
105
320
320
319
269
206
156
106
kW
17.8
17.8
17.9
18.4
19.2
19.8
20.5
18
18
18
18.5
19.3
20
20.6
75
TC
306
307
308
329
356
378
398
315
315
315
333
360
383
404
SHC
306
304
302
252
195
149
103
315
314
314
266
203
153
103
kW
18.7
18.7
18.7
19.3
20
20.6
21.3
18.9
18.9
18.9
19.4
20.1
20.8
21.4
85
TC
295
296
297
315
340
362
379
303
303
303
319
344
365
385
SHC
295
295
294
246
189
144
97.3
303
303
303
260
198
148
97.9
kW
20.5
20.5
20.5
21
21.7
22.3
22.8
20.7
20.7
20.7
21.1
21.8
22.4
23
95
TC
286
286
286
303
327
344
364
293
293
294
307
330
347
366
SHC
286
286
286
241
185
138
93
293
293
294
255
193
142
92.8
kW
22.7
22.7
22.7
23.1
23.8
24.3
24.9
22.9
22.9
22.9
23.2
23.9
24.4
24.9
105
TC
277
277
277
290
312
329
347
284
284
285
295
314
331
352
SHC
277
277
277
236
179
133
88.3
284
284
285
250
188
137
88.7
kW
25.4
25.4
25.4
25.7
26.2
26.7
27.2
25.5
25.6
25.6
25.8
26.3
26.7
27.3
115
TC
268
269
269
281
300
315
332
274
274
275
283
303
317
333
SHC
268
269
269
232
176
129
84.4
274
274
275
245
184
133
84
kW
28.5
28.5
28.5
28.7
29.2
29.5
30
28.6
28.6
28.6
28.8
29.2
29.5
30
125
TC
260
259
259
269
287
300
316
265
265
264
271
289
302
318
SHC
260
259
259
227
171
125
80
265
265
264
240
179
129
80.1
kW
32
32
32
32.1
32.5
32.8
33.2
32.1
32.1
32.1
32.2
32.5
32.8
33.3
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
—
Compressor Motor Power Input
ldb
—
Leaving Dry-Bulb
lwb
—
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
tldb = tedb –
sensible capacity (Btuh)
1.10 x cfm
hlwb = hewb –
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
CFM
ENTERING WET-BULB (F)
54
58
62
67
72
76
80
Bypass Factor
7,500
0.407
0.208
0.097
0.104
0.123
0.000
0.000
8,250
0.443
0.256
0.110
0.112
0.128
0.000
0.000
9,500
0.494
0.324
0.138
0.123
0.136
0.000
0.000
10,750
0.536
0.380
0.181
0.134
0.145
0.000
0.000
12,000
0.571
0.427
0.232
0.145
0.154
0.000
0.000
581
A155
, 18
0
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...