PERFORMANCE DATA (cont)
COOLING CAPACITIES — UNITS WITH PERFECT HUMIDITY™ ADAPTIVE DEHUMIDIFICATION SYSTEM OPTION (cont)
LEGEND
*Negative SHC value indicates that the air entering the coil is being heated.
NOTES:
1. Direct interpolation is permissible. Do not extrapolate.
2. The following formulas may be used:
Where: h
ewb
= Enthalpy of air entering evaporator coil.
3. The SHC is based on 80 F edb temperature of air entering evaporator
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
581B120 (10 TONS) — SUBCOOLING MODE
Temp (F)
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Cfm/BF
3000/0.03
3200/0.03
4000/0.04
5000/0.04
Air Entering Evaporator — Ewb (F)
72
67
62
72
67
62
72
67
62
72
67
62
75
TC
134.3
122.5
111.4
135.8
124.3
113.0
138.4
129.5
123.5
143.3
136.5
130.2
SHC
60.0
76.1
93.7
61.3
79.1
97.4
68.0
89.5
109.4
75.2
100.9
123.3
kW
7.03
6.84
6.72
7.01
6.89
6.77
7.10
6.92
6.77
7.15
7.03
6.88
85
TC
127.6
115.4
104.6
128.9
118.1
107.0
132.5
121.5
116.6
137.2
128.0
122.9
SHC
51.5
68.8
87.2
53.9
72.0
91.2
61.0
82.7
102.4
68.6
93.6
115.9
kW
7.96
7.86
7.59
7.94
7.78
7.51
8.02
7.84
7.69
8.02
7.94
7.79
95
TC
120.9
108.3
97.8
121.9
111.8
101.0
126.5
113.4
109.7
131.1
119.4
115.5
SHC
43.0
61.5
80.6
46.5
64.8
84.9
53.9
75.9
95.4
62.0
86.2
108.4
kW
8.88
8.87
8.46
8.86
8.66
8.26
8.94
8.76
8.60
8.89
8.85
8.69
105
TC
112.0
99.9
90.4
113.1
103.2
93.4
117.2
105.0
100.7
122.1
110.5
105.9
SHC
36.1
54.1
73.8
38.8
57.8
78.9
45.6
68.2
86.8
53.0 78.3
99.7
kW
10.0
10.0
9.6
10.0
9.8
9.5
10.1
9.9
9.8
10.1
10.0
9.9
115
TC
103.0
91.5
83.1
104.3
94.6
85.9
107.8
96.7
91.7
113.0
101.6
96.4
SHC
29.2
46.7
66.9
31.2
50.7
72.9
37.3
60.6
78.3
44.0
70.3
90.9
kW
11.2
11.1
10.8
11.2
11.0
10.7
11.3
11.1
11.0
11.3
11.2
11.1
125
TC
94.1
83.1
75.7
95.5
86.0
78.3
98.5
88.3
82.7
104.0
92.7
86.8
SHC
22.3
39.3
60.1
23.5
43.7
66.8
29.0
52.9
69.7
35.0
62.4
82.2
kW
12.35
12.15
11.94
12.38
12.13
11.92
12.48
12.27
12.25
12.53
12.30
12.28
581B120 (10 TONS) — HOT GAS REHEAT MODE*
Temp (F)
Air Ent
Condenser
(Edb)
Air Entering Evaporator — Ewb (F)
75 Dry Bulb
62.5 Wet Bulb
(50% Relative)
75 Dry Bulb
64 Wet Bulb
(55% Relative)
75 Dry Bulb
65.3 Wet Bulb
(60% Relative)
Air Entering Evaporator — Cfm
3000
3200
4000
5000
3000
3200
4000
5000
3000
3200
4000
5000
80
TC
49.15
50.16
53.80
57.72
51.04
52.08
55.86
59.94
52.67
53.74
57.65
61.86
SHC
9.58
12.02
20.74
29.89
2.88
5.29
13.88
22.89
–2.92
-0.55
7.93
16.83
kW
7.39
7.38
7.38
7.37
7.45
7.45
7.44
7.43
7.50
7.50
7.49
7.49
75
TC
49.60
50.61
54.30
58.28
51.45
52.50
56.33
60.45
53.05
54.14
58.09
62.34
SHC
10.07
12.38
20.60
29.23
3.82
6.09
14.20
22.70
–1.60
0.64
8.65
17.05
kW
7.56
7.56
7.55
7.55
7.63
7.63
7.62
7.62
7.69
7.69
7.69
7.68
70
TC
50.04
51.07
54.81
58.83
51.86
52.92
56.80
60.96
53.43
54.53
58.52
62.82
SHC
10.56
12.73
20.47
28.58
4.75
6.89
14.52
22.52
–0.28
1.83
9.36
17.26
kW
7.73
7.73
7.72
7.72
7.81
7.81
7.81
7.80
7.89
7.88
7.88
7.87
60
TC
50.93
51.98
55.81
59.93
52.68
53.77
57.73
61.99
54.20
55.32
59.39
63.77
SHC
11.54
13.44
20.19
27.28
6.62
8.49
15.16
22.15
2.36
4.21
10.79
17.70
kW
8.07
8.07
8.07
8.06
8.18
8.18
8.17
8.17
8.27
8.27
8.26
8.26
50
TC
51.82
52.90
56.81
61.03
53.50
54.62
58.66
63.01
54.96
56.10
60.26
64.73
SHC
12.53
14.14
19.92
25.98
8.50
10.09
15.80
21.78
5.00
6.58
12.22
18.14
kW
8.42
8.42
8.41
8.41
8.54
8.54
8.54
8.54
8.66
8.65
8.65
8.65
40
TC
52.71
53.81
57.82
62.13
54.32
55.46
59.59
64.04
55.72
56.89
61.13
65.69
SHC
13.51
14.85
19.64
24.67
10.37
11.70
16.43
21.41
7.64
8.96
13.65
18.58
kW
8.76
8.76
8.76
8.75
8.91
8.91
8.91
8.90
9.04
9.04
9.04
9.03
BF
—
Bypass Factor
Edb
—
Entering Dry Bulb
Ewb
—
Entering Wet Bulb
kW
—
Compressor Motor Power Input
SHC
—
Sensible Heat Capacity (1000 Btuh) Gross
TC
—
Total Capacity (1000 Btuh) Gross
t
ldb
=
t
edb
–
sensible capacity (Btuh)
1.10 x cfm
t
lwb
=
Wet-bulb temperature corresponding to enthalpy of air
leaving evaporator coil (h
lwb
)
h
lwb
=
h
ewb
–
total capacity (Btuh)
4.5 x cfm
5
81B0
36-
15
0
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...