GUIDE SPECIFICATIONS — 580F036-151 AND 581B036-150 (cont)
23. Return Air Enthalpy Sensor (EconoMi$er IV or
EconoMi$er2):
The return air enthalpy sensor shall be used with the
EconoMi$er IV or EconoMi$er2 device. When used
in conjunction with an outdoor air enthalpy sensor,
the EconoMi$er IV or EconoMi$er2 device will pro-
vide differential enthalpy control.
24. Return Air Temperature Sensor (EconoMi$er IV or
EconoMi$er2):
The return air temperature sensor shall be used with
the EconoMi$er IV or EconoMi$er2 device. When
used in conjunction with the standard outdoor air tem-
perature sensor, the EconoMi$er IV or EconoMi$er2
device will provide differential temperature control.
25. Indoor Air Quality (CO
2
) Sensor (EconoMi$er2):
a. Shall have the ability to provide demand ventila-
tion indoor air quality (IAQ) control through the
EconoMi$er2 with an IAQ sensor.
b. The IAQ sensor shall be available in duct mount,
wall mount, and wall mount with LED display. The
set point shall have adjustment capability.
c. Requires EconoMi$er2 control option.
26. Indoor Air Quality (CO
2
) Room Sensor (EconoMi$er
IV):
Sensor shall have the ability to provide demand ven-
tilation control through the EconoMi$er IV. The IAQ
sensor shall be wall mounted with an LED display in
parts per million. The set point shall have adjustment
capability.
27. Return Air CO
2
Sensor (EconoMi$er IV):
Sensor shall have the ability to provide demand ven-
tilation control through the EconoMi$er IV. The IAQ
sensor shall be duct mounted. The set point shall
have adjustment capability.
28. Gas Heat options (sizes 004-006):
a. Single-stage gas heat shall be provided in lieu of
two-stage heat.
b. NOx reduction shall be provided to reduce nitrous
oxide emissions to meet the California Air Quality
Management NOx requirement of 40 nanograms/
joule or less.
c. Primary tubes on low NOx units shall be 409
stainless steel. Other components shall be alumi-
nized steel.
29. Ultraviolet Germicidal Lamps:
Ultraviolet germicidal lamps are designed to elimi-
nate odor causing mold and fungus that may
develop in the wet area of the evaporator section of
the unit. The high output, low temperature germicidal
lamps are field installed in the evaporator section of
the unit, aimed at the evaporator coil and conden-
sate pan. The short wavelength ultraviolet light inhib-
its and kills mold, fungus and microbial growth. The
lamps have an output rating at 45F in 400 fpm air-
flow of 120 microwatts/cm
2
at 1 meter.
30. Perfect Humidity™ Adaptive Dehumidification Sys-
tem (581B only):
a. The Perfect Humidity dehumidification system
shall be factory-installed in the rooftop units, and
shall provide greater dehumidification of the
occupied space by two modes of dehumidification
operations beside its normal design cooling
mode:
1) Subcooling mode further subcools the hot liq-
uid refrigerant leaving the condenser coil when
both temperature and humidity in the space
are not satisfied.
2) Hot gas reheat mode shall mix a portion of the
hot gas from the discharge of the compressor
with the hot liquid refrigerant leaving the con-
denser coil to create a two-phase heat transfer
in the system, resulting in a neutral leaving-air
temperature when only humidity in the space is
not satisfied.
b. The system shall consist of a subcooling/reheat
dehumidification coil located downstream of the
standard evaporator coil. This dehumidification
coil is a two-row coil with the exception of the 036
unit, which has a one-row coil.
c. The system shall include crankcase heater(s) for
the scroll compressor(s).
d. The system shall include a low outdoor air tem-
perature switch to lock out both subcooling and
hot gas reheat mode when the outdoor-air tem-
perature is below 40 F.
e. The system shall include a Motormaster® low
ambient control to ensure the normal design cool-
ing mode capable of down to 0° F low ambient
operation.
f. The system shall include a low-pressure switch
on the suction line to ensure low pressure start-up
of hot gas reheat mode at lower outdoor tempera-
ture condition.
g. The system operation may be controlled by a
field-installed, wall-mounted humidistat. The
dehumidification circuit will then operate only
when needed. Field connections for the humidis-
tat are made in the low-voltage compartment of
the unit control box. The sensor can be set for
any level between 55% and 80% relative humid-
ity.
h. The system shall include a thermostatic expan-
sion valve (TXV) to ensure a positive superheat
condition and a balance of pressure drop.
i. For units with two compressors (sizes 090-150),
depending on the conditions required to maintain
the space set points, one or both compressors
can operate in subcooling mode, one compressor
could operate in subcooling mode while the other
operates in hot gas reheat mode, or one or both
compressors can operate in hot gas reheat mode.
31. Humidistat:
Field-installed, wall-mounted humidistat is used to
control activation of the dehumidification package.
The humidistat can be set for humidity levels
between 20% and 80% relative humidity.
32. Hinged Panel Option:
Hinged panel option provides hinged access panels
for the filter, compressor, evaporator fan, and control
box areas. Filter hinged panels permit tool-less entry
for changing filters. Each hinged panel is perma-
nently attached to the rooftop unit.
33. Louvered Hail Guard:
The hail guard shall protect the entire outdoor coil
surface from direct or indirect (from adjacent sur-
faces) hail damage. Hail guard shall have a pressure
drop of 2%.
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...