PERFORMANCE DATA (cont)
COOLING CAPACITIES — STANDARD UNITS (cont)
LEGEND
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
tlwb = Wet-bulb temperature corresponding to enthalpy of air leaving evapo-
rator coil (hlwb)
Where: hewb = Enthalpy of air entering evaporator coil
3. The SHC is based on 80 F edb temperature of air entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Interpolation is permissible.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
4. Use chart below for bypass factor.
581A240 (20 Tons)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
6,000/0.04
7,000/0.05
8,000/0.05
Evap Air — Ewb (F)
54
58
62
67
72
76
80
54
58
62
67
72
76
80
54
58
62
67
72
76
80
60
TC
235
242
248
267
288
306
323
247
251
256
274
296
312
330
257
259
262
279
300
317
333
SHC
235
224
212
178
143
115
86.6
247
238
230
191
151
119
87
257
251
246
204
159
123
86.7
kW
11.5
11.6
11.7
12
12.4
12.7
13
11.7
11.8
11.8
12.1
12.5
12.8
13.1
11.9
11.9
11.9
12.2
12.6
12.9
13.1
70
TC
231
237
242
261
282
300
316
242
246
250
268
289
305
323
252
254
256
273
293
310
326
SHC
231
220
209
175
141
113
84.5
242
234
227
189
149
117
84.9
252
247
243
201
156
120
84.6
kW
13.1
13.2
13.3
13.6
14
14.3
14.6
13.3
13.3
13.4
13.7
14.1
14.4
14.8
13.4
13.5
13.5
13.8
14.2
14.5
14.8
75
TC
228
234
239
257
278
295
311
239
243
246
264
285
301
318
249
250
252
269
290
305
322
SHC
228
218
208
174
139
112
83.1
239
232
225
187
147
115
83.6
249
245
241
199
155
119
83.5
kW
13.9
14
14.1
14.5
14.9
15.2
15.6
14.1
14.2
14.2
14.6
15
15.3
15.7
14.3
14.3
14.4
14.7
15.1
15.4
15.8
85
TC
223
227
231
250
270
287
303
234
236
238
256
277
292
310
243
244
245
261
282
296
314
SHC
223
213
204
171
136
109
80.5
234
227
221
184
144
112
80.9
243
240
236
196
152
116
81.3
kW
15.6
15.7
15.8
16.2
16.6
17.1
17.4
15.8
15.9
15.9
16.3
16.8
17.2
17.6
16
16.1
16.1
16.5
16.9
17.3
17.7
95
TC
216
219
223
241
260
277
292
226
228
230
247
267
282
298
235
235
236
251
272
285
303
SHC
216
208
200
167
132
105
77.2
226
221
217
180
141
109
77.7
235
233
231
192
148
112
78
kW
17.4
17.5
17.6
18.1
18.6
19
19.4
17.7
17.7
17.8
18.2
18.7
19.1
19.6
17.9
17.9
17.9
18.3
18.9
19.2
19.7
105
TC
208
211
214
231
249
265
279
218
219
220
236
256
270
285
226
226
226
241
260
273
290
SHC
208
202
195
163
129
101
73.6
218
215
212
176
137
105
74
226
226
225
188
145
108
74.4
kW
19.3
19.4
19.5
20
20.6
21
21.5
19.6
19.6
19.7
20.2
20.8
21.2
21.6
19.9
19.9
19.9
20.3
20.9
21.3
21.8
115
TC
200
202
204
220
237
253
266
209
210
210
225
243
257
271
217
217
217
229
248
260
275
SHC
200
195
190
158
124
97.2
69.5
209
207
206
171
132
101
70
217
217
217
183
140
104
70.4
kW
21.3
21.4
21.5
22
22.7
23.2
23.6
21.7
21.7
21.7
22.2
22.9
23.3
23.8
21.9
21.9
21.9
22.4
23
23.4
23.9
125
TC
191
192
193
208
224
239
251
199
199
200
212
230
243
255
207
207
206
216
232
245
257
SHC
191
188
185
153
120
92.8
65.3
199
199
199
166
128
96.4
65.7
207
207
206
178
135
99.8
65.5
kW
23.5
23.5
23.6
24.2
24.8
25.4
25.9
23.8
23.8
23.8
24.4
25
25.5
26
24.1
24.1
24.1
24.5
25.1
25.7
26.1
581A240 (20 Tons) (cont)
Temp (F)
Air Ent
Cond
Evap Air — Cfm/BF
9,000/0.06
10,000/0.07
Evap Air — Ewb (F)
54
58
62
67
72
76
80
54
58
62
67
72
76
80
60
TC
265
266
267
284
305
321
338
272
272
272
287
307
325
340
SHC
265
262
260
216
166
126
87
272
271
271
227
173
130
86.7
kW
12
12
12
12.3
12.7
12.9
13.2
12.1
12.1
12.1
12.4
12.7
13
13.3
70
TC
260
261
261
277
298
315
331
266
267
267
281
301
317
333
SHC
260
258
256
213
164
124
85
266
267
267
225
171
127
84.7
kW
13.6
13.6
13.6
13.9
14.3
14.6
14.9
13.7
13.7
13.7
14
14.3
14.6
15
75
TC
256
257
258
273
294
310
326
263
263
263
277
296
312
327
SHC
256
255
254
211
162
123
83.7
263
263
263
223
169
126
83.4
kW
14.5
14.5
14.5
14.8
15.2
15.5
15.8
14.6
14.6
14.6
14.9
15.2
15.6
15.9
85
TC
250
250
250
265
285
301
316
257
256
256
268
287
303
317
SHC
250
250
249
208
159
120
81
257
256
256
220
166
123
80.7
kW
16.2
16.2
16.2
16.5
17
17.4
17.7
16.4
16.4
16.4
16.6
17
17.4
17.7
95
TC
242
242
242
255
274
288
304
248
248
248
258
276
292
306
SHC
242
242
242
204
155
116
77.8
248
248
248
215
162
120
77.6
kW
18.1
18.1
18.1
18.4
18.9
19.3
19.7
18.3
18.3
18.2
18.5
19
19.4
19.7
105
TC
233
233
233
244
263
275
291
239
239
239
247
264
279
291
SHC
233
233
233
200
152
112
74.2
239
239
239
211
158
116
73.9
kW
20.1
20.1
20.1
20.4
21
21.4
21.8
20.3
20.2
20.2
20.5
21
21.5
21.8
115
TC
223
223
223
232
250
262
276
229
228
228
235
251
263
276
SHC
223
223
223
195
147
108
70.2
229
228
228
206
154
111
69.9
kW
22.2
22.1
22.1
22.5
23.1
23.5
24
22.3
22.3
22.3
22.6
23.1
23.6
24
125
TC
213
212
212
219
234
247
258
218
217
217
222
235
248
259
SHC
213
212
212
189
142
103
65.4
218
217
217
200
148
106
65.2
kW
24.3
24.3
24.3
24.6
25.2
25.7
26.2
24.5
24.5
24.5
24.7
25.3
25.8
26.2
BF
—
Bypass Factor
Edb —
Entering Dry-Bulb
Ewb —
Entering Wet-Bulb
kW
—
Compressor Motor Power Input
ldb
—
Leaving Dry-Bulb
lwb
—
Leaving Wet-Bulb
SHC —
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
tldb = tedb –
sensible capacity (Btuh)
1.10 x cfm
hlwb = hewb –
total capacity (Btuh)
4.5 x cfm
BYPASS
FACTOR
(BF)
ENTERING AIR DRY-BULB TEMP (F)
79
78
77
76
75
under 75
81
82
83
84
85
over 85
Correction Factor
.05
1.04
2.07
3.11
4.14
5.18
Use formula
shown below.
.10
.98
1.96
2.94
3.92
4.90
.20
.87
1.74
2.62
3.49
4.36
.30
.76
1.53
2.29
3.05
3.82
CFM
ENTERING WET-BULB (F)
54
58
62
67
72
76
80
Bypass Factor
6,000
0.386
0.197
0.108
0.109
0.134
0.000
0.000
7,000
0.444
0.260
0.131
0.121
0.138
0.000
0.000
8,000
0.492
0.321
0.163
0.133
0.145
0.000
0.000
9,000
0.532
0.375
0.205
0.146
0.154
0.000
0.000
10,000
0.566
0.420
0.245
0.158
0.164
0.000
0.000
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...