222
PERFORMANCE DATA (cont)
ACCESSORY/FIOP STATIC PRESSURE (in. wg)* — 580F180-300
LEGEND
*The static pressure must be added to external static pressure. The sum and the evaporator entering-air cfm should then be
used in conjunction with the Fan Performance tables to determine blower rpm and watts.
FAN RPM AT MOTOR PULLEY SETTINGS*
*Approximate fan rpm shown.
†Indicates standard drive package.
**Indicates alternate drive package.
††Due to belt and pulley size, pulley cannot be set to this number of turns open.
EVAPORATOR-FAN MOTOR PERFORMANCE
LEGEND
*Extensive motor and electrical testing on these units ensures that the full horse-
power (brake kilowatt) range of the motors can be utilized with confidence. Using
your fan motors up to the horsepower (brake kilowatt) ratings shown in this table
will not result in nuisance tripping or premature motor failure. Unit warranty will
not be affected.
NOTE:
All indoor-fan motors 5 hp and larger meet the minimum efficiency require-
ments as established by the Energy Policy Act of 1992 (EPACT) effective
October 24, 1997.
EVAPORATOR-FAN MOTOR EFFICIENCY
NOTE:
The EPACT (Energy Policy Act of 1992) regulates energy
requirements for specific types of indoor fan motors. Motors regulated
by EPACT include any general purpose, T-frame (three-digit, 143 and
larger), single-speed, foot mounted, polyphase, squirrel cage induction
motors of NEMA (National Electrical Manufacturers Association) design
A and B, manufactured for use in the United States. Ranging from 1 to
200 Hp, these continuous-duty motors operate on 230 and 460 volt,
60 Hz power. If a motor does not fit into these specifications, the motor
does not have to be replaced by an EPACT-compliant energy-efficient
motor. Variable-speed motors are exempt from EPACT compliance
requirements. Therefore, the indoor-fan motors for these units are
exempt from these requirements.
COMPONENT
CFM
4500
5000
5400
6000
7200
7500
9000
10,000
11,250
EconoMi$er IV and EconoMi$er2
0.040
0.050
0.060
0.070
0.090
0.100
0.110
0.120
0.140
FIOP
—
Factory-Installed Option
UNIT
580F
MOTOR PULLEY TURNS OPEN
0
1
/
2
1
1
1
/
2
2
2
1
/
2
3
3
1
/
2
4
4
1
/
2
5
5
1
/
2
6
180†
††
††
††
††
1021
1002
984
965
947
928
910
891
873
180**
††
††
††
††
1200
1178
1156
1134
1112
1091
1069
1047
1025
210†
††
††
1095
1077
1058
1040
1021
1002
984
965
947
928
910
210**
††
††
1287
1265
1243
1222
1200
1178
1156
1134
1112
1091
1069
240†
††
††
††
††
1151
1132
1114
1095
1077
1058
1040
1021
1002
240**
††
††
††
††
1369
1347
1325
1303
1281
1259
1237
1215
1193
300†
††
††
1283
1269
1247
1225
1203
1182
1160
1138
1116
1095
1066
300**
††
††
††
††
1551
1524
1497
1470
1443
1415
1388
1361
1332
UNIT
580F
UNIT
VOLTAGE
MAXIMUM
ACCEPTABLE
CONTINUOUS
BHP*
MAXIMUM
ACCEPTABLE
CONTINUOUS
BkW*
MAXIMUM
ACCEPTABLE
OPERATING
WATTS
MAXIMUM
AMP DRAW
180
208/230
6.13
4.57
5,180
15.8
460
7.9
575
6.0
210
208/230
5.90
4.40
5,180
15.8
460
7.9
575
6.0
240
208/230
8.70
6.49
7,915
22.0
460
9.50
7.08
8,640
13.0
575
8.70
6.49
7,915
10.0
300
208/230
10.20
7.61
9,510
28.0
460
11.80
8.80
11,000
14.6
575
10.20
7.61
9,510
13.0
BHP
—
Brake Horsepower
BkW
—
Brake Kilowatts
UNIT 580F
MOTOR EFFICIENCY
(%)
5 Hp
87.5
7.5 Hp
88.5
10 Hp
89.5
Содержание 581A
Страница 30: ...30 BASE UNIT DIMENSIONS 580F036 072 a48 8195 580F036 151 ...
Страница 31: ...31 BASE UNIT DIMENSIONS 580F073 a48 8196 580F036 151 ...
Страница 32: ...32 BASE UNIT DIMENSIONS 580F090 120 150 a48 8197 580F036 151 ...
Страница 33: ...33 BASE UNIT DIMENSIONS 580F091 103 121 151 a48 8198 580F036 151 ...
Страница 91: ...91 BASE UNIT DIMENSIONS 581B036 072 a48 8199 581B036 150 ...
Страница 93: ...93 ACCESSORY DIMENSIONS 581B036 072 a48 8201 581B036 150 ...
Страница 94: ...94 ACCESSORY DIMENSIONS 581B090 150 a48 8202 581B036 150 ...
Страница 139: ...139 TYPICAL WIRING SCHEMATICS 581B SIZES 036 150 581B090 460 3 60 Shown a48 8233 580F036 151 AND 581B036 150 ...
Страница 150: ...150 BASE UNIT DIMENSIONS 581C024 060 581C024 060 ...
Страница 198: ...198 TYPICAL WIRING SCHEMATICS 579F 579F240 208 230 V Shown a48 7929 ...
Страница 202: ...202 TYPICAL PIPING AND WIRING 579F180 300 579F180 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 205: ...205 BASE UNIT DIMENSIONS 580F180 210 a48 8203 580F180 300 ...
Страница 206: ...206 BASE UNIT DIMENSIONS 580F240 a48 8204 ...
Страница 207: ...207 BASE UNIT DIMENSIONS 580F300 a48 8205 580F180 300 ...
Страница 209: ...209 ACCESSORY DIMENSIONS 580F300 Vertical Roof Curbs 580F300 a48 7456 580F180 300 ...
Страница 227: ...227 TYPICAL PIPING AND WIRING 580F180 300 LEGEND NEC National Electrical Code b48 1258 580F180 300 ...
Страница 233: ...233 BASE UNIT DIMENSIONS 581A210 300 a48 8206 581A155 180 ...
Страница 237: ...237 ACCESSORY DIMENSIONS 581A210 300 a48 8234 581A155 180 ...
Страница 280: ...280 TYPICAL PIPING AND WIRING 581A 581A155 Shown LEGEND NEC National Electrical Code b48 1258 ...
Страница 297: ...297 ...