TYPICAL WIRING SCHEMATICS — 579F
(579F240, 208/230 V Shown) (cont)
AHA
—
Adjustable Heat Anticipator
BKR W/AT —
Breaker with Amp Turns
C
—
Contactor, Compressor
CB
—
Circuit Breaker
CC
—
Cooling Compensator
CLO
—
Compressor Lockout
COMP
—
Compressor Motor
CR
—
Control Relay
CT
—
Control Transformer
DM
—
Damper Motor
DU
—
Dummy Terminal
EQUIP
—
Equipment
FPT
—
Freeze Protection Thermostat
FU
—
Fuse
GND
—
Ground
HPS
—
High-Pressure Switch
HS
—
Hall Effect Sensor
HV
—
High Voltage
I
—
Ignitor
IDM
—
Induced-Draft Motor
IFC
—
Indoor-Fan Contactor
IFCB —
Indoor-Fan Circuit Breaker
IFM
—
Indoor-Fan Motor
IGC
—
Integrated Gas Unit Controller
L
—
Light
LED —
Light-Emitting Diode
LOR —
Lockout Relay
LPS —
Low-Pressure Switch
LS
—
Limit Switch
MGV —
Main Gas Valve
NEC —
National Electrical Code
OFC —
Outdoor-Fan Contactor
OFM —
Outdoor-Fan Motor
PL
—
Plug Assembly
PRI
—
Primary
RS
—
Rollout Switch
SN
—
Sensor
SR
—
Solenoid Relay
SW
—
Switch
TB
—
Terminal Block
TC
—
Thermostat Cooling
TH
—
Thermostat Heating
TRAN —
Transformer
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
Splice
Splice (Marked)
Splice (Field Supplied)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential
only; not to represent wiring.
NOTES:
1. Compressor and fan motors thermally protected; 3-phase motors protected against primary single-phasing conditions.
2. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
3. Jumpers are omitted when unit is equipped with economizer.
4. IFCB must trip amps is equal to or less than 140% full load amps.
5. On 208/230-v unit, TRAN1 is factory wired to ORN lead for 230-v power supply. If unit is to run on 208-v power supply, TRAN1
must be rewired. Disconnect the BLK wire on TRAN1 and connect wire to 208-v RED wire. Insulate 230-v ORN wire.
6. The CLO locks out the compressor to prevent short cycling on compressor overload and safety devices. Before replacing CLO,
check these devices.
7. Number(s) indicates the line location of used contacts. A bracket over (2) numbers signifies a single-pole, double-throw contact.
An underlined number signifies a normally closed contact. A plain (no line) number signifies a normally open contact.
LEGEND AND NOTES
LEGEND
a48-5655
579
F18
0
-300
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...